Veris Industries PX3 SERIES Data Sheet

Pressure Monitoring | Dry Media Digital Pressure Transducer
PX3 SERIES
Differential Pressure/Air Velocity Transducer
PX3
The PX3 transducer can measure either air pressure or velocity
with the ip of a switch. The PX3 is available in three installation congurations: duct, panel or universal. Duct and panel models have two pressure and velocity options: 0-1” WC / 0-3,000 ft/min or 1-10” WC / 3,000-6,000 ft/min with four eld-selectable sub-ranges. The universal model comes in one pressure/velocity range: 0-10” WC / 0-7,000 ft/min with seven eld-selectable sub-ranges for pressure and eight for velocity. All variants are available with and without display. The PX3 has an IP65/NEMA 4 environmental rating and a 5-year limited warranty.
Reduce field failures
Excellent tolerance to overpressure & vibration reduces field failures
High accuracy
High accuracy digital sensor with seven selectable pressure and eight velocity sub-ranges, maintains calibration and reduces callbacks
Maintenance free
High reliability sensor technology for long-term, maintenance-free operation
APPLICATIONS
• Duct static pressure (Pressure mode)
• Building or room pressure (Pressure mode)
Reduce setup
Selectable ranges and scales reduce setup time and number of models to stock
Water-resistant housing
IP65/NEMA 4 housing allows for mounting in wash-down locations
Circuit protection
Circuit protection avoids damage due to incorrect input wiring
• Filter status (Pressure mode)
• Air flow measurement (Velocity mode)
SPECIFICATIONS
GENERAL
Media Compatibility
Input Power Three-wire Volt mode: 24 Vac or 12-30 Vdc*
Output Power Field-selectable:
PRESSURE RANGES
01 Pressure Range
02 Pressure Range
Dry air or inert gas
Two-wire mA mode: 12-30 Vdc*
2-wire, loop-powered 4-20 mA** (DC only, clipped and capped), 24 Vac/dc or 3-wire 0-5V/0-10V***
Pressure Mode: Unidirectional: 0.1/0.25/0.5/1.0 in. WC FS, switch selectable Bidirectional: ±0.1/±0.25/±0.5/±1.0 in. WC FS, switch selectable Unidirectional: 25 Pa/50 Pa/100 Pa/250 Pa, FS, switch selectable Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, FS, switch selectable
Velocity Mode: 500/1,000/2,000/3,000 ft/min
2.5/5/10/15 m/s
Pressure Mode: Unidirectional: 1.0/2.5/5.0/10 in. WC FS, switch selectable Bidirectional: ±1.0/±2.5/±5.0/±10 in. WC FS, switch selectable Unidirectional: 0.250 kPa/0.500 kPa/1.000 kPa/2.500 kPa, FS, switch selectable Bidirectional: ±0.250 kPa/±0.500kPa/±1.000 kPa/±2.500 kPa, FS, switch selectable
Velocity Mode: 3,000/4,000/5,000/6,000 ft/min 15/20/25/30 m/s
05 Pressure Range
SENSOR
Response Time
Mode Unidirectional or bidirectional, DIP switch selectable
Display (option)
Proof Pressure 3 psid (20.6 kPa)
Burst Pressure 5 psid (34.5 kPa)
Pressure Mode Accuracy
Velocity Mode Accuracy
Temperature Effect
Zero Drift (1-year)
Pressure Mode: Unidirectional: 0.1/0.25/0.5/1.0/2.5/5/10 in. WC FS, switch selectable Bidirectional: ±0.1/0.25/0.5/1.0/2.5/5/10 in. WC FS, switch selectable Unidirectional: 25Pa/50Pa/100Pa/250Pa/0.5kPa/1kPa/2.5kPa FS, switch selectable Bidirectional: ±25Pa/50Pa/100Pa/250Pa/0.5kPa/1kPa/2.5kPa FS, switch selectable
Velocity Mode: 500/1000/2000/3000/4000/5000/6000/7000 ft/min
2.5/5/10/15/20/25/30/35 m/s
Standard: T95 in 20 sec, Fast: T95 in 2 sec, DIP switch selectable
Pressure mode: Signed 3-1/2 digit LCD, indicates pressure, overrange indicator Velocity mode: Signed 4-1/2 digit LCD, indicates velocity, overrange indicator
±1% FS (combined linearity and hysteresis)
±90 ft/min (±0.45 m/s) plus 5% of measured value****
1” (250 Pa) models: 0.05%/°C; 10” (2.5 kPa) models: 0.01%/°C (Relative to 25 °C) 0 to 50 °C (32 to 122 °F)
1” (250 Pa) models: 2.0% max.; 10” (2.5 kPa) models: 0.5% max.
HQ0001827.F 0117
TM
HQ0007001.B 0118
Pressure Monitoring | PX Series
(188)
3 )
Pressure Monitoring | PX3 Series
SPECIFICATIONS (CONT.)
Zero Adjust Pushbutton auto-zero and digital input (2-pos terminal block)
Operating Environment
Altitude of Operation
Pollution Deg. 2
Humidity Range
Mounting Location
Fittings Brass barb; 0.24” (6.1 mm) o.d.
Environmental Rating
Flammability Rating
WARRANTY
Limited Warranty
AGENCY APPROVALS
EMC Conformance: EN 61000 -6-3 and A1 Class B, EN 61000-6-1. * Class 2/II power source. ** Minimum input voltage for 4 to 20 mA operation: 250 Ω loop = 12 Vdc; 500 Ω loop = 19 Vdc. *** Minimum load resistance for Volt operation: 5 k Ω. **** For measured values between 200 and 700 0 ft/min (1 and 35 m/s).
0 to 60 °C (32 to 140 °F)
0 to 3000 m
100% RH, non-condensing
For indoor use only.
IP65, NEMA 4
UL 94 5VA fire retardant ABS, plenum rated
5 years
WIRING DIAGRAM
2-wire, 4-20 mA Current Loop Output
Digital
Output
DIGITAL CONTROL
Return
V+
WIRING DIAGRAM
3-wire, 0-5 V/0-10 V Voltage Output
Digital
Output
DIGITAL CONTROL
V IN
POWER SOURCE
24 Vac/dc
-
-
+
RMT. ZERO
RMT. ZERO
PWR
ZERO
{
V+/PWR
ZERO
{
V-/GND
mA RTN
VOUT
1.000
1.000
0
1
7
2
6
3
5
4
0
1
7
2
6
3
5
4
DIMENSIONAL DRAWING
in. (mm)
1.6
(42)
3.5
(88)
3.1
(78)
4.4
(112)
ORDERING INFORMATION
Enclosure
PX3 PX3U
D = Duct P = Panel
Example:
Local Display Local Display
L = LCD Display X = No Display
LD X 01PX3
NIST Certificate NIST Certificate
N = NIST X = None
Range Range
01 = Pressure: 0 to 1 in . WC / 0 to 250 Pa Velocit y: 0 to 3000 ft/m in / 0 to 15 m/s 02 = Pressure: 0 to 10 in . WC/0 to 2500 Pa Velocit y: 0 to 6000 ft /min / 0 to 30 m/s
Example:
7.4
L = LCD Display X = No Display
L X 05PX3U
N = NIST X = None
0. (7
05 = Pressure : 0 to 10 in. WC / 0 to 250 0 Pa Velocit y: 0 to 7000 ft/mi n / 0 to 35 m/s
HQ0001827.F 0117
HQ0007001.B 0118
TM
Loading...