Veris Industries HO Series Installation Guide

TM
HO SerieS HO SerieS
Availabl e
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
ENVIRONMENTAL SENSORS
Accuracy NIST
HO
2 = 2% 3 = 3% 5 = 5%
N = NIST X = None
Output
M = 4-20mA V = 0-5V/0-10VDC
US or EU Temp.
S = Standard C = CE
T = Temp X = No Temp (Stop here)
INSTALLATION GUIDE
Digital RH and RH/T Transmitters
Installer’s Specifications
HS Element Digitally proled thin-lm capacitive (32-bit mathematics) U.S. Patent No. 5,844,138 Accuracy @ 25°C from 10-80% RH* 2%, 3%, or 5% (specif y); Multi-point calibration, NIST traceable Reset Rate** 24 hours Stability ±1% @ 20°C (68°F) annually, for two years Operating
Humidity Range 0 to 100% RH Operating Temperature Range -40° to 50°C (-40° to 122°F) Hysteresis 1.5% typical Linearity Included in Accuracy spec. Temperature Analog 0-5V/0-10V versions: 3 wire; observe polarity Scaling 0–100% RH Input 0-5V/0-10V versions: 12-30VDC/24VDC, 15mA max. Optional or 0-5V/0-10V output; accuracy ±1.3°C (±2.3°F) typical EMC EN61000-4-3, ENV 50204, EN61000-4- 6
* Specied accuracy with 24VDC supplied power with rising humid ity. ** Reset Rate is the time required to recover to 50% RH after e xposure to 90% RH for 24 hours. *** One side of transformer seconda ry is connected to signal common. Isolation transformer or dedicated power supply may be requ ired. RTD Thermistors are not compenstated for internal heating of product To conform to EMC standards, shielded cabling and technical i nformation is available from factory upon request or is availab le on our website: www.veris.com
QUICK INSTALL
Coeff icient ±0.1% RH/°C above or below 25°C (typical)
Output 4-20mA version: 2-wire, polarity insensitive (clipped and capped);
Power*** 4-20mA version: loop powered 12-30VDC only, 30mA max.;
Temperature Transmit ter Output Digital, 4-20mA (clipped and capped)
Conformance - CE Option EN50081-1, EN 50082-1, EN 61000-4-4, EN 61000-4-5,
Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty.
Humidity Transmitter Combination Humidity RTD/Thermistor Combination
OPTION
Temp Cert
Blank = None 1 =1pt Cal 2 = 2pt Cal
Sensor Type Range
A
= Transmitter
1 = -40° to 50 °C (-40° to 122°F ) 2 = 0° to 50°C (32° to 122°F)
OPTION
Temp Cert
Blank = None 1 =1pt Cal 2 = 2pt Cal
Sensor Type
B = 100R Platinu m, RTD C = 1k Platinum, RTD D = 10k T2, Therm istor E = 2.2k, Ther mistor F = 3k, Therm istor G = 10k CPC, Ther mistor H = 10k T3, Thermi stor J = 10k Dale, Ther mistor K = 10k with 11k shunt, Ther mistor M = 20k NTC, Ther mistor N = 1800 ohm TAC, Thermi stor Q = 1uA/˚C, Linite mp R = 10k US, Thermis tor S = 10k 3A 221, Thermisto r T = 100k, The rmistor U = 20k “D”, Thermis tor
1. Choose an outdoor location in a sheltered area, out of direct sunlight.
2. Mount unit with probe pointing down. Unit may be suspended by conduit. Do not
obstruct vent openings.
3. Wire probe (see Wiring section). Leave wires at factory length to allow for a service
loop (to remove sensor from junction box for service without disturbing the conduit).
DIMENSIONS
2.7"
(69 mm)
2.3"
(58 mm)
2.8"
(72 mm)
4.6"
(116 mm)
12.2"
(310 mm)
0.7"
(18 mm)
Z201382-0X PAGE 1 ©2011 Veris Industries 02112
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
POWER SUPPLY
24 VDC only
DIGITAL CONTROL
Temperature
4-20mA Return
(optional)
Humidity
4-20mA Return
BLUE HUMIDITY
BLUE HUMIDITY
White/Gray 0-1V Test Leads for use with voltmeter
ORANGE TEMP
ORANGE TEMP
+
POWER SUPPLY
24 VDC
BLK
RED
BLUE 0-10V HUMIDITY ORANGE 0-10V TEMP
GREEN 0-5V HUMIDITY
YELLOW 0-5V TEMP
+
8.45"
(215 mm)
POWER SUPPLY
12 to 24 VDC
DIGITAL CONTROL
Temperature
4-20mA Return
(optional)
Humidity
4-20mA Return
BLUE HUMIDITY
BLUE HUMIDITY
White/Gray 0-1V Test Leads for use with voltmeter
ORANGE Thermistor
ORANGE Thermistor
+
POWER SUPPLY
12 to 24 VDC/24 VAC
BLK
RED
BLUE 0-10V HUMIDITY
GREEN 0-5V HUMIDITY
ORANGE THERMISTOR
ORANGE THERMISTOR
+
HO SERIES
INSTALLATION GUIDE
OPERATION
The HO Series outdoor humidity sensors provide high accuracy humidity monitoring with a fully replaceable HS element for easy eld maintenance. NIST certied accuracy and temperature sensing capability are available.
WIRING
0-5V/0-10V Versions
NOTE: For 24 VAC transformer powered applicatio ns, one side of transformer secondary is con­nected to common. Isolation transform er or dedicated power supply may be required.
4-20mA Versions
TROUBLESHOOTING
Problem Solution
Filter tip does not t on probe HS element is backwards; reverse element.
Unit reads approx. 4.5mA HS element is backwards; reverse element.
Unit reads 100% with new
replacement sensor
Accuracy appears incorrect · Remove HS element while powered and verify output
Unit must be unpowered when installing a new sensor;
interrupt sensor power to restart.
goes to full scale.
· Verify voltage test leads on 4-20mA models corresponds to the 4-20mA output.
RTD/Thermistor, 0-5V/0-10V Versions
RTD/Thermistor, 4-20mA Versions