Veris Industries H932, H952 Data Sheet

SENSED AMPS
30/60/120 A*
0 V
0 A
5 V
SENSOR OUTPUT
*Factory calibrated ranges selected with the amperage range switch
Minimize Installed Cost
Current Monitoring | Current Transducers with Relay:
0 to 5 Vdc Analog Output
H932 & H952
Load Trending and Control Relay in One Package
H932
TM
Maximize Reliability
The Hawkeye 932 and 952 Series provide accurate load trending information with a proportional 0 to 5 Vdc output signal. This feature combined with an integrated command relay makes these products ideal for start/stop and status monitoring of motors.
The relay is fully isolated from the current sensor, and all relay connections are externally available for maximum flexibility.
Self-powered
Self-powered analog current transducer with integral start/stop command relay
Saves time
Reduces the number of installed components…saves time and space
Retrofit
Self-gripping, split-core design for fast retrofit installation…no need to remove conductor
APPLICATIONS
• Load trending
• Motor control
• Fan/pump status
Reduces installation
One device to install for start/stop and status
No external power
No external power required for current sensor
Increased flexibility
Selectable factory calibrated ranges up to 120 A for increased flexibility and resolution
EXAMPLE LINEAR OUTPUT
Scale software as shown
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Insulation Class 600 Vac RMS
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Accuracy ±2% F.S. from 10% to 100% (selected range)
Response Time 2 sec.
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals
Note: Do not use LED status indicators as evidence of applied voltage
UL 508 open device listing, CAT III, Pollution Degree 2, basic insulation
)
TM
HQ0001767.F 0117
Current Monitoring | H932 & H952
H932/H952
Dimensional Drawing
Removable Mounting Bracket
1.0”
(25 mm)
1.1”
(26 mm)
3.1”**
(79 mm)
Ø 0.3”
(8 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown.
(21 mm)
(70 mm)
3.0”
(76 mm)
0.8”
2.8”
2.5”
(64 mm)
RELAY CONTACT RATINGS (N.O.)
Resistive 5 A @ 250 Vac, 30 Vdc
5 A @ 30 Vac, 30 Vdc
Inductive 2 A @ 250 Vac, 30 Vdc
2 A @ 30 Vac, 30 Vdc
TYPICAL COIL PERFORMANCE
Voltage AC DC
24 (H932) 15 15
12 (H952) 20
Pull In Voltage (H952 only)
12 Vdc 8.4 Vdc
Drop Out Voltage (H952 only)
12 Vdc 3.0 Vdc
Bracket can be mounted on three sides for added installation flexibility.
Self-gripping Iris
1.4”*
(36 mm)
TRENDING & CONTROLLING MOTOR LOADS WITH THE HAWKEYE 932
Wiring Diagram
CONTROLLER
Digital Output (Relay Coil) Analog Input (0 to 5 Vdc)
CONTROL
POWER
CONTACTOR
Fan or Pump
Motor
ORDERING INFORMATION
MODEL
H932
H952 12 Vdc
HQ0001767.F 0117
AMPE RAGE
RANGE
0 to 30/60/120 A 0 to 5 Vdc SPST, N.O.
SENSOR OUTPUT
RE LAY
TYPE
24 Vac/dc
TM
RE LAY
COIL
HOUSING UL
Split-core
Loading...