Pressure Monitoring | Digitally Controlled Gauge Pressure Transducer
PH SERIES
Three Switch-Selectable Ranges
with Test Mode
PH
The PH Series pressure transducers are designed for steam, air, gas, and
liquid pressure measurement in all media compatible with 17-4PH N8
stainless steel. They utilize a microprocessor controlled sensor profiled
for exceptional accuracy and reliability. All models feature three switchselectable ranges and a “test mode” to verify wiring and panel input
scaling. A pushbutton and digital input terminal is used to automatically
zero the output, and the microprocessor guards against accidental zero
adjustment during operation. The field-selectable output, offering
options of 0 to 5 V, 0 to 10 Vdc, or 4 to 20 mA, ensures excellent systems
compatibility. Jumper controlled surge damping is provided on all
models to reduce false alarms.
Reduces failures
Micromachined silicon sensor
design…improves overpressure
capacity and reduces failures
High stability
Electronic surge damping for high
stability
Zero calibration
Pushbutton zero calibration...
no trim pots to adjust, saves
installation time
APPLICATIONS
• Chilled and hot water pump
monitoring
• HVAC and industrial gas
monitoring
Switch-selectable
Switch-selectable pressure
ranges…fewer models to order
and stock
Pushbutton
Pushbutton and remote zero
adjustment…maintain accuracy
and prevent callbacks with
automatic zero calibration
Microprocessor
Microprocessor controlled signal
conditioning (see graph)
• Instrument air pressure
• Hydraulic oil pressure
SPECIFICATIONS
GENERAL
Input Power Class 2; 12 to 30 Vdc/24 Vac
Output 3-wire transmitter; user selectable 4 to 20
mA (clipped & capped)/0-5 V/0-10 V*
Surge Damping Electronic; 5-second averaging
Test Mode Overrides output to full-scale
(20 mA, 5 V, 10 V)
Zero Adjust Pushbutton auto-zero and digital input
(2-pos terminal block)
Status Indication Dual-color LED: Green = Normal,
Red = Overpressure, Flashing Red = Fault
Housing Material White powder-coated steel
PRESSURE RANGES
0 to 100 psi 25/50/100 psig switch selectable
0 to 250 psi 62.5/125/250 psig switch selectable
0 to 500 psi 125/250/500 psig switch selectable
0 to 1000 psi 250/500/1000 psig switch selectable
OTHER SPECS
Product Operating Environment -10 to 55 °C (-4 to 130 °F); 0 to 90% RH
non-condensing
SENSOR
Accuracy ±1% F.S. Combined linearity, hysteresis,
and repeatability
Long Term Stability ±0.25% per year
Media Compatibility Media compatible with 17-4 PH
stainless steel
Proof Pressure Max. 2x F.S. range
Burst Pressure Max. 5x F.S. range
Temp Compensated Range 0 to 50 °C (32 to 122 °F)
Media Temperature Limits -20 to 85 °C (-4 to 185 °F); 0 to 90% RH
non-condensing
Fittings 1/4" NPT male thread, 17-4 PH stainless
WARRANTY
Limited Warranty 5 years
*Minimum input voltage for 4 to 20 mA operation:
250 Ω loop (1 to 5 V) = 12 Vdc
500 Ω loop (2 to 10 V) = 15 Vdc
TM
HQ0001825.F 0117
WIRING DIAGRAM DIMENSIONAL DRAWING
Output
B
50
125
250
500
Slow
Fast
C
100
250
500
1000
Remote
Zero
5.1"
(129 mm)
4.5"
(115 mm)
POWER SOURCE
12 to 30 Vdc/24 Vac
DIGITAL CONTROL
Analog Input
0 to 5 V/0 to 10 V
or 4 to 20 mA
Optional
Digital Output
+
-
-
VIN
OUT
COMMON
TEST
C
Zero
Response
A
B
Range
VOLT
mA
0-5
0-10
RANGE
MODEL
07
08
09
10
A
25
62.5
125
250
SIGNAL CONDITIONING DIAGRAM
Pressure Monitoring | PH Series
2.25"
(57 mm)
2.2"
(56 mm)
2.5"
(62 mm)
F.S.
Noise Rejection
PRESSURE
0
Actual Pressure
Digitally Conditioned Output
ORDERING INFORMATION
PH
N = NIST
X = None
Example:
NIST
Range
07 = 0-100 psig
08 = 0-250 psi g
09 = 0-50 0 psig
10 = 0-1000 psig
07X SPH
S
= Standard
Output Clamping
Surge Damping
TIME
HQ0001825.F 0117
TM