Z20526 6-0B
08 113
Z20526 6-0B
08 113
TM
HS SENSOR
REPLACEMENT
PRODUCT IDENTIFICATION
Accurac y NIST
HS X
1 = 1%*
N = NIST (1% and
2 = 2%
2% models only)
3 = 3%
X = None (2%, 3%,
5 = 5%
and 5% models
only)
INSTALLATION
For all unit types, ensure that the four HS pin holes are
inserted fully onto the unit pin connec tors.
Humidity Outdoor and Duct Units
1. Disconnect power to the unit.
2. Remove probe f rom junction box by loosening black
swage nut and sliding out.
3. Unscrew lter on tip of probe. Set lter aside.
4. Remove HS element by gently pulling from pin
connector. Do not attempt to remove temperature
sensor adjacent to HS element (if equipped).
5. Place new HS element onto pin connec tor. Orient as
shown, or unit will not function (lter will not screw
on if HS is inser ted incorrectly).
6. Replace lter. Re-insert probe into junction box and
tighten swage nut.
* 1% HS sensors used in outdoor
applicatio ns are limited by the
device to 2% accuracy.
The microprocessor-proled
capacitive HS element can be
replaced in the el d without
calibration.
HS sensor elements are sold as open devices.
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.
Top
Side
Bottom
Side
Temp sensor
(if equipped)
Top
Side
Bottom
Side
TM
HS SENSOR
REPLACEMENT
PRODUCT IDENTIFICATION
Accurac y NIST
HS X
1 = 1%
N = NIST (1% and
2 = 2%
2% models only)
3 = 3%
X = None (2%, 3%,
5 = 5%
and 5% models
only)
INSTALLATION
For all unit types, ensure that the four HS pin holes are
inserted fully onto the unit pin connec tors.
Humidity Outdoor and Duct Units
1. Disconnect power to the unit.
2. Remove probe f rom junction box by loosening black
swage nut and sliding out.
3. Unscrew lter on tip of probe. Set lter aside.
4. Remove HS element by gently pulling from pin
connector. Do not attempt to remove temperature
sensor adjacent to HS element (if equipped).
5. Place new HS element onto pin connec tor. Orient as
shown, or unit will not function (lter will not screw
on if HS is inser ted incorrectly).
6. Replace lter. Re-insert probe into junction box and
tighten swage nut.
* 1% HS sensors used in outdoor
applicatio ns are limited by the
device to 2% accuracy.
The microprocessor-proled
capacitive HS element can be
replaced in the el d without
calibration.
HS sensor elements are sold as open devices.
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.
Top
Side
Bottom
Side
Temp sensor
(if equipped)
Top
Side
Bottom
Side
TM
HS SENSOR
REPLACEMENT
PRODUCT IDENTIFICATION
Accurac y NIST
HS X
1 = 1%
N = NIST (1% and
2 = 2%
2% models only)
3 = 3%
X = None (2%, 3%,
5 = 5%
and 5% models
only)
INSTALLATION
For all unit types, ensure that the four HS pin holes are
inserted fully onto the unit pin connec tors.
Humidity Outdoor and Duct Units
1. Disconnect power to the unit.
2. Remove probe f rom junction box by loosening black
swage nut and sliding out.
3. Unscrew lter on tip of probe. Set lter aside.
4. Remove HS element by gently pulling from pin
connector. Do not attempt to remove temperature
sensor adjacent to HS element (if equipped).
5. Place new HS element onto pin connec tor. Orient as
shown, or unit will not function (lter will not screw
on if HS is inser ted incorrectly).
6. Replace lter. Re-insert probe into junction box and
tighten swage nut.
* 1% HS sensors used in outdoor
applicatio ns are limited by the
device to 2% accuracy.
Z20526 6-0B
08 113
The microprocessor-proled
capacitive HS element can be
replaced in the el d without
calibration.
HS sensor elements are sold as open devices.
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.
Top
Side
Bottom
Side
Temp sensor
(if equipped)
Top
Side
Bottom
Side
TM
HS SENSOR
REPLACEMENT
PRODUCT IDENTIFICATION
Accurac y NIST
HS X
1 = 1%
N = NIST (1% and
2 = 2%
2% models only)
3 = 3%
X = None (2%, 3%,
5 = 5%
and 5% models
only)
INSTALLATION
For all unit types, ensure that the four HS pin holes are
inserted fully onto the unit pin connec tors.
Humidity Outdoor and Duct Units
1. Disconnect power to the unit.
2. Remove probe f rom junction box by loosening black
swage nut and sliding out.
3. Unscrew lter on tip of probe. Set lter aside.
4. Remove HS element by gently pulling from pin
connector. Do not attempt to remove temperature
sensor adjacent to HS element (if equipped).
5. Place new HS element onto pin connec tor. Orient as
shown, or unit will not function (lter will not screw
on if HS is inser ted incorrectly).
6. Replace lter. Re-insert probe into junction box and
tighten swage nut.
* 1% HS sensors used in outdoor
applicatio ns are limited by the
device to 2% accuracy.
Z20526 6-0B
08 113
The microprocessor-proled
capacitive HS element can be
replaced in the el d without
calibration.
HS sensor elements are sold as open devices.
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.
Top
Side
Bottom
Side
Temp sensor
(if equipped)
Top
Side
Bottom
Side
CO2 Duct Units
1. Disconnect power to the unit.
2. Remove unit from duct.
3. Lift lid at end of probe.
4. Remove HS element by gently pulling from pin
connector.
5. Place new HS element onto pin connec tor. Orient
as shown, or unit will not function.
6. Close lid.
7. Replace unit in duct.
Lift to open tip
of probe
Pins
HS Sensor
Top
Side
CO2 Duct Units
1. Disconnect power to the unit.
2. Remove unit from duct.
3. Lift lid at end of probe.
4. Remove HS element by gently pulling from pin
connector.
Lift to open tip
of probe
Pins
HS Sensor
Top
Side
5. Place new HS element onto pin connec tor. Orient
Lift to open tip
of probe
Pins
HS Sensor
Bottom
Side
as shown, or unit will not function.
6. Close lid.
7. Replace unit in duct.
Lift to open tip
of probe
Pins
HS Sensor
Bottom
Side
Wall Units
1. Disconnect power to the unit.
2. Remove faceplate.
3. Remove HS element by gently
pulling from pin connector.
4. Place new HS element onto pin
connector. Orient as shown, or unit
will not function.
5. Replace faceplate.
CO2 Duct Units
1. Disconnect power to the unit.
2. Remove unit from duct.
3. Lift lid at end of probe.
4. Remove HS element by gently pulling from pin
connector.
5. Place new HS element onto pin connec tor. Orient
as shown, or unit will not function.
6. Close lid.
7. Replace unit in duct.
Top
Side
Wall Units
1. Disconnect power to the unit.
2. Remove faceplate.
3. Remove HS element by gently
pulling from pin connector.
4. Place new HS element onto pin
connector. Orient as shown, or unit
will not function.
5. Replace faceplate.
Bottom
Side
Z20526 6-0B
08 113
Lift to open tip
of probe
Pins
HS Sensor
Top
Side
CO2 Duct Units
1. Disconnect power to the unit.
2. Remove unit from duct.
3. Lift lid at end of probe.
4. Remove HS element by gently pulling from pin
connector.
5. Place new HS element onto pin connec tor. Orient
Lift to open tip
of probe
Pins
HS Sensor
Bottom
Side
as shown, or unit will not function.
6. Close lid.
7. Replace unit in duct.
Top
Side
Bottom
Side
Z20526 6-0B
08 113
Lift to open tip
of probe
Pins
HS Sensor
Top
Side
Lift to open tip
of probe
Pins
HS Sensor
Bottom
Side
Wall Units
1. Disconnect power to the unit.
2. Remove faceplate.
3. Remove HS element by gently
pulling from pin connector.
4. Place new HS element onto pin
connector. Orient as shown, or unit
will not function.
5. Replace faceplate.
Top
Side
Bottom
Side
Z20526 6-0B
08 113
Wall Units
1. Disconnect power to the unit.
2. Remove faceplate.
3. Remove HS element by gently
pulling from pin connector.
4. Place new HS element onto pin
connector. Orient as shown, or unit
will not function.
5. Replace faceplate.
Top
Side
Bottom
Side
Z20526 6-0B
08 113