Veris Industries T SERIES Data Sheet

Temperature Monitoring | Duct Mount Temperature Sensors
T SERIES
Sensor Housed in Probe, Protects Against Corrosion
TDDA
TF
TG
TD
Cost effective
Cost-eective, high accuracy thermistors or RTDs available with or without a junction box
No calibration
No calibration required
APPLICATIONS
• Duct systems
• Industrial
Durable
Corrosion resistant stainless steel probe design
TK
Duct mount temperature sensors from Veris are pre-calibrated and housed in sturdy stainless steel probes. The devices are easy to install, durable, and highly accurate.
SPECIFICATIONS
3-wire: Linitemp
TEMPERATURE TRANSMITTER OPTION
Input Power 4 to 20 mA models: Loop powered Class 2,
12 to 30 Vdc only, 30 mA max; 0-5/0-10 V models: Class 2, 12 to 30 Vdc/24 Vac, 50/60 Hz, 15 mA max
Temp. Output 2-wire, loop powered 4 to 20 mA
3-wire, 0-5V/0-10Vdc
Sensor Type Solid-state, integrated circuit
Transmitter Accuracy ±0.5 °C (±.9 °F) typical*
Ranges Selectable 0 to 50 °C (32 to 122 °F) or
-40 to 50 °C (-40 to 122 °F)
LINITEMP OPTION
Input Power 5 to 30 Vdc
Output 10 mV/°C
Operating Temp -25 to 105 °C (-13 to 221 °F)
Calibration Offset 1.5 °C (2.7 °F) typical; 2.5 °C (4.5 °F) max. at
25 °C (77 °F)**
Offset over Temp
RESISTIVE OPTION
Operating Temp -25 to 105 °C (-13 to 221 °F)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
**
*Room temperature oset documented on each unit. **The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details.
1.8 °C (3.24 °F) typical; 3.0 °C (5.4 °F) max. over 0 to 70 °C (32 to 158 °F) range
2.0 °C (3.6 °F) typical, 3.5 °C (6.3 °F) max. over
-25 to 105 °C (-13 to 221 °F) range
TM
HQ0001874.H 0117
Temperature Monitoring | T Series
TD
Dimensional Drawing
1.5" (38 mm)
2"
(51 mm)
TF
Dimensional Drawing
2.3" (59 mm)
4.3"
(109 mm)
TK
Dimensional Drawing
0.25"
(6 mm)
1.1"
(28 mm)
TDDA
Dimensional Drawing
2.9"
0.25"Dia.
(74 mm)
(6 mm)
L
4.6"
(117 mm)
TG
Dimensional Drawing
0.25"Dia. (6 mm)
L
L
(74 mm)
(117 mm)
(51 mm)
2.9"
4.6"
(18 mm)
2.0"
0.7"
(18 mm)
2.0"
(51 mm)
Foam Gasket
2.5" x 2.5" (64 mm x 64 mm)
0.5" Dia. (13 mm.)
8.5"
(216 mm)
0.7"
Foam Gasket
2.5" x 2.5" (64 mm x 64 mm)
0.25"Dia. (6.3 mm)
L
ORDERING INFORMATION
RTD/Thermistor Models
Immersi on Probe
Enclosure
T
D = Duct K = Probe onl y (no mounting hardware) F = Duct wi th mounting box G = Duct wi th water resistant housing
* TK model i s 4 1/2” (115 mm) ** Not avai lable with TK mod el *** Not av ailable with W and Y high-accuracy thermistors
Transmitter Models
Output
TDDA
M = 4 to 20mA V = 5/10 V
Length “L”
B = 4" (102mm)* C = 6" (152mm) D = 8" (203mm) E = 12”(305mm)** F = 18”(457mm)** G = 24”(610mm)** K = 36”(914mm)**
Range
1 = -40 to 50 ° C (-40 to 122 °F) 2 = 0 to 50 °C (32 to 122 °F)
Sensor Type
B = 100R platin um, RTD C = 1k platinum, R TD D = 10k T2, Ther mistor E = 2.2k, T hermistor F = 3k, The rmistor G = 10k CPC, The rmistor H = 10k T3, Ther mistor I = 1k Balco (Nickel -iron) RTD J = 10k Dale, The rmistor K = 10k w/11k shunt , Thermistor M = 20k NTC, T hermistor N = 1800 ohm, Th ermistor P = 10mV/°C, Linit emp R = 10k US, Ther mistor S = 10k 3A221, Thermis tor T = 100k, Th ermistor U = 20k “D”, Ther mistor W = 10k T2 high acc uracy, Thermis tor Y = 10k T3 high acc uracy, Thermist or
Cal Certicate
0 = None 1 = 1 point Cal v alidation 2 = 2 point Cal v alidation
Example:
TDDA
Output
= Resisti ve Output
V 2 0
Calibration
Certicate
0 = None 1 = 1-point cal validation*** 2 = 2-point cal validation***
Examples:
D B D R0 2
T
HQ0001874.H 0117
TM
Loading...