Installation Guide
Temperature
TS
TC
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
TM
TC/TS Series
Ceiling Mounted Temperature Sensors
Product Overview
TC and TS ceiling mounted temperature sensors monitor the temperature of the air in a room. The design is ideal for
large open spaces, such as open oce environments. The TC comes with a variable length temperature probe, and
the TS has a recessed design. Both models have resistive outputs compatible with building control systems. Both
models are warranted for a period of ve years.
Product Identification
Probe Length
TC
B = 4" (102mm)
C = 6" (152mm)
D = 8" (203mm)
E = 12" (305mm)
F = 18" (457mm)
G = 24" (610mm)
Sensor Type
B = 100R platinum, RTD
C = 1k platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k w/11k shunt, Thermistor
M = 20k NTC, Thermistor
Cal Certificate
N = 1800 ohm, Thermistor
R = 10k US, Thermistor
S = 10k 3A221, Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor
CC = 15k, Thermistor
0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation
Sensor Type
TS
B = 100R platinum, RTD
C = 1k platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
I = 1k Balco (Nickel-iron) RTD
J = 10k Dale, Thermistor
K = 10k w/11k shunt, Thermistor
M = 20k NTC, Thermistor
Specifications
Wiring
Housing
Cal Certificate
N = 1800 ohm, Thermistor
R = 10k US, Thermistor
S = 10k 3A221, Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor
CC = 15k, Thermistor
22 AWG; 2-wire RT D/ Thermistor
White ABS Plastic
(Black plastic available for TS, consult factory)
0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation
Z205468-0D Page 1 of 2 ©2013 Veris Industries 08131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
0.3"
(8 mm)
2"
(51 mm)
1.4"
(36 mm)
2.1"
(52 mm)
1.4"
(35 mm)
L
0.3"
(8 mm)
2"
(51 mm)
1.4"
(36 mm)
2.1"
(52 mm)
1.4"
(35 mm)
Temperature
TC/TS
TM
Dimensions
Installation
TC Model
TS Model
1. Drill a mounting hole using a 1 3/8” hole saw (1” conduit, electrical trade).
2. Pull the wires through the junction box or receptacle and connect them to the TC
or TS device.
DIGITAL CONTROL
Thermistor/RTD
3. Press t the TC/TS housing into the ceiling.
ORANGE
Z205468-0D Page 2 of 2 ©2013 Veris Industries 08131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.