Veris Industries H6ECM Data Sheet

Minimize Installed Cost
Current Monitoring | ECM-Optimized Current Switch
H6ECM
Split-core Current Switch, Proof of Rotation (Flow) for ECM Systems
H6ECM05
TM
Maximize Reliability
The H6ECM is a current-sensitive switching device that monitors current (amperage) in the conductor passing through it. A change in amperage in the monitored conductor that crosses the switch (setpoint) causes the resistance of the FET status output to change state, similar to the action of a mechanical switch. The status output is suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to 30 V. The product requires no external power supply to generate its output.
Electrically Commutated Motors (ECMs) are increasingly common as more energy conservation measures are implemented. The ECM is a brushless DC motor that is supplied AC power, converts that power to DC current and uses electronic switching to control the motor rotation. The ECM motor shaft speed can be reduced to save energy, resulting in lower cost and less component wear. The H6ECM is optimized to provide meaningful proof of rotation which verifies that the ECM motor is operating as expected.
High performance
High performance device, split-core housing
Precise
Precise current trip point setting
Small size
Fits easily inside small enclosures
Self-gripping iris
Self-gripping iris for easy installation
Status LEDs
Status LEDs for easy setup and local indication
Up to 1 Amp status output
Increased application flexibility
APPLICATIONS
• Systems with Electrically Commutated Motors such as cooling fans or compressor motors with off-state (keep alive) current less than 0.5 A
SPECIFICATIONS
Sensor Power Induced from the monitored conductor
Insulation Class 600 Vac RMS
Frequency Range 60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Hysteresis 10% typical
Accuracy ±10%
Amperage Range 0.5 to 175 A continuous
Setpoint 0.5 A (keep alive current < 0.5 A)
O State Resistance Open switch represents > 1 MΩ
On State Resistance Closed switch represents < 200 mΩ
TM
N.O. 1.0A @ 30 Vac/dc, not polarity sensitive
Terminal Block Max. Wire Size 24 to 14 AWG (0.2 to 2.1mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals UL508 open device listing
Installation Category CAT III, Pollution Degree 2
Notes: For applications requiring double or reinforced insulation, please contact the fac tory. The product design provides basic insulation only. Do not use the LED indicators as evidence of applied voltage.
HQ0005778.D 0117
DIMENSIONAL DRAWING WIRING DIAGRAM
Current Monitoring | H6ECMCurrent Monitoring | ECM-Optimized Current Switch
Removable Mounting Bracket
0.6"
(16 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
0.7"
(18 mm)
3.5"
(89 mm)
1.2"
(31 mm)
Self-gripping Iris
2.5" *
(64 mm)
1.0"
(26 mm)
AC Power Insulated Conductor (line or load) ONLY
ORDERING INFORMATION
MODEL AMPERAGE RANGE STATUS OUTPUT TRIP POINT STAT US L ED UL
H6ECM05 0.5 to 175 A N.O. 1.0 A @ 30 Vac/dc 0.5 A