Current Monitoring | ECM-Optimized Current Switch
H6ECM
Split-core Current Switch, Proof of Rotation
(Flow) for ECM Systems
H6ECM05
TM
Maximize Reliability
The H6ECM is a current-sensitive switching device that monitors current
(amperage) in the conductor passing through it. A change in amperage
in the monitored conductor that crosses the switch (setpoint) causes the
resistance of the FET status output to change state, similar to the action
of a mechanical switch. The status output is suitable for connection to
building controllers or other appropriate data acquisition equipment
operating at up to 30 V. The product requires no external power supply
to generate its output.
Electrically Commutated Motors (ECMs) are increasingly common as
more energy conservation measures are implemented. The ECM is a
brushless DC motor that is supplied AC power, converts that power to
DC current and uses electronic switching to control the motor rotation.
The ECM motor shaft speed can be reduced to save energy, resulting
in lower cost and less component wear. The H6ECM is optimized to
provide meaningful proof of rotation which verifies that the ECM motor
is operating as expected.
High
performance
High performance device,
split-core housing
Precise
Precise current trip point setting
Small size
Fits easily inside small enclosures
Self-gripping iris
Self-gripping iris for easy
installation
Status LEDs
Status LEDs for easy setup and
local indication
Up to 1 Amp
status output
Increased application flexibility
APPLICATIONS
• Systems with Electrically Commutated Motors such as cooling fans or
compressor motors with off-state (keep alive) current less than 0.5 A
SPECIFICATIONS
Sensor Power Induced from the monitored conductor
Insulation Class 600 Vac RMS
Frequency Range 60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Hysteresis 10% typical
Accuracy ±10%
Amperage Range 0.5 to 175 A continuous
Status Output Ratings
Setpoint 0.5 A (keep alive current < 0.5 A)
O State Resistance Open switch represents > 1 MΩ
On State Resistance Closed switch represents < 200 mΩ
TM
N.O. 1.0A @ 30 Vac/dc, not polarity
sensitive
Terminal Block Max. Wire Size 24 to 14 AWG (0.2 to 2.1mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals UL508 open device listing
Installation Category CAT III, Pollution Degree 2
Notes: For applications requiring double or reinforced insulation, please contact the
fac tory.
The product design provides basic insulation only.
Do not use the LED indicators as evidence of applied voltage.
HQ0005778.D 0117
DIMENSIONAL DRAWING WIRING DIAGRAM
Current Monitoring | H6ECMCurrent Monitoring | ECM-Optimized Current Switch
Removable Mounting Bracket
0.6"
(16 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
0.7"
(18 mm)
3.5"
(89 mm)
1.2"
(31 mm)
Self-gripping Iris
2.5" *
(64 mm)
1.0"
(26 mm)
AC Power
Insulated Conductor (line or load) ONLY
ORDERING INFORMATION
MODEL AMPERAGE RANGE STATUS OUTPUT TRIP POINT STAT US L ED UL
H6ECM05 0.5 to 175 A N.O. 1.0 A @ 30 Vac/dc 0.5 A • •
Digital
Input
HQ0005778.D 0117
TM