Veris Industries PWR Series Installation Guide

Installation Guide
No responsibility is assumed by Veris Industries for any consequences arising out of the
Compliant
Pressure
RoHS
• This product is not intended for life or safety applications.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
use of this material.
NOTICE
PWR Series
Wet Media Remote Pressure Transducer
Product Overview
The PWR Series remote pressure transducers are designed for dierential pressure applications. The sensors are remotely installed on existing plumbing runs. The PWR is available with either armored (6 ft.) or shielded (10 or 20 ft) sensor cables, and it requires a 15 to 30 VDC or 24 VAC power source to generate its output. The PWR is warranted for a period of ve years.
Product Identification
Cable
Blank = Standard A = Armored
PWR
NISTDisplay
L
= LCD = Water
Operational Range Cable Length
X
= Standard
03 = 0-50 psid
Media
S
04 = 0-100 psid 05 = 0-250 psid
† Standard cable avai lable only in 10 ft and 20 ft le ngths. ‡ Armored cable ava ilable only in 6 ft leng th. Note: Extensio n of total cable length greater than 20 fee t may result in reduce d accuracy.
006 = 6 ft (1.8 m) 010 = 10 ft (3.1 m) 020 = 20 ft (6.1 m)
TM
Specifications
Media Compatibility
Input Power
Maximum Current Draw
Status Indication
Proof Pressure
Burst Pressure
Accuracy at 25°C***
Surge Damping
Long Term Stability
Zero Offset
(Bidirectional and Port
Swap Mo des Only)
Zero Adjust
0-1 00 ps ig
0-250 psig
Output
Fittings
0-50 psig
17-4 PH stainless steel
15 to 30VDC, 24VAC nom. 5 0/ 60 Hz*
DC: 125mA; AC: 280mA
3-wire transmitter; user-selectable 4-20mA/ 0- 5V/ 0-10V
Dual color LED
2x max. F.S. range**
5x max. F.S. range**
Ranges A and B: ±1% F.S. typical; Range C : ±1.5% F.S. typic al; Range D : ±2% F.S. typical. (For less than or equal to 20 ft. (6.1 m) cable length)
Electronic; 1 or 5 second averaging
±0.25%
0.5%
Pushbutton auto-zero and digital input (2-position terminal block)
¼” NPT female thread, stainless steel 17-4 PH; Overall thread length: 0.59” (conforms to ANSI/ASME B1.20.1 standard)
OPERATIONAL RAN GES
5/10/ 25/ 50 psid
10/20/50/100 psid
25/ 50/125/250 psid
Z206731-0A Page 1 of 4 ©2014 Veris Industries 08141
Alta Labs, E nercept, Ensp ector, Hawkeye, Tru stat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Pressure PWRSeries
TM
Specifications (cont.)
Dimensions
OPERATING CO NDITION S
Temperature Compensated
Sensor Operating Range
Operating Environment
Approvals
* VFD systems and system wiring generate fields that can disrupt electrical devices. Ensure that these fields are minimized and
are not affecting the sensor or sensor wiring. ** F.S. is defined as full span of selected range. *** Accuracy combines linearity, hysteresis, and repeatability.
0° to 50 °C (32° to 122° F);
Range
TC Zero <1.5% of product F.S. per sensor; TC Span <1.5% of product F.S. per sensor
-20° to 8 5°C ( -4° to 185°F)
-10° to 50°C (14° to 122°F); 10- 90% RH noncondensing
COMPLIANCE INFORMATION
RoHS, IP65, CE
6.7"
(170 mm)
3.1"
(78 mm)
2.4"
(61 mm)
Installation
Disconnect power from the power source before beginning the installation.
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
1. Mount the housing using the included screws. Avoid locations where excessive vibrations occur.
2. Remove the housing cover by pressing the corner tabs. There are two tabs on each side of the housing. One side is shown below.
Press tabs to remove cover (2 tabs per side)
Z206731-0A Page 2 of 4 ©2014 Veris Industries 08141
Alta Labs, E nercept, Ensp ector, Hawkeye, Tru stat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Model
-03
-04
-05
A
50
100
250
B
25
50
125
C
10
20
50
D
5
10
25
Range
Zero
Range
A B C D
Low
Sensors
Hi
Power Shield Signal
Common
ON
OFF
mA Volt
1 2 3 4 5 6
Status LED
DIP Switches
Num
1
2
3
4
5
6
Function
Damping
Test
Mode
Analog
Port
Voltage Out**
O/On*
Fast/Slow
Operate/Test
Normal/Bidirec.
Normal/Reverse
Normal/Swap
0-10V/0-5V
* “O” position is the default setting for all DIP switches. ** Ignored in mA mode.
POWER
DIGITAL CONTROL
Analog Input: 0-5V/0-10V
or 4-20mA
Optional
Digital Output
POWER SOURCE
15 to 30 VDC/24 VAC
SIGNAL
COM
Wire Colors
(coming from sensor cable)
Red
Uninsulated
White/Clear
Black
Power
Shield
Signal
Common
Pressure PWRSeries
TM
Installation (cont.)
3. Run the digital control and power source wiring and connect to the left-most terminal block.
4. The sensors and monitor assembly are matched at the factory and calibrated as a unit. They must be kept paired to obtain the
accuracy stated in the product specications. Verify that the serial numbers on the sensors match the serial number on the main housing.
Main Housing serial number located
on label on the top of the housing
Sensor serial numbers
located on the sensor labels
PWR
HI
S/N
PWR
LO
S/N
5. Run wires from the remote pressure sensor cables and connect to the pair of 4-terminal blocks at the right side of the board. To
maintain the correct calibration, it is impor tant not to confuse the high side and the low side. To assist, the sensors are labeled, “HI” and “LO.”
6. If the sensors are installed on the wrong side, they can be reversed in one of two ways:
• Swap the cables at the sensor end.
• Swap the headers at the control unit end.
7. Adjust the switches on the board as desired.
8. Reconnect power to the power source. Check that the green LED illuminates, indicating normal operation. If not, check the
wiring.
9. Re-ax the cover onto the housing, ensuring that the cover is properly seated. .Do not operate the PWR without the housing
cover in place.
10. Choose sensor mounting locations that minimize cable length. Use plumbing connections of appropriate “tees” or equivalent,
made of compatible material. Observe safety precautions for plumbing connections. Release pressure from the system. Tighten sensor connections according to ANSI B1.20.3 (hand tighten plus one turn).
Z206731-0A Page 3 of 4 ©2014 Veris Industries 08141
Alta Labs, E nercept, Ensp ector, Hawkeye, Tru stat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Pressure PWRSeries
TM
Configuration
Test Mode
Test mode overrides the output to full-scale. If the PWR is congured for current (mA) operation, Test mode sets the output to 20.0 mA. If congured for voltage (VDC) operation, Test mode sets the output to 5.0 VDC or 10.0 VDC (depending on the position of the output selection switch).
Status LED
LED Status
Solid Green Normal operation.
Flashing Green Low > High; use port swap jumper or bidirectional mode.
Solid Red Dierential pressure is too high; select a higher pressure range.
Flashing Red Gauge pressure over sensor range; reduce line pressure or replace with a higher range device.
Alternating Red/Green Flash Sensor input is below sensor range. Verify that the sensor is connected correctly.
Auto Zero Function
To automatically reset the output to zero pressure, press and hold the Zero push-button for 2 seconds or provide contact closure on the auxiliary remote tare terminal. To protect the unit from accidental tare, this feature is enabled only when the detected pressure is within 5% of factory calibration.
Z206731-0A Page 4 of 4 ©2014 Veris Industries 08141