Veris Industries MSC SERIES Data Sheet

Occupancy Sensors | Ceiling Mount Occupancy Sensors
MSC SERIES
Uses the Latest Passive Infrared and Ultrasonic Technologies
MSCD/MSCP
MSCU
MSC Series Occupancy Sensors employ passive infrared (PIR) and/or ultrasonic technologies to accurately detect occupancy and automatically switch room lighting.
The low-profile sensor is ceiling-mounted to maximize motion sensitivity in large areas with obstructions. With a 360 degree field of view, and up to 2000 square feet of coverage area, the ceiling-mounted occupancy sensor is ideal for conference rooms, classrooms, multi-stall bathrooms, and large office areas.
The MSC series also incorporates an integral photosensor to prevent lights from switching on when sufficient ambient light is present, as commonly found in windowed areas.
Installation and configuration are simple. The sensor readily mounts to drop ceilings, and it features front adjustments for setting sensitivity and time delay. The sensor also features an auxiliary relay for use with building automation and HVAC systems.
SPECIFICATIONS
Standards UL and cUL Listed; FCC part 15 (Class B)
for home and office use
Input Voltage 24 Vdc
Isolated Relay Contact rating: 1 A@24 Vdc Resistive
Temperature 0 to 50 °C (32 to 122 °F)
Humidity Max. 90% RH non-condensing
CURRENT CONSUMPTION @ 24 VDC*
PIR 21 mA nominal
Ultrasonic 34 mA nominal
Dual 37 mA nominal
MSCU 4.6” (117 mm) diameter, 1.4” (35.1 mm) high
MSCD/MSCP 4.6” (117 mm) diameter, 1.8” (45.7 mm) high
WARRANTY
Limited Warranty 1 year
AGENCY APPROVALS
* For local line switching control, power must be provided by AA47 power pack or an approved equivalent.
Wide coverage
Up to 2000 square foot coverage area and 360-degree field of view for application versatility
Daylight sensing
Daylight level sensing (from
0.5 to 250 foot-candles)… avoids unneccessary lighting
Adjustable time delay
Adjustable time delay (preset time delays from 15 seconds [test] to 30 minutes)…provides ultimate flexibility
Adjustable coverage
Adjustable coverage sensitivity (from 60 to 100%)
Auxiliary relay
Easily communicates with building control system
Tamper resistant cover
Adjustment compartment cover…tamper resistant
APPLICATIONS
• Lighting control based on occupancy
• Reducing energy usage
• Key component for LEED* certication programs retrot installations
• MSC1000 – best for conference rooms, classrooms, and other general applications
*Leadership in Energy and Environmental Design (LEED) is a registered mark of the US Green Building Council
• MSCD2000 – best for multi-stall bathrooms, large conference rooms, and warehouses
• MSCU2000 – best for lobbies, aisles, and great for multi-stall bathrooms
MSC SERIES
Coverage Patterns for 9 ft (2.8 m) Ceiling Height
PIR Sensor
25 ft (7.7m)
32 ft (9.8m)
30 ft
(9.2m) 48 ft (14.7m)
24 ft (7.4m)
Minor Motion
Major Motion
42 ft (12.8m)
Ultrasonic Sensor
Ultrasonic Major Motion Ultrasonic Minor Motion PIR Major Motion PIR Minor Motion
TM
HQ0001801.F 0117
Aux. Relay
ange (N.O
een (N.C.)
Class 2
Voltage Selector
Line 120/277
dH
Neutral
erride
Load
Sensor
GRN N.C.
CONTROL IN
+24 Vdc
or
Occupancy Sensors | MSC Series
LOCAL LINE-POWER CONTROL MSC
Wiring Diagram
Black
Red
.)
Or
Blue
Yellow (Common)
Gr
Contact rating: 1 A @ 24 Vdc Resistive
Class 1
Hot Neutral
Load
Black
White
Red
Black
Blue
Power Pack AA47
Red
AA47 LOCAL LINE SWITCHING POWER PACK
System Diagram
Hot
Voltage
Vac
Neutral
Load
BLK
White
RED
Ext. Override OFF
277 V
120 V
+24 Vdc Common Control Input
BLUE
Sensor
AA48 AUXILARY RELAY (OPTIONAL)
System Diagram
Override OFF
Hot
Red
White
Black
Load
AA47
Power
Pack
+24 Vdc (Red)
0 Vdc (Blk) Control (Blue)
Load
AA48 Optional
Auxiliary
Relay
Black
Blue
Additional
Sensor(s)
(optional)
Red
Re
REDBLK
Red
Ext. Ov OFF
BUILDING CONTROL PANEL
Wiring Diagram
+
24 Vdc
-
BLK BLKRED RED
COMMON
CONTROL IN
ORG N.O. ORG N.O.GRN N.C.
or
The AA47 Line-Switching Power Pack provides local switching capability to control loads at a signal from MSC Series occupancy sensors, independent of any connection to building control systems. The AA47 routes 120/277 Vac, 60 Hz line power directly to a Form A relay contact (SPST) to control a load and generates full-wave, 24 Vdc to power up to four MSC sensors (dependent on model). The AA47 can be mounted either inside or outside an electrical box, and sensor power can be routed via plenum-rated cable to the sensor(s).
SPECIFICATIONS
AA47
Storage Temp. -29 to 65 °C (-20 to 150 °F )
Operating Temp. 0 to 40 °C (32 to 104 °F)
Maximum Humidity 90% RH non-condensing
AC Power Input 120/277 Vac ± 10%, 60 Hz
Output Voltage 24 Vdc
Output Current 100 mA max.
Dimensions 3.2” (81.3 mm) x 3” (76.2 mm) x 1.75” (44.5 mm)
RELAY CONTACTS
Horsepower Rating 1HP@120 V
Switching Capacity 120 Vac, 60 Hz; 15 A tungsten 1800 W
The AA48 Auxiliary Relay is a low-voltage relay device for expanding the switching capacity of an AA47. It can be used to control loads connected
ot
to additional circuits in response to a signal from a connected sensor. It is essentially a relay with a SPST output controlled directly by the occupancy sensor. The auxiliary relay can be mounted inside or outside of an electrical junction box.
277 Vac, 60 Hz; 20 A Ballast
ORDERING INFORMATION
Sensing Technology
MSC
U = Ultrasonic D = PIR + Ultras onic P = Passive Inf rared (PIR)
Example:
MSC D 2000
HQ0001801.F 0117
Coverage
1000 = 1000 Sq . Ft. (Passive Infare d only) 2000 = 200 0 Sq. Ft. (Ultraso nic or Dual techno logy only)
TM
SPECIFICATIONS
AA48
Storage Temperature -29 to 65 °C (-20 to 150 °F )
Operating Temperature 0 to 40 °C (32 to 104 °F)
Maximum Humidity 90% RH non-condensing
Control Input 24 Vdc, 36 mA nominal
Dimensions 3.2” (81.3 mm) x 3” (76.2 mm) x 1.75” (44.5 mm)
RELAY CONTACTS
Horsepower Rating 1HP@120 V
Switching Capacity 120 Vac, 60 Hz; 15 A tungsten 1800 W
120/277 Vac, 60 Hz; 20 A ballast
Loading...