Current Monitoring | Current Switches with Relay: Fixed Trip Point
HX30/40/50 SERIES
On/Off Status and Control in One Package
H730 H930
On/off status
On/off status and command relay
in a single labor and space saving
device
TM
Detect belt loss
Cost-effectively monitor start/stop,
unit vents, fan coils,
exhaust fans, and other loads
where belt loss is not a concern
SPDT command
relay
H740 and H940 feature a SPDT
command relay
No tubing
necessary
Easier to install than differential
pressure switches
Easy setup
No calibration required…easy
setup and operation
APPLICATIONS
Maximize Reliability
The Hawkeye Relay Combination Series combines an on/off status
sensor and command relay in one package, saving the labor, wire runs,
and space required to mount a separate relay. The switch and relay
(not electrically connected) are in the same housing, saving space and
cost. It is ideal for monitoring and controlling motors where belt loss is
not a concern.
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Insulation Class 600 Vac RMS
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals
UL 508 open device listing, CAT III, Pollution
Degree 2, basic insulation
• Monitoring direct drive units,
exhaust fans, and other
fixed loads
RELAY CONTACT RATINGS
Hx30, Hx50 (SPST, N.O.)
Resistive 10 A @ 250 Vac, 30 Vdc
Inductive 5 A @ 250 Vac, 30 Vdc
Hx40 (SPDT)
Resistive 8 A @ 250 Vac, 30 Vdc
Inductive 3.5 A @ 250 Vac, 30 Vdc
TYPICAL COIL PERFORMANCE
Voltage AC DC
24V 10 mA 10 mA
Pull In Voltage
Hx30 20.1 Vdc
Hx40 20 .1 Vdc
Hx50 8.4 Vdc
Drop Out Voltage
Hx30 5.2 Vdc
Hx40 5.2 Vdc
Hx50 3.0 Vdc
• Monitoring on/off status of
electrical loads
• Starting/stopping motors
Note: Do not use the LED status indicators as evidence of applied voltage.
TM
HQ0001759.F 0117
![](/html/27/2777/2777f6019537674baf14de8bb6e83136f9a70bcbdcab26f93f7ac117b280cfa2/bg2.png)
Current Monitoring | Hx30/40/50 SeriesCurrent Monitoring | Current Switches with Relay: Fixed Trip Point
H730/740/750
Dimensional Drawing
Removable/Adjustable Mounting Bracket
0.9"
0.7"
(19 mm)
4.2"
(106 mm)
2.8"
(68 mm)
3.8"
(95 mm)
0.2” x 0.15”
slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
** Slide switch may extend up to 1/4” over the height dimensions shown.
(23 mm)
3.0" **
(75 mm)
1.1" *
(27 mm)
H930/940/950
Dimensional Drawing
Removable Mounting Bracket
Bracket can
be mounted
on three sides
for added
installation
flexibility.
3.1”**
(79 mm)
1.1”
(26 mm)
0.8”
(21 mm)
1.0”
(25 mm)
START/STOP MONITORING
OF FAN/PUMP MOTORS
Wiring Diagram
CONTACTOR
Motor
RELAY CONTROLLED DIREC TLY
BY STATUS CONTACTS
Wiring Diagram
Fan or Pump
CONTROLLER
Digital Output
(Relay Coil)
Digital Input
(Status)
CONTROL
POWER
Relay Coil
Power Source
Self-gripping Iris
2.8”
(70 mm)
Ø 0.3”
(8 mm)
2.5”
(64 mm)
3.0”
(76 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown.
1.4”*
(36 mm)
RELAY LOAD
ORDERING INFORMATION
MODEL
H730 0.5 to 200 A
H740 0.5 to 200 A 0.5 A or less SPDT 24 Vac/d c Solid-core • •
H750 0.5 to 200 A 0.5 A or less SPST, N.O. 12 Vdc nom. Solid-core • •
H930 1.5 to 200 A 1.5 A or less SPST, N.O. 24 Vac/d c Split-core • •
H940 1.5 to 200 A 1.5 A or less SPDT 24 Vac/dc Split-core • •
H950 1.5 to 200 A 1.5 A or less SPS T, N.O. 12 Vdc nom. Split-core • •
AMPE RAG E
RANGE
STATUS OUTPUT
(MAX.)
N.O. 1.0 A @ 30 Vac/dc
TRIP
POINT
0.5 A or less SPST, N.O. 24 Vac/d c Solid-core • •
RE LAY
RE LAY
COIL
HOUSING
RE LAY
POWER LED
UL
HQ0001759.F 0117
TM