Veris Industries HW2TA2N User manual

Page 1
Humidity Monitoring | Analog Humidity Sensors
HW2 SERIES
Wall Mount Humidity Sensors
HW2Txxxx HW2Lxxxx HW2Xxxxx
The HW2 Series of humidity sensors for living space is a flexible multisensor platform for use with BAS controllers designed to accept 4 to 20mA, 0 to 5Vdc or 0 to 10Vdc outputs. HW2 Series sensors are available with three user interface options: touchscreen, LCD with three buttons and blank. Humidity and temperature sensors are included with all HW2 Series sensors.
SPECIFICATIONS
OPERATING ENVIRONMENT
Input Power Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Analog Output Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V
Operating Temperature Range 0 to 50 °C (32 to 122 °F)
Operating Humidity Range 0 to 95% RH non-condensing
Housing Material High-impact ABS plastic
Terminal Block Torque 0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)
RH TRANSMITTER
HS Sensor Thin-film capacitive, replaceable
Accuracy ±2% from 10 to 80% RH @ 25°C (77 °F)
Hysteresis 1.5% typical
Stability ±1% @ 20°C (68 °F) annually for 2 years
Output Range 0 to 100% RH
Temperature Coefficient
TEMPERATURE TRANSMITTER OPTION
Sensor Type Solid state, integrated circuit
Accuracy ±0.2 °C (±0.4 °F) typical
Resolution 0.1 °C (0.1 °F)
Range 0 to 50 °C (32 to 122 °F)
DISPLAY MODELS
Touchscreen
LCD
±0.1% RH/°C above or below 25 °C (77 °F) typical
61 mm (2.4 in), color, backlit, capacitive, 240x300 px Setpoint: 0-10 Vdc. Temperature, humidity or fan speed selectable Timeout override: Display timeout* Lockout override: Touchscreen/button lockout*
52mm (2.05 in), segmented with 3 buttons Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable Timeout override: Display timeout* Lockout override: Touchscreen/button lockout*
Sensor element
Thin-lm capacitive sensor element recovers from 100% saturation
Interchangable element
Fully interchangeable element to 1% or 2% accuracy with NIST calibration certicate…no calibration
Flexible
Polarity insensitive, two-wire 4 to 20 mA or 3-wire 0-5/0-10 Vdc versions…exible systems compatibity…save time in the eld, stock fewer devices
Field replaceable
Replace element in the eld… maintain accuracy and minimize downtime
Easy to install
Large wiring terminals on baseplate and snap-on covers with security screw simplify installation and service
Calibration free
Calibration-free interchangeable NIST traceable HS element
APPLICATIONS
• Controlling HVAC systems for improved comfort and energy savings
• Museums, schools, printing shops, and other locations requiring humidity control
SETPOINTS**
Temperature Setpoint
Humidity Setpoint
Fan Speed Setpoint
OVERRIDE
Override Button
WIRING TERMINALS
Terminal Blocks Screw terminals, 18-24 AWG
Screw Terminal Torque 0.2 N-m (2.0 in-lbF) max.
WARRANTY
Limited Warranty 5 years
COMPLIANCE INFORMATION
Agency Approvals
• Facilitating compliance with ASHRAE standards for environmental control and indoor air quality
0 to 10V output Scale: 10 to 35 °C (50 to 95 °F) / 0 to 50 °C (32 to 122 °F)
0 to 10V output Scale: 0 to 100% RH
0 to 10V output Off 0V, Low 3.3V, Med. 6.7V, High 10.0V
Display models feature momentary-to-ground override button
UL 916, European conformance CE: EN61000-6-2 EN61000-6-3 EN61000 Series - industrial immunity EN 61326-1 FCC Part 15 Class B, REACH, RoHS, RCM (Australia), ICES-003 (Canada)
*DIP switch selectable.. ** One setpoint type is selectable via DIP switch on display models only.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 2
POWER (+24)
Humidity Monitoring | HW2 SeriesHumidity Monitoring | Analog Humidity Sensors
(4.5)
(3.3)
OR OUT
POWER (+24)
OR OUT
DIMENSIONAL DRAWING USER INTERFACE TYPES
115
85
24
(0.9)
HW2L/HW2T DISPLAY MODELS WITH TEMP TRANSMITTER
Wiring Diagram
OVERRIDE
SETPOINT OUT
RH OUT
TEMP OUT
COMMON
10 9876 5432 1
HW2X WITH TEMP TRANSMITTER
Wiring Diagram
RH OUT
TEMP OUT
COMMON
Touchscreen
LCD with Buttons
Blank
HW2L/HW2T DISPLAY MODELS WITH RTD/THERMISTOR
Wiring Diagram
OVERRIDE
SETPOINT OUT
RH OUT
RTD/THERMISTOR OUT
RTD/THERMIST
COMMON
POWER (+24)
10 9876 5432 1
HW2X WITH RTD/THERMISTOR
Wiring Diagram
RH OUT
RTD/THERMISTOR OUT
RTD/THERMIST
COMMON
POWER (+24)
54321
54321
ORDERING INFORMATION
User Interface TemperatureOutput RH Accuracy*
HW2
T
=
Color touchscreen
L
=
3-but ton LCD display
X
=
None
A = Analog output 2 = 2%
A
=
Transmitter only
C
=
1000 PT RT D
D
=
10K T2 therm istor
G
=
10K CPC therm istor**
H
=
10K T3 therm istor
K
=
10K curve G/11K shunt
M
=
20K NTC ther mistor
N
=
1.8K TAC thermist or
R
=
10K curve G** *
Example:
HW2
* Replace able 1% with NIST cert icate, 2% with NIS T certicate and 2 % elements availa ble. ** Availab le in HW2XA2G onl y. *** Avail able in HW2XA2R o nly.
2
AAT
REPLACEABLE RH ELEMENTS
MODEL RH ACCU RACY
HS1N ±1% X Replaceable RH sensor, 1% with NIST certication
HS2N ±2% X Replaceable RH sensor, 2% with NIST certication
HS2X ±2% Replaceable RH sensor, 2%