Veris Industries HS SENSOR Installation Guide

Z20526 6-0B
08 113
Z20526 6-0B
08 113
TM
HS SENSOR
REPLACEMENT
PRODUCT IDENTIFICATION
Accurac y NIST
HS X
1 = 1%*
N = NIST (1% and
2 = 2%
2% models only)
3 = 3%
X = None (2%, 3%,
5 = 5%
and 5% models only)
INSTALLATION
For all unit types, ensure that the four HS pin holes are inserted fully onto the unit pin connec tors.
Humidity Outdoor and Duct Units
1. Disconnect power to the unit.
2. Remove probe f rom junction box by loosening black swage nut and sliding out.
3. Unscrew lter on tip of probe. Set lter aside.
4. Remove HS element by gently pulling from pin connector. Do not attempt to remove temperature sensor adjacent to HS element (if equipped).
5. Place new HS element onto pin connec tor. Orient as shown, or unit will not function (lter will not screw on if HS is inser ted incorrectly).
6. Replace lter. Re-insert probe into junction box and tighten swage nut.
* 1% HS sensors used in outdoor applicatio ns are limited by the device to 2% accuracy.
The microprocessor-proled capacitive HS element can be replaced in the el d without calibration.
HS sensor elements are sold as open devices. Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty.
Top
Side
Bottom
Side
Temp sensor (if equipped)
Top
Side
Bottom
Side
TM
HS SENSOR
REPLACEMENT
PRODUCT IDENTIFICATION
Accurac y NIST
HS X
1 = 1%
N = NIST (1% and
2 = 2%
2% models only)
3 = 3%
X = None (2%, 3%,
5 = 5%
and 5% models only)
INSTALLATION
For all unit types, ensure that the four HS pin holes are inserted fully onto the unit pin connec tors.
Humidity Outdoor and Duct Units
1. Disconnect power to the unit.
2. Remove probe f rom junction box by loosening black swage nut and sliding out.
3. Unscrew lter on tip of probe. Set lter aside.
4. Remove HS element by gently pulling from pin connector. Do not attempt to remove temperature sensor adjacent to HS element (if equipped).
5. Place new HS element onto pin connec tor. Orient as shown, or unit will not function (lter will not screw on if HS is inser ted incorrectly).
6. Replace lter. Re-insert probe into junction box and tighten swage nut.
* 1% HS sensors used in outdoor applicatio ns are limited by the device to 2% accuracy.
The microprocessor-proled capacitive HS element can be replaced in the el d without calibration.
HS sensor elements are sold as open devices. Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty.
Top
Side
Bottom
Side
Temp sensor (if equipped)
Top
Side
Bottom
Side
TM
HS SENSOR
REPLACEMENT
PRODUCT IDENTIFICATION
Accurac y NIST
HS X
1 = 1%
N = NIST (1% and
2 = 2%
2% models only)
3 = 3%
X = None (2%, 3%,
5 = 5%
and 5% models only)
INSTALLATION
For all unit types, ensure that the four HS pin holes are inserted fully onto the unit pin connec tors.
Humidity Outdoor and Duct Units
1. Disconnect power to the unit.
2. Remove probe f rom junction box by loosening black swage nut and sliding out.
3. Unscrew lter on tip of probe. Set lter aside.
4. Remove HS element by gently pulling from pin connector. Do not attempt to remove temperature sensor adjacent to HS element (if equipped).
5. Place new HS element onto pin connec tor. Orient as shown, or unit will not function (lter will not screw on if HS is inser ted incorrectly).
6. Replace lter. Re-insert probe into junction box and tighten swage nut.
* 1% HS sensors used in outdoor applicatio ns are limited by the device to 2% accuracy.
Z20526 6-0B
08 113
The microprocessor-proled capacitive HS element can be replaced in the el d without calibration.
HS sensor elements are sold as open devices. Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty.
Top Side
Bottom
Side
Temp sensor (if equipped)
Top Side
Bottom
Side
TM
HS SENSOR
REPLACEMENT
PRODUCT IDENTIFICATION
Accurac y NIST
HS X
1 = 1%
N = NIST (1% and
2 = 2%
2% models only)
3 = 3%
X = None (2%, 3%,
5 = 5%
and 5% models only)
INSTALLATION
For all unit types, ensure that the four HS pin holes are inserted fully onto the unit pin connec tors.
Humidity Outdoor and Duct Units
1. Disconnect power to the unit.
2. Remove probe f rom junction box by loosening black swage nut and sliding out.
3. Unscrew lter on tip of probe. Set lter aside.
4. Remove HS element by gently pulling from pin connector. Do not attempt to remove temperature sensor adjacent to HS element (if equipped).
5. Place new HS element onto pin connec tor. Orient as shown, or unit will not function (lter will not screw on if HS is inser ted incorrectly).
6. Replace lter. Re-insert probe into junction box and tighten swage nut.
* 1% HS sensors used in outdoor applicatio ns are limited by the device to 2% accuracy.
Z20526 6-0B
08 113
The microprocessor-proled capacitive HS element can be replaced in the el d without calibration.
HS sensor elements are sold as open devices. Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty.
Top Side
Bottom
Side
Temp sensor (if equipped)
Top Side
Bottom
Side
CO2 Duct Units
1. Disconnect power to the unit.
2. Remove unit from duct.
3. Lift lid at end of probe.
4. Remove HS element by gently pulling from pin connector.
5. Place new HS element onto pin connec tor. Orient as shown, or unit will not function.
6. Close lid.
7. Replace unit in duct.
Lift to open tip of probe
Pins
HS Sensor
Top
Side
CO2 Duct Units
1. Disconnect power to the unit.
2. Remove unit from duct.
3. Lift lid at end of probe.
4. Remove HS element by gently pulling from pin connector.
Lift to open tip of probe
Pins
HS Sensor
Top
Side
5. Place new HS element onto pin connec tor. Orient
Lift to open tip of probe
Pins
HS Sensor
Bottom
Side
as shown, or unit will not function.
6. Close lid.
7. Replace unit in duct.
Lift to open tip of probe
Pins
HS Sensor
Bottom
Side
Wall Units
1. Disconnect power to the unit.
2. Remove faceplate.
3. Remove HS element by gently pulling from pin connector.
4. Place new HS element onto pin connector. Orient as shown, or unit will not function.
5. Replace faceplate.
CO2 Duct Units
1. Disconnect power to the unit.
2. Remove unit from duct.
3. Lift lid at end of probe.
4. Remove HS element by gently pulling from pin connector.
5. Place new HS element onto pin connec tor. Orient as shown, or unit will not function.
6. Close lid.
7. Replace unit in duct.
Top
Side
Wall Units
1. Disconnect power to the unit.
2. Remove faceplate.
3. Remove HS element by gently pulling from pin connector.
4. Place new HS element onto pin connector. Orient as shown, or unit will not function.
5. Replace faceplate.
Bottom
Side
Z20526 6-0B
08 113
Lift to open tip of probe
Pins
HS Sensor
Top
Side
CO2 Duct Units
1. Disconnect power to the unit.
2. Remove unit from duct.
3. Lift lid at end of probe.
4. Remove HS element by gently pulling from pin connector.
5. Place new HS element onto pin connec tor. Orient
Lift to open tip of probe
Pins
HS Sensor
Bottom
Side
as shown, or unit will not function.
6. Close lid.
7. Replace unit in duct.
Top
Side
Bottom
Side
Z20526 6-0B
08 113
Lift to open tip of probe
Pins
HS Sensor
Top
Side
Lift to open tip of probe
Pins
HS Sensor
Bottom
Side
Wall Units
1. Disconnect power to the unit.
2. Remove faceplate.
3. Remove HS element by gently pulling from pin connector.
4. Place new HS element onto pin connector. Orient as shown, or unit will not function.
5. Replace faceplate.
Top
Side
Bottom
Side
Z20526 6-0B
08 113
Wall Units
1. Disconnect power to the unit.
2. Remove faceplate.
3. Remove HS element by gently pulling from pin connector.
4. Place new HS element onto pin connector. Orient as shown, or unit will not function.
5. Replace faceplate.
Top
Side
Bottom
Side