Veris Industries H721xC Series, H921 Series Data Sheet

Current Monitoring |
Current Transducers: 4 to 20 mA Analog Output
H721xC Series & H921
H921
H721HC
TM
SPECIFICATIONS
Sensor Powe r 30 mA (max) @ 12 to 30 Vdc
Insulation Class 600 Vac RMS (UL), 30 0 Vac RMS (CE1)
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Accuracy
Response Time 2 sec.
Terminal Bloc k Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N -m)
Agency Approvals
Limited Warranty 5 years
1. The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details.
±2% F.S. from 10% to 100% of s elected range, b ut not less than ±0.4 A
UL 508 open de vice listing; CE: EN61010-1, CAT III, pollutio n degree 2, basic insulation
Maximize Reliability
Minimize Installed Cost
LOAD TRENDING WITH 4 TO 20 MA OUTPUT
DESCRIPTION
The Hawkeye 721LC, 721HC, and 921 provide accurate load trending information with a proportional 4-20mA output signal. Preset slide­switches provide easy eld setup of sensed amperage range with no need for jumpers.
APPLICATIONS
• Load trending
• Motor control
• Fan/Pump Status
EXAMPLE LINEAR OUTPUT
Scale software as shown
20mA
SENSOR OUTPUT
4mA
0A
SENSED AMPS
*Factory calibrated ranges selected
with the amperage range switch
Selected Range*
FEATURES
• Power the sensor, and receive the signal with only two wires...lower cabling and commissioning costs than with traditional 3-wire sensors
• Self-gripping, split-core design for fast retrot installation...no need to remove conductor (H921)
• Economical solid-core features adjustable bracket for easy alignment (H721 Series)
• Factory calibrated switch-selectable ranges for high resolution and installation ease
• Three eld-selectable ranges per unit...fewer versions to choose from, stock, and install
• Removable mounting bracket for installation exibility
• Bracket on H921 can be installed in three dierent congurations...added exibility
• 100% solid state, no moving parts to fail
• 5-year warranty
TM
HQ0001762.E 0116
Current Monitoring | H721xC Series & H921
DIMENSIONAL DRAWINGS
H721LC/H721HC
Removable/Adjustable Mounting Bracket
 0.7"
(19 mm)
0.2” x 0.15” slot (2x)
1.1”
(26 mm)
3.1”**
(79 mm)
Ø 0.3”
(8 mm)
2.8"
(68 mm)
3.8"
(95 mm)
4.2"
(106 mm)
H921
Removable Mounting Bracket
0.8”
(21 mm)
2.8”
(70 mm)
2.5”
(64 mm)
3.0”
(76 mm)
(25 mm)
1.0”
0.9" (23 mm)
3.0" **
(75 mm)
1.1" *
(27 mm)
Bracket can be mounted on three sides for added installation flexibility.
Self-gripping Iris
1.4”*
(36 mm)
WIRING DIAGRAMS
Monitoring Fan /Pump Motors for Positive Proof of Flow
DDC CONTROLLER
AI
+
+ -
12 to 30Vdc
Power Source
Voltage Output
+
CONTROLLER
CONTACTOR
Fan or Pump
Motor
Voltage input 250Ω = 1 to 5 Vdc 500Ω = 2 to 10 Vdc
* Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown.
ORDERING INFORMATION
MODEL AMPERAGE RANGE SENSOR OUTPUT HOUSING UL CE
H721LC 0 to 10/20/40 A
H721H C 0 to 50/100/200 A Solid-Core
H921 0 t o 30/60/120 A Split-Core
1. Listed for use on 75 °C insulated conductors. Note: For 10 to 80 Hz applications, see the H720 VFD sensor.
4 to 20 mA DC
Solid-Core
n n
n n
1
n
ACCESSORIES
DIN Rail Clip Set (AH01) DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ0001762.E 0116
AH01
AV01 AV02
n
Loading...