Veris Industries HX39 SERIES, HX49 SERIES, HX59 SERIES Data Sheet

Minimize Installed Cost
Current Monitoring | Current Switches with Relay: Adjustable Trip Point,
High Voltage Output
HX39, HX49 & HX59 SERIES
Status and Control in One Package
H939
H739
Maximize Reliability
Hawkeye Relay Combination Series high voltage output current switches are the ideal solution for the automation installer. These units combine a current switch and relay into a single package, reducing the space required for total control of fans and pumps. The integrated current switch and relay operate independently of one another. All relay connections are externally available for maximum flexibility.
These products perform the functions of start/stop and status monitoring with one device instead of two.
SPECIFICATIONS
Combined relay & status
Combines command relay and fan/ pump status sensor in a single, easy-to-install unit
TM
Polarity insensitive
Polarity insensitive status outputs…fast and easy installation
Easy setup
Relay and status LEDs
No tubing
Easier to install than differential pressure switches…no tubing needed
Detect belt loss
Detect belt loss & motor failure... ideal for fan and pump status
Added flexibility
Bracket on H939, H949, and H959 can be installed in three different configurations
APPLICATIONS
• Starting/stopping and monitoring positive status of motors
DETECTS BELT LOSS/COUPLING SHEAR!
DETECTS BELT LOSS/COUPLING SHEAR!
Calibrated
Trip Point
O O
Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That’s why our sensors are the industry standard for status.
Loss of Belt/Coupling Shear
• Detecting belt loss and coupling shear
Fan/pump On
Electrical Failure
Sensor Power Induced from monitored conductor
Insulation Class 600 Vac RMS
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Hysteresis 10% Typical
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Agency Approvals UL 508 open device listing, CAT III, Pollution
Degree 2, basic insulation
AGENCY APPROVALS
Limited Warranty 5 years
Do not use the LED status indicators as evidence of applied voltage.
TM
Relay Contact Ratings
Hx39, Hx59 (SPST, N.O.)
Resistive 10 A @ 250 Vac, 30 Vdc
Inductive 5 A @ 250 Vac, 30 Vdc
Hx38, Hx58 (SPDT)
Resistive 8 A @ 250 Vac, 30 Vdc
Inductive 3.5 A @ 250 Vac, 30 Vdc
Typical Coil Performance
Voltage AC DC
24V 10 mA 10 mA
12V (Hx58) 20 mA
Pull-in Voltage
Hx39 20.1 Vdc
Hx49 20.1 Vdc
Hx59 8.4 Vdc
Drop-out Voltage
Hx39 5.2 Vdc
Hx49 5.2 Vdc
Hx59 3.0 Vdc
HQ0001761.G 0117
Current Monitoring | Hx39, Hx49 & Hx59 Series
H739/H749
Dimensional Drawing
Removable/Adjustable Mounting Bracket
0.9"
 0.7"
(19 mm)
4.2"
(106 mm)
2.8"
(68 mm)
3.8"
(95 mm)
0.2” x 0.15” slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown.
(23 mm)
3.0" **
(75 mm)
1.1" *
(27 mm)
H939/H949/H959
Dimensional Drawing
Removable Mounting Bracket
Bracket can be mounted on three sides for added installation flexibility.
3.1”**
(79 mm)
1.1”
(26 mm)
0.8”
(21 mm)
1.0”
(25 mm)
START/STOP MONITORING OF FAN /PUMP MOTORS
Wiring Diagram
CONTROLLER
Digital Output (Relay Coil)
Digital Input (Status)
CONTROL
POWER
CONTACTOR
Fan or Pump
Motor
RELAY CONTROLLED DIRECTLY BY STATUS CONTACTS
Wiring Diagram
Relay Coil Power Source
Self-gripping Iris
2.8”
(70 mm)
Ø 0.3”
(8 mm)
2.5”
(64 mm)
3.0”
(76 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown.
1.4”*
(36 mm)
RELAY LOAD
ORDERING INFORMATION
MODEL AMPERAGE RANGE
H739 1 to 135 A
H749 1 to 135 A 1 A or less SPDT 24 Vac/dc Solid-core
H939 2.5 to 135 A 2.5 A or less SPST, N.O. 24 Vac/dc Split-core
H949 2.5 to 135 A 2.5 A or less SPDT 24 Vac/dc Split- core
H959 2.5 to 135 A 2.5 A or less SPST, N.O.
STATUS OUTPUT
(MAX.)
N.O. 0.2 A @
120 Va c/d c
MIN. TRIP
POINT
1 A or less SPST, N.O. 24 Vac/dc Solid-core
RE LAY
TYPE
RE LAY
COIL
12 Vdc nom.
HOUSING
Split-core
STAT US
LED
RELAY POWER
LED
UL