SENSED AMPS
100 to 300A (H221/H221SP)
300 to 800A (H321/H321SP)
1000 to 2400A (H421/H421SP)
0A *
4mA
20mA
SENSOR OUTPUT
*Adjusted with Span Potentiometer for Hx21 models;
Factory-set per customer specification for Hx21SP models
Current Monitoring | Current Transducers: 4 to 20 mA
Analog Output, High Current Monitoring
HX21 & HX21SP SERIES
Large Load Trending with 4 to 20 mA Output
H321
TM
Maximize Reliability
Hawkeye x21/x21SP analog current transducers provide reliable
load trending information for large motor loads (up to 2400 A), with
a proportional 4 to 20 mA signal. Three devices are available, each
with a different amperage range. The Hx21 versions include a span
potentiometer that allows each sensor to be calibrated for maximum
resolution. The Hx21SP versions are factory-calibrated at a range
specified by the customer.
Split-core design
Split-core design for easy
installation and fast retrofits
No need for
external CTs
No need for external CTs on large
conductors
Large openings
Large openings for heavy
conductors
APPLICATIONS
• Load trending of large motors
and other loads up to 2400 A
• Monitor critical motors
(compressor, fuel, etc.)
Loop powered
Loop powered 4 to 20 mA output
Two-wire design
Two-wire design reduces wiring
cost
Field flexibility
Hx21 models offer zero and span
adjustments for field flexibility
EXAMPLE LINEAR OUTPUT
Scale software as shown
SPECIFICATIONS
Sensor Power 30 mA (max) @ 12 to 30 Vdc
Insulation Class 600 Vac RMS (UL), 300 Vac RMS (CE1)
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH, non-condensing
Accuracy ±2% from 10 to 100% of full scale
Response Time 2 sec.
Terminal Block Wire Size 12 AWG (3.3 mm2) - 22 AWG (0.33 mm2)
Terminal Block Torque 7 to 8 in-lbs (0.8 to 0.9 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals
1. The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
UL 508 open device listing, CE: EN61010-1,
(H221, H321 only)CAT III, Pollution Degree 2,
basic insulation
TM
HQ0001763.F 0117
Current Monitoring | Hx21 & Hx21SP Series
DIMENSIONAL DRAWING MONITORING FAN /PUMP MOTORS LOADS
Wiring Diagram
Voltage Output
ORDERING INFORMATION
MODEL AMPERAGE RANGE
4 mA
(Lower Limit)
H221
H221SP 100, 150, 200, 250, or 300 A
H321 300 to 800 A
H321SP 300, 400, 500, 600, 700, or 800 A
0 A
H421 1000 to 2400 A •
H421SP
1. Listed for use on 75 °C insulated conductors.
2. Factory calibrated - not field adjustable.
Note: When ordering HxxxSP versions, specify upper current limit for factory calibration (device is not field adjustable).
20 mA (Upper Limit)
100 to 300 A
2
2
1000, 1200, 1400, 1600, 1800, 2000,
2200, or 2400 A
2
SENSOR
OUTPUT
4 to 20 mA
DC
HOUSING UL CE
1
•
1
•
1
•
Split-core
1
•
•
•
•
•
LEAD
FREE
•
HQ0001763.F 0117
TM