Veris Industries HX00 SERIES Data Sheet

SPECIFICATIONS
E150462
Current Monitoring | Current Switches: Fixed Trip Point
HX00 SERIES
On/Off Status Current Switches
H800
H300
Maximize Reliability
Minimize Installed Cost
Hawkeye x00 on/off current switches provide a cost-effective solution for monitoring status on unit vents, exhaust fans, recirculation pumps, and other fixed loads where belt loss is not a concern.
Veris has applied new technology to the H300, H600, and H800 models to achieve impressive improvement in turn-on levels. The Hawkeye H300 and H600 have the lowest turn-on current in the industry at a mere 0.15 A!
H900
H600
Reliable
More reliable for status than relays across auxiliary contacts
Ideal for direct­drive units
Ideal for direct-drive units, unit vents, fan coil units, exhaust fans, and other fixed loads
Low setpoint
Minimum trip point as low as 0.5 A (H608)…avoids the need for multiple wraps of the conductor through the sensor even on loads as small as 1/5 HP
APPLICATIONS
• Electrical load status
• Direct-drive units, exhaust fans, process motors, and other fixed loads
• Lighting run times and status
Installation flexibility
Removable mounting bracket provides installation flexibility
Flexibility
Bracket on H900 can be installed in three different configurations
Quick installation
Split-core H300, H600 and H900 for fast retrofit installation
• VFD output On/Off status
• Direct-Drive units, unit vents, fan coil units, exhaust fans, and other fixed loads
Sensor Power N.O models: Induced from monitored current;
Insulation Class 600 Vac RMS (UL), 300 Vac RMS (CE*)
Frequency Range 50/60 Hz, On/O status for Variable Frequency Drive
Temperature Range: H800NC, H300, H900
H600
H800, H800HV
Humidity Range 10 to 90% RH non-condensing
O State Leakage (H800NC Only)
On State Voltage Drop (H800NC Only)
H800NC: 5 to 30 Vdc, permanently connected
(VFD) outputs at 12 to 115 Hz (a)
-15 to 60 °C (5 to 140 °F)
-15 to 40 °C (5 to 104 °F) (to 200 A);
-15 to 60 °C (5 to 140 °F) (to 150 A)
-40 to 50 °C (-40 to 122 °F) (to 200 A);
-40 to 75 °C (-40 to 167 °F) (to 100 A, and 0.25 A status output)
34 μA @ 5 Vdc, 200 μA @ 30 Vdc
1.9 Vdc (max.) @ 0.1 A
TM
Terminal Block Wire Size H600, H800, H900 H300
Terminal Block Torque H600, H800, H900 H300
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency approvals UL 508 open device listing; CE: EN61010-1, CAT III,
*The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details.
Note: Do not use the LED status indicators as evidence of applied voltage.
(a) VFD systems generate fields that can disrupt electrical devices. Ensure that these fields are minimized and are not af fecting the sensor.
24 to 14 AWG (0.2 to 2.1 mm2); 22 to 16 AWG (0.3 to 1.3 mm2)
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m); 7 in-lbs (0.8 N-m)
Pollution Degree 2, basic insulation
HQ0001753.F 0117
Current Monitoring | Hx00 Series
H300
Dimensional Drawing
Removable Mounting Bracket
0.3”
(8 mm)
6 AWG max.
1.5”
Ø 0.18” (x2)
(5 mm)
(38 mm)
1.8”
(46 mm)
H800, H800HV, H800NC
Dimensional Drawing
Removable/Adjustable Mounting Bracket
 0.7" (18 mm)
Self-gripping Iris
1.6”
(40 mm)
0.6”
(15 mm)
0.9"
(23 mm)
2.8" *
(71 mm)
H600
Dimensional Drawing
Removable Mounting Bracket
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
H900
Dimensional Drawing
Removable Mounting Bracket
1.1”
(26 mm)
3.1”**
(79 mm)
0.6"
(16 mm)
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
0.8”
(21 mm)
0.7"
(18 mm)
3.5"
(89 mm)
1.0”
(25 mm)
1.2"
(31 mm)
Self-gripping Iris
Bracket can be mounted on three sides for added installation flexibility.
Self-gripping Iris
2.5" *
(64 mm)
1.0"
(26 mm)
UNIT VENT HEATER CONTROL
Wiring Diagram
POWER SOURCE
POWER SOURCE
UNIT VENT HEATER
BUILDING AUTOMATION
CONTROLLER
Digital Input
Digital Input
0.4” x 0.2” Slot (x2)
1.7
(43 mm)
1.1" *
Ø 0.3”
(8 mm)
(27 mm)
2.3"
* Terminal block may extend up to 1/8” over the height dimensions shown.* Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown.
ORDERING INFORMATION
MODEL
H300
H600
H800
H800NC
H800HV
H900
AMPERAGE RANGE
@ 50/60 H Z ONLY
0.15 to 60 A N.O. 1.0 A @ 30 Vac/dc 0.15 A or less Split-core
0.15 to 200 A N.O. 1.0 A @ 30 Vac/dc 0.15 A or less Split-core
0.25 to 200 A N.O. 1.0 A @ 30 Vac/dc 0.25 A or less Solid-core
0.5 to 200 A N.C. 0.1 A @ 30 Vdc 0.5 A or less Solid-core
0.75 to 200 A N.O. 0.5 A @ 250 Vac/dc 0.75 A or less Solid-core
1.5 to 200 A N.O. 1.0 A @ 30 Vac/dc 1.5 A or less Split-core
STATUS OUTPUT
(MAX.)
(70 mm)
3.0”
(76 mm)
2.8”
2.5”
(64 mm)
TRIP
POINT
1.4”*
(36 mm)
HOUSING UL CE
2
1
1
1
3
LEAD
FREE
1. Listed for use on 75°C insulated conductors.
2. Product provides functional insulation only.
3. Listed for use on 90°C insulated conductors.
HQ0001753.F 0117