SENSOR OUTPUT
Selected Range
0 V
0 A
10 V
SENSED AMPS
Current Monitoring | Current Transducers:
0 to 10 Vdc Analog Output
HX23 SERIES
Load Trending with 0 to 10 Vdc Output
H723
H923
H623-xx
TM
Maximize Reliability
The Hawkeye 623-xx, 723LC, 723HC, and 923 Series provide accurate
load trending information with a proportional 0 to 10 Vdc output signal.
Devices offer three amperage range options, with slide-switch selection
for easy field adjustment – no need for jumpers.
Self-powered
analog
Self-powered analog current
transducer 0 to 10 Vdc output
Retrofit
Self-gripping, split-core design for
fast retrofit installation…no need
to remove conductor (H623-xx
and H923)
No jumpers
No jumpers on unit…reduces
installation error
APPLICATIONS
• Load trending
• Motor control
• Fan/pump status
No external
power required
No external power required for
sensor
Factory
calibrated
Factory calibrated ranges for high
resolution and installation ease
Field-selectable
ranges
Some models available with fieldselectable ranges
EXAMPLE LINEAR OUTPUT
Scale software as shown
SPECIFICATIONS
Sensor Power Induced from monitored current
Insulation Class
Frequency Range 50/60 Hz nominal
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH, non-condensing
Accuracy ±2% F.S. from 10% to 100% (range)
Response Time 2 sec.
Terminal Block
Wire Size
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals
1. The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
600 Vac RMS (UL) (H623-xx)
300 Vac RMS (CE) (H623-xx , H723, H923)
24 to 14 AWG (0.2 to 2.1 mm2)
UL 508 open device listing (H623-xx only); CE1:
EN61010-1, CAT III, Pollution Degree 2, basic
insulation
TM
HQ0001765.G 0117

Current Monitoring | Hx23 Series
H623-XX
Dimensional Drawing
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
H923
Dimensional Drawing
3.1”**
(79 mm)
Ø 0.3”
(8 mm)
Removable Mounting Bracket
0.6"
(16 mm)
Removable Mounting Bracket
1.1”
(26 mm)
0.5"
(13 mm)
(74 mm)
(89 mm)
(21 mm)
(70 mm)
3.0”
(76 mm)
2.1"
(54 mm)
2.9"
3.5"
0.8”
2.8”
2.5”
(64 mm)
0.7"
(18 mm)
1.0”
(25 mm)
1.2"
(31 mm)
Self-gripping Iris
1.4”*
(36 mm)
2.5"
(64 mm)
1.0"
(26 mm)
Bracket can
be mounted
on three sides
for added
installation
flexibility.
H723LC/H723HC
Dimensional Drawing
Removable/Adjustable Mounting Bracket
0.9"
0.7"
(19 mm)
(23 mm)
3.0" **
(75 mm)
0.2” x 0.15”
slot (2x)
2.8"
(68 mm)
1.1" *
(27 mm)
3.8"
(95 mm)
4.2"
(106 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown.
** Slide switch may extend up to 1/4” over the height dimensions shown.
MONITORING FAN/PUMP MOTORS
FOR POSITIVE PROOF OF FLOW
Wiring Diagram
CONTACTOR
CONTROLLER
AI
–
COMMON
0 to 10 Vdc
+
Fan or Pump
* Terminal block may extend up to 1/8” over the height dimensions shown.
** Slide switch may extend up to 1/4” over the height dimensions shown.
ORDERING INFORMATION
MODEL AMPERAGE RANGE SENSOR OUTPUT HOUSING UL CE
H623-10 0 to 10 A
H623-20 0 to 20 A Split-core
H723LC 0 to 10/20/40 A Solid-core
0 to 10 Vdc
H723HC 0 to 50/100/200 A Solid-core
H923 0 to 20/100/150 A Split-core
HQ0001765.G 0117
TM
Split-core • •
• •
•
•
•