Veris Industries PWR SERIES Data Sheet

Pressure Monitoring | Wet Media Differential Pressure Remote Transducer
PWR SERIES
3-Wire Device, User-Selectable Output
PWR
The PWR Series remote wet media pressure transducers allow remote pressure sensing capability using existing plumbing runs. With no need to run plumbing lines all the way to the transducer, the installation time and cost is greatly reduced. Select either armored (6 ft.) or shielded (10 or 20 ft.) cable, depending on the application.
Armor cable
Armor cable or conduit connector minimizes the need for field customization
Lower costs
Remote probes reduce need for plumbing or bypass assemblies lower costs and reduced labor for installation
APPLICATIONS
• Monitoring and controlling pump differential pressure
• Chiller/boiler differential pressure drop
Zero calibration
Pushbutton zero calibration – no trim pots to adjust
maintain
accuracy and prevent callbacks with automatic zero calibration
Switch-selectable
Switch-selectable pressure ranges
fewer models to order
and stock
• CW/HW system differential pressure
SPECIFICATIONS
GENERAL
Input Power Class 2; 15 to 30 Vdc, 24 Vac nom. 50/60 Hz*
Maximum Current Draw DC: 125 mA; AC: 280 mA
Output 3-wire transmitter; user-selectable 4 to 20mA/
Status Indication Dual color LED
Surge Damping Electronic; 1 or 5 second averaging
Zero Adjust Pushbutton auto-zero and digital input
Fittings 1/4” NPT male thread, stainless steel 17-4 PH
SENSOR
Media Compatibility 17-4 PH stainless steel
Proof Pressure 2x max. F.S. range**
Burst Pressure 5x max. F.S. range**
Accuracy at 25 °C*** Ranges A and B: ±1% F.S. typical;
Long Term Stability ±0.25%
Zero Offset (Bidirectional and Port Swap Modes Only)
Temperature Compensated Range
0 to 5 V/0 to 10 V
Overall thread length: 0.5946” (conforms to ANSI/ASME B1.20.1 standard)
Range C: ±1.5% F.S. typical; Range D: ±2% F.S. typical. (For less than or equal to 20 ft. (6.1 m) cable length)
±0.5%
0 to 50 °C (32 to 122 °F); TC Zero <1.5% of product F.S. per sensor; TC Span <1.5% of product F.S. per sensor
PRESSURE RANGES
0 to 50 psig (Gauge) 5/10/25/50 psid (Differential)
0 to 100 psig (Gauge) 10/20/50/100 psid (Differential)
0 to 250 psig (Gauge) 25/50/125/250 psid (Differential)
OPERATING CONDITIONS
Sensor Operating Range -20 to 85 °C (-4 to 185 °F)
Operating Environment -10 to 50 °C (14 to 122 °F); 10 to 90% RH
non-condensing
WARRANTY
Limited Warranty 5 years
COMPLIANCE INFORMATION
Approvals RoHS, CE, NEMA4, IP65 at sensor
*VFD systems and system wiring generate f ields that can disrupt electrical devices. Ensure that these fields are minimized and are not affecting the sensor or sensor wiring. **F.S. is defined as full span of selected range. ***Accuracy combines linearity, hysteresis, and repeatability. † The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details.
TM
HQ0004952.H 0117
WIRING DIAGRAM
POWER SOURCE
15 to 30 Vdc/24 Vac
DIGITAL CONTROL
Analog Input: 0 to 5 V/0 to 10 V
or 4 to 20 mA
Optional
Digital Output
POWER
SIGNAL
COM
Zero
mA Volt
ON
OFF
1 2 3 4 5 6
(coming from sensor cable)
Red
Uninsulated
White/Clear
Black
Range
A B C D
Power Shield Signal
Common
Low Sensors Hi
Wire Colors
Pressure Monitoring | PWR Series
Status LED
Power
Shield
Signal
Common
Model
-03
-04
-05
DIMENSIONAL DRAWING
170 mm
(6.7")
ORDERING INFORMATION
Display
PWR
= LCD Display
L X
NIST
= None
Operational Range*
A
50
100
250
03 = 0-50 psi g 04 = 0-100 psig 05 = 0-250 psig
25
50
125
B
Range
78 mm
(3.1")
Media
S
= Water
C
10
20
50
61 mm
(2.4")
Cable Length
006 = 6 ft . (1.8 m) 010 = 10 ft. (3.1 m) 020 = 20 ft. (6.1 m)
DIP Switches
Function
D
5
10
25
Num
Damping
1
Test
2
Mode
3
Analog
4
Port
5
Voltage Out
6
1. “Off” position is the default setting for all DIP switches.
2. Ignored in mA mode.
Cable
Blank = Standard** A = Armore d***
2
0 to 10 V/0 to 5 V
1
Off/On
Fast/Slow
Operate/Test
Normal/Bidirec.
Normal/Reverse
Normal/Swap
Example:
S03 020 APWRLX
* Select operational range according to ma ximum gauge pressure, NOT differential pressure. Example: High gauge pressure=90 psig, Select 100 psig model (04). ** Standard cable available only in 10 ft and 20 ft lengths. *** Armored cable available only in 6 ft length. Note: Extension of total cable length greater than 20 feet may result in reduced accuracy.
HQ0004952.H 0117
TM