Veris Industries HW2XA2H, HW2TA2K, HW2XA2C, HW2XA2D, HW2LA2C User manual

...
Page 1
Installation Guide
Humidity
HW2 Series
Wall Mount Humidity Sensors
HW2Txxxx HW2Lxxxx HW2Xxxxx
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
Read and understand the instructions before installing this product.
• Turn o all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
If this product is used in a manner not specied by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by the manufacturer for any consequences arising out of the use of this material.
Product Overview
The HW2 Series of humidity sensors for living space is a exible multisensor platform for use with BAS controllers designed to accept 4 to 20mA, 0 to 5Vdc or 0 to 10Vdc outputs. HW2 Series sensors are available with three user interface options: touchscreen, LCD with three buttons and blank. Humidity and temperature sensors are included with all HW2 Series sensors.
Product Identication
User Interface Output RH Accuracy* Temperature
HW2
T = Color touchscreen L = 3-button LCD display X = None
* Replaceable 1% with NIST certicate, 2% with NIST certicate and 2% elements availab le. ** Available in HW2XA2G only. *** Available in HW2XA2R only.
A = Analog output 2 = 2% A = Transmitter only
C = 1000 PT RTD D = 10K T2 thermistor G = 10K CPC thermistor** H = 10K T3 thermistor K = 10K curve G/11K shunt M = 20K NTC thermistor N = 1.8K TAC thermistor R = 10K curve G***
Specications
OPERATING ENVIRONMENT
Input Power Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Analog Output Select able 4 to 20 mA, 0 to 5 V, 0 to 10 V
Operating Temp. Range 0 to 50 °C (32 to 122 °F)
Operating Humidity Range 0 to 95% RH non- condensing
Housing Material High-imp act ABS plastic
Terminal Block Torque 0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)
RH TRANSMITTER
HS Sensor Thin-lm capacitive, replaceable
Accuracy ±2% from 10 to 80 % RH @ 25°C (77 °F)
Hysteresis 1.5 % typ ical
Stability ±1% @ 20°C (68 °F) annually for 2 year s
Output Range 0 to 100% RH
Temperature Coecient ±0.1% RH/°C above or below 25 °C (77 °F ) typical
TEMPERATURE TRANSMIT TER OPTION
Sensor Type Solid state, integrated circuit
Accuracy ±0.2 °C (±0.4 °F) t ypical
Resolution 0.1 °C (0.1 °F)
Range 0 to 50 °C (32 to 122 °F)
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 2
HW2 Series Installation Guide
Specications (cont.)
DISPLAY MODELS
Touchscreen 61 mm (2.4 in), color, backlit, capac itive, 240x300 px
Setpoint : 0-10Vdc. Temperature, humidit y or fan speed selec table Timeout over ride: Display timeout * Lockout overr ide: Touchscre en/button lockout *
LCD 52mm (2.05 in), segmented w ith 3 buttons
Setpoint : 0-10Vdc. Temperature, humidit y or fan speed selec table Timeout over ride: Display timeout * Lockout overr ide: Touchscre en/button lockout *
SETPOINTS**
Temperature Setpoint 0 to 10V output
Scale: 10 to 35 °C (50 to 95 °F) / 0 to 50 °C (32 to 122 °F)
Humidity Setpoint 0 to 10V output
Scale: 0 to 100% RH
Fan Speed Setpoint 0 to 10V output
O 0V, Low 3.3V, Med. 6.7V, High 10.0V
OVERRIDE
Override Button Display models feature a momentary-to-ground override button
WIRING TERMINALS
Terminal Blocks Screw terminals , 18-24 AWG
Screw Terminal Torque 0.2 N-m (2.0 in-lbF) max.
WARRANTY
Limited Warranty 5 years
COMPLIANCE INFORMATION
Agency Approvals UL 916, European conformance CE : EN61000-6 -2,
EN61000-6 -3, EN61000 Series - indus trial immunity, EN 61326 -1 FCC Part 15 Class B, REACH, RoHS, RC M (Australia), ICES- 003 (Canada)
*DIP switch selectable. ** One setpoint t ype is selectable via DIP switch on display models only.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 3
HW2 Series Installation Guide
(3.3)
Dimensions
115
(4.5)
Functions
Installation
85
The HW2 Series sensor measures the RH and temperature in a room and provides analog outputs to a controller.
1. Remove the cover from the base at the bottom of the device.
2. Position the sensor base vertically on the wall 1.35 m (4.5 ft.) above the oor with the “UP” arrow facing upward. Locate away from windows, vents and other sources of draft. If possible, do not mount on an external wall, as this may cause inaccurate temperature readings.
24
(0.9)
3. Pull 18 or 22 AWG cable(s) through the hole in the backplate.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 4
HW2 Series Installation Guide
10 9876 54321
10 9876 54321
Installation (cont.)
4. Mount the backplate onto the wall using the screws provided.
Six screw holes available. Use a minimum of two for secure mounting.
5. Connect the wires to the screw terminals. Do not over-tighten the screws.
Wiring for models with temperature transmitter:.
CONTROL SYSTEM
OVERRIDE* SETPOINT OUT**
RH OUT TEMP OUT COMMON
POWER SUPPLY 20-30 Vdc, 24 Vac
-
COMMON
+
POWER (+24)
Wiring for models with RTD/thermistor:
CONTROL SYSTEM
OVERRIDE* SETPOINT OUT**
RH OUT RTD/THERMISTOR OUT RTD/THERMISTOR OUT COMMON
POWER SUPPLY 20-30 Vdc, 24 Vac
-
COMMON
+
POWER (+24)
* Momentary to ground. ** 0-10V DIP switch selectable for temperature, RH or fan speed (o, 0V, Low 3.3V, Medium 6.7V or high 10V).
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 5
HW2 Series Installation Guide
ON
2345678
Touch-Button Disable On/Off
Installation (cont.)
6. Set the DIP switches.
1
5V / 10V
Unused
Unused
Temp / RH-Fan Setpoint
Temp Range 1 / 2
RH / Fan Setpoint
mA / Voltage
Screen Timeout On/Off
Switch Function Description
1 Output mode ON - 4-20mA output mode enabled
OFF - Voltage output mode enabled
2 Voltage output range* ON - 0-5V output range enabled
OFF 0-10V output range enabled
3 Unused Unused
4 Unused Unused
5 Setpoint output type ON - Temperature setpoint enabled (temp range selected on DIP switch 6)
OFF - RH or Fan Speed setpoint enabled (specic setpoint output type to be selected on DIP switch 6)
Models without RH option select only temp or fan setpoint
6 Setpoint output temperature range or
RH/Fan Speed output type
7 Display times out and turns o after
6-10 seconds of touchscreen/button press
8 Touchscreen touch functions and
buttons are disabled
* Only used with voltage output mode enabled.
Temperature setpoint (must be enabled on DIP switch 5) ON - Temp range 1, 50 to 95 °F (10 to 35 °C) enabled OFF - Temp range 2, 32 to 122 °F (0 to 50 °C) enabled
RH or Fan Speed setpoint (must be enabled on DIP switch 5) ON - RH setpoint enabled OFF - Fan Speed setpoint enabled Models without RH option, set to OFF
ON - Display Timeout enabled OFF - Display Timeout disabled
ON - Touchscreen touch/button functions disabled OFF - Touchscreen touch/button functions enabled
7. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover downward until it latches at the bottom.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 6
HW2 Series Installation Guide
Setpoint value (temperature setpoint shown)
RH value
Fahrenheit/Celsius
Temperature value
Integrator’s Submenu
Submenu Only
Fahrenheit when pressed.
Installation (cont.)
Touchscreen Operation
8. Install locking screw to secure cover in closed position.
Main Screen
The touchscreen user interface displays applicable sensor output values (temperature and RH), setpoint value and menu button.
Menu button
Menu Screen
The menu screen opens when pressing the Menu button on the main screen. Integrator’s submenu, occupancy/override, Fahrenheit/Celsius, settings and setpoint submenu (temp, RH or fan, determined by DIP switch settings) are displayed on the menu screen.
Temperature setpoint
DIP switch selected
Menu Button Functions
Press this icon to access the Integrator’s menu.
Occupied Override Button
Press this icon to provide momentary ground output to the controller
Fahrenheit/Celsius Switch
Press this icon to display either °C or °F.
RH setpoint
DIP switch selected
Fan Speed setpoint DIP switch selected
Single Press Only
Signals occupied/override call to controller.
Single Press Only
Changes units to
Changes units to Celsius when pressed.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 7
HW2 Series Installation Guide
Selected
Submenu Only
Settings
Touchscreen Operation (cont.)
This icon provides the ability to change the color scheme of the display.
Temp Setpoint Adjustment
Click this icon to access the setpoint change menu. Mutually exclusive with fan speed, set by DIP switch.
Humidity Setpoint Adjustment
Click this icon to access the setpoint change menu. Mutually exclusive with humidity and fan speed. Set by DIP switch.
Fan Speed
Click this icon to access the fan speed menu. Mutually exclusive with humidity and fan speed. Set by DIP switch.
Menu Button Functions (cont.)
Submenu Only
Submenu Only
Submenu Only
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 8
HW2 Series Installation Guide
Note: Numeric information will ash while in S
Press the Menu Advance button
Press the Menu Advance button
Note: Numeric information will ash while in S
Indicator
LCD Display Operation
Button Functions
Change Values
Menu Advance
Change Values
Display Icons
The main screen displays sensor values for RH, temperature and Celsius/Fahrenheit.
Temperature Value
Setpoint Function
Humidity Value
Override Press
A single 0-10V setpoint (temperature, RH or fan speed) can be selected via DIP switch.
Temperature Setpoint Adjustment
Adjusts setpoint up
After adjustment, wait 6 seconds or press the Menu Advance button.
Adjusts setpoint down
et mode.
Setpoint is accepted and main screen appears.
RH Setpoint Adjustment
Adjusts setpoint up
Adjusts setpoint down
et mode.
After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 9
HW2 Series Installation Guide
Press the Menu Advance button
Note: F
Press and hold the Menu Advance button for 1 second
Press the Menu Advance button 2 times
Note: ºF or ºC te
Setpoint Function (cont.)
Fan Speed Setpoint Adjustment
an speed scale ashes when in Set mode. O setting is default.
Changing Celsius and Fahrenheit Scales
2x
xt will ash while in Set mode.
Occupied/Override Button
Low
Adjusts setpoint up
Adjusts setpoint down
Adjusts from ºF to ºC
Adjusts from ºC to ºF
Override Press Indicator illuminates for 6 seconds, indicating a momentary output to ground.
Medium
High
After adjustment, wait 6 seconds or press the Menu Advance button to return to the main screen.
After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and the main screen appears.
China RoHS Compliance Information
Environment-Friendly Use Period (EFUP) Table
部件名称
Part Name
电子件
Electronic
本表格依据SJ/T11364规定编制。 O: 表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定的限量要求以下。 X: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572规定的限量要求。
(企业可在此处,根据实际情况对上表中打 的技术原因进行进一步说明。)
(Pb)
X O O O O O
This table is made according to SJ/T 11364.
O: indicates that the concentraon of hazardous substance in all of the homogeneous materials for this part is below the limit as spulated in GB/T 26572. X: indicates that concentraon of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as spulated in GB/T 26572
Z000057-0B