![](/html/14/14bb/14bbef963d9515368343f35e44c48cfcbe427cc06a7e8982acc19598b626ee31/bg1.png)
Temperature Monitoring | VAV Discharge Temperature Sensors
TJ SERIES
VAV Discharge Air Sensor for
Reheat Applications
TJ
The TJ Series temperature sensors are highly accurate and cost effective,
with trouble-free installation. The sensor is encased in a sturdy
corrosion-resistant stainless steel probe. A variety of RTD/thermistor
sensor and probe length options are available for maximum versatility
in applications.
SPECIFICATIONS
Wiring 22 AWG; 2-wire: RTD/Thermistor
Probe Stainless steel
Operating Temp -25 to 105 °C (-13 to 221 °F)
LINITEMP OPTION
Input Power Class 2; 5 to 30 Vdc
Output 10mV/°C
Operating Temp -25 to 105 °C (-13 to 221 °F)
Calibration Offset
Offset over Temp
WARRANTY
Limited Warranty 5 years
1.5 °C (2.7 °F) typical; 2.5 °C (4.5 °F) max.
at 25 °C (77 °F)*
1.8 °C (3.24 °F) typical; 3.0 °C (5.4 °F) max.
over 0 to 70 °C (32 to 158 °F) range;
2.0 °C (3.6 °F) typical, 3.5 °C (6.3 °F) max.
over -25 to 105 °C (-13 to 221 °F) range
Easy installation
Stainless steel duct probe with
mounting ange
VAV systems
Installation-ready for VAV systems
and plenum areas
on job commissioning and
warranty service
…saves money
Application
flexibility
4” or 8” (102 mm or 204 mm) duct
probes
APPLICATIONS
• VAV reheat boxes
• Dual duct boxes
• Fan coils
• Prove that hot water valve
or electric heat is
functioning properly
Two wires
2-wire installation (optional quick
disconnect)…installs in minutes
Plenum rated
Plenum rated cable standard
• Check individual reheating
stages
• Check for hot water valve leaks
• Determine if damper actuators
are functioning on dual
duct boxes
Increased cable length aec ts the readings of lower resistance RTDs (100R platinum, RTD).
* Room temperature oset documented on each unit.
Note: See page 202 for thermistor table.
TM
HQ0001880.H 0117
![](/html/14/14bb/14bbef963d9515368343f35e44c48cfcbe427cc06a7e8982acc19598b626ee31/bg2.png)
DIMENSIONAL DRAWING
Temperature Monitoring | TJ Series
1.5"
(38 mm)
ORDERING INFORMATION
Probe
Length “L”
TJ
B = 4"(102mm)
D = 8"(204mm)
Sensor Type
B = 100R platin um, RTD
C = 1k platinum, R TD
D = 10k T2, Ther mistor
E = 2.2k, T hermistor
F = 3k, The rmistor
G = 10k CPC, The rmistor
H = 10k T3, Ther mistor
I = 1k Balco (Nickel -iron) RTD
J = 10k Dale, The rmistor
K = 10k w/11k shunt, Th ermistor
M = 20k NTC, T hermistor
N = 1800 ohm, Th ermistor
P = 10mV/°C, Linit emp
R = 10k US, Ther mistor
S = 10k 3A221, Thermis tor
T = 100k, Th ermistor
U = 20k “D”, Ther mistor
W = 10k T2 high acc uracy, Thermis tor
Y = 10k T3 high acc uracy, Thermist or
2.0"
(51 mm)
1.1"
(28 mm)
1.0"
(26 mm)
Output
R
= Resistive 0 = None
Cal Certicate
1 = 1-point ca l
validation*
2 = 2-point c al
validation*
Example:
TJ B D R 2 1
*Not avail able with W and Y high -accuracy the rmistors.
0.25"
(6.3 mm)
L
Option
0 = Standard 5 f t. cable, No QD s
1 = 1/4" Female Quick D isconnects (QD)
2 = 1/4” QDs with 8 ft. l eadwires
3 = 10 ft. cabl e, no QDs
Optional 1/4” female quick disconnect
HQ0001880.H 0117
TM