Power Monitoring Single-Circuit | Power Meter for Voltage-Mode CTs
H84XXV, H84XXVB,
& H84XXVBS SERIES
Revenue Grade Power Meter
for Voltage Mode CTs
BACnet
Connectivity
Via E8951 Gateway
The H84xxV, H84xxVB, and H84xxVBS Series digital power meters
deliver high accuracy and high value at a competitive price.
Whether you are looking for a 1-phase pulse output meter to monitor
kWh, or a 3-phase communicating meter to monitor THD, the H84xxV
Series has the right meter for you, in panel and wall mounting styles for
your convenience.
The pulse output unit offers two pulse outputs. While kWh is standard,
the second pulse output provides a field-selectable choice between
phase loss or kVARh.
The Modbus communications unit offers a choice between two data
outputs, Full Data Set (FDS) or Extended Data Set (EDS). Data points are
listed on the next page.
SPECIFICATIONS
INPUTS
Control Power 100 to 415 ± 10% Vac, 5 VA, 45 to 60 Hz*
DC 125 to 250 Vdc ± 20% Vdc, 3 W, external current
Voltage Input UL: 600 Vac; CE: 300 Vac (L-N)
CURRENT INPUT
CT Scaling Primary: Adjustable from 5 A to 32,767 A
Measurement Input
Range
ACCURACY
Current and Voltage 0.5%
Power ANSI C12.16, 1%
Measurement - True
RMS
OUTPUTS
Pulse Output #1 (kWh) N.O. Static Output (240 Vac or 300 Vdc, 100 mA
limiting required
1 V RMS full scale (+20% over-range). CTs must be
rated for use with Class 1 voltage inputs
True RMS up to 15th harmonic, 3-phase AC System
max. @ 25 ˚C, derate 0.56 mA per ˚C above 25 ˚C) 2.41
kV RMS isolation
Revenue grade
measurements
Meets ANSI C12.20 Class 0.2
standards
Intuitive
navigation
Context-sensitive menus for easy use
Trouble-free
installation
Automatically detects and corrects
phase reversal, eliminating the
need to be concerned with CT
load orientation
Mounting
flexibility
Panel, wall, DIN rail mount
Real-time
Real-time power monitoring via
local display or through
control/data acquisition systems
Large display
Large, easy-to-read display
APPLICATIONS
• Energy monitoring in building
automation systems
• Renewable energy
• Energy management
Pulse Output #2
(H8463V/VB/VBS)
MECHANICAL
Weight H84xxV: 0.8 lbs; H84xxVB: 6.35 lbs;
Protection Class V: IP40 front, IP30 back; VB: NEMA 1, IP40
ENVIRONMENTAL
Altitude of Operation 3000 m
Operating Temp Range Meter: 0 to 60 °C (32 to 140 °F);
Storage Temp Range Meter and Display: -40 to 85 °C (-40 to 185 °F)
Humidity Range 0 to 95% non-condensing; indoor use only
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals UL508; Cat. III, Pollution Degree 2, for distribution
**
* For control voltages >415 Vac to 600 Vac order H8 4xxVBS.
**The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
(Phase Loss or kVARh) N.C. Static Output (240 Vac or
300 Vdc, 100 mA max. @ 25 ˚C, derate 0.56 mA per˚C
above 25˚C) 2.41 kV RMS isolation
H84xxVBS: 9.15 lbs
Display: -10 to 50 °C (14 to 122 °F)
systems up to 347VAC (L-N)/600VAC (L-L);
CE per IEC61010-1, Cat. III, Pollution Degree 2, for
distribution systems up to 300 Vac (L-N)/480 Vac (L-L)
• Commercial sub-metering
• Industrial monitoring
• Cost allocation
TM
HQ0001713.F 0117
Power Monitoring Single-Circuit | H84xxV, H84xxVB, & H84xxVBS Series
DIMENSIONAL DRAWINGSORDERING INFORMATION
MODEL DESCRIPTION DATA OUTPUT DISPLAY SCREENS
PANEL MOUNT - 120 to 480 V
(For Control Volt ages > 415 Vac to
600 Vac, or der H84x xVBS)
H8463V*
H8453V*
H8436V
H8437V
Panel Moun t, 1 V, CT Input, FDS
Panel Moun t, 1 V, CT Input, FDS
Panel Moun t, 1 V, CT Input, FDS
Panel Moun t, 1 V, CT Input, E DS
WALL MOUNT - 120 to 480 V
(For Control Voltages > 415 Vac
to 600 Vac, order H84xxVBS)
H8463VB*
H8453VB*
H8436VB
H8437VB
Wall Mount, 1 V, CT Input, FDS
Wall Mount, 1 V, CT Input, FDS
Wall Mount, 1 V, CT In put, FDS
Wall Mount, 1 V, CT In put, EDS
WALL MOUNT - 240-600V Pulse
H84 63VBS*
H8453VBS**
H8436VBS
H8437VBS
*The H8453 has two normally open solid-state outputs: one kWh and one eld-selectable for phase
loss or kVARh. The H8463 has one normally open output (kWh) and one normally closed output
(eld selectable for phase loss or kVAR).
Wall Mount, 1 V, CT Input, FDS,
240 to 600 V
Wall Mount, 1 V, CT Input, FDS,
240 to 600 V
Wall Mount, 1 V, CT Input, FDS,
240 to 600 V
Wall Mount, 1 V, CT Input, FDS,
240 to 600 V
Pulse Modbus FDS EDS
• •
• •
• •
• •
Pulse Modbus FDS EDS
• •
• •
• •
• •
Modbus
FDS EDS
• •
• •
• •
• •
(92 mm)
+0.8
3.6"
–0.0
(92 mm)
+0.8
–0.0
3.9"
(96 mm)
2"
(50 mm)
8.3"
(210 mm)
H8400 SERIES
0.8"
(19 mm)
3.9"
(96 mm)
4.1"
(104 mm)
(242 mm)
9.1"
DATA OUTPUTS
H8436: Full Data Set (FDS)
kWh, Consumption
kW, Real Power
kVAR, Reactive power
kVA, Apparent power
Power factor
Voltage, line to line
Voltage, line to neutral
Amps, Average current
kW, Real power ØA
kW, Real power ØB
kW, Real power ØC
Power factor ØA
Power factor ØB
Power factor ØC
Voltage, ØA to ØB
Voltage, ØB to ØC
Voltage, ØA to ØC
Voltage, ØA to Neutral
Voltage, ØB to Neutral
Voltage, ØC to Neutral
Amps, Current ØA
Amps, Current ØB
Amps, Current ØC
HQ0001713.F 0117
H8437: Extended Data Set (EDS)
(FDS Plus):
Amps, Current Neutral
Frequency
kVAh, Consumption
kVARh, Consumption
Minimum Real power
Maximum Real power
KVA, Apparent Power, Per Phase
KVAR, Reactive Power, Per Phase
KW, Total Real Power Present Demand
KVA, Total Apparent Power Present Demand
KVAR, Total Reactive Power Present Demand
KW, Total Real Power Max Demand
KVA, Total Apparent Power Max Demand
KVAR, Total Reactive Power Max Demand
THD, Voltage A-N, B-N, C-N
THD, Voltage A-B, B-C, A-C
THD, Current, Per Phase
Usage Hours
Usage Minutes
Total Hours
Total Minutes
TM
COMPANION CURRENT TRANSFORMERS
(Model/Amps)
H681
Small:
0-100 = 100 A
0-200 = 200 A
0-300 = 30 0 A
Medium:
1-400 = 4 00 A
1-600 = 6 00 A
1-800 = 80 0 A
Large:
2-800 = 8 00 A
2-1600 = 1600 A
2-2000 = 200 0 A
2-2400 = 2400 A
(Output Type)
1V
= 0 to 1 Vac
Example:
H681
2-800 1V–