Veris Industries H681x-5A Series Installation Guide

Installation Guide
Power Metering CTs
Product Overview
H681x-xxx 5 Amp split-core current transformers (CTs) provide secondary amperage proportional to the primary (sensed) current. For use with power meters, data loggers, chart recorders, and other instruments, the H681x Series 5 Amp CTs provide a cost-eective means to transform electrical service amperages to a 0 to 5 Amp level compatible with monitoring equipment.
E207042
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Product may use multiple voltage/power sources. Be sure all sources of power have been disconnected before servicing.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2011 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable re and electrical enclosure.
Product Identification
H6810-200A-5A Split-Core CT, Small, 200A:5A 2.5 H6810-300A-5A Split-Core CT, Small, 300A:5A 2.5 H6811-400A-5A Split-Core CT, Medium, 400A:5A 5.0 H6811-600A-5A Split-Core CT, Medium, 600A:5A 5.0 H6811-800A-5A Split-Core CT, Medium, 800A:5A 12.5 H6812-800A-5A Split-Core CT, Medium, 800A:5A 5.0 H6812-1000A-5A Split-Core CT, Large, 1000A:5A 22.5 H6812-1200A-5A Split-Core CT, Large, 1200A:5A 22.5 H6812-1600A-5A Split-Core CT, Large, 1600A:5A 22.5 H6812-2000A-5A Split-Core CT, Large, 2000A:5A 22.5 H6812-2400A-5A Split-Core CT, Large, 2400A:5A 22.5
TM
H681x-5A Series
Split-Core Current Transformers, 5A Output
5 A Models Description Burden Capacity
in VA
Specifications
Frequency Range
Accuracy
Output at Rated Current
Insulation
Operating Temp Range
Storage Temp Range
Humidity Range
Altitude of Operation
Agency Approvals
Installation Category
INP UTS
50 /60 Hz
Leads
6 ft (1.8 m)
ACCUR ACY
±1% of reading from 5% to 10 0% of rated current, specified with the primary conductor(s) centered in the CT window.
OUTPUTS
5A
MECHAN ICAL
60 0VAC
ENVIRONMENTAL
2400A models only: -15° to 50°C (5° to 122° F);
All other models: -15° to 60 °C (5° to 140°F)
-4 0° to 70°C (- 40° to 158°F)
0-95% noncondensing
3 km max.
COMPLIANCE INFORMATION
UL61010-1, E N61010 -1
Category III, Pollution Degree 2
Z201970-0H Page 1 of 2 ©2014 Veris Industries 05142
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
A
B
E
F
C
D
B
E
F
C
D
A
A
B
E
C
F
D
Wire t
i
Power Metering CTs Hx-5ASeries
Dimensions
TM
Installation
H6810/Small
200 Amp, 300 Amp
H6811/Medium
400 Amp, 600 Amp, 800 Amp
H6812/Large
800 Amp, 1000 Amp, 1200 Amp, 1600 Amp, 2000 Amp, 2400 Amp
A = 3.8” (96 mm) B = 1.2” (30 mm) C = 1.3” (32 mm) D = 1.2” (30 mm) E = 4.0" (100 mm) F = 4.8" (121 mm)
A = 4.9” (125 mm) B = 2.9” (73 mm) C = 2.5” (62 mm) D = 1.2" (30 mm) E = 5.2” (132 mm) F = 6.0" (151 mm)
A = 4.9” (125 mm) B = 5.5” (139 mm) C = 2.5” (62 mm) D = 1.2” (30 mm) E = 7.9" (201 mm) F = 6.0" (151 mm)
1. Disconnect and lock out power to the primary circuit before installing these CTs.
2. Connect the secondary leads to the burden or test switching/shorting bar. The white wire is the X1 lead.
3. Depress the tabs on one end of the CT to open it. Check the core ends on both sections of the CT to ensure there is no rust or debris in the closure areas.
4. Slip the CT over the primar y leads. Note labeling on the product indicating “source side.”
5. Close and latch the CT, and mount it securely.
6. In any application where fault currents can exceed 20 times rated current of CT, use wire ties or similar fasteners to secure the I-bar to the CT housing (see below). Secure both sides of the I-bar.
Secure the I-ba r with a wire tie in applicatio ns where a fault current could exceed 20x rated cu rrent.
7. Reconnect power to the panel.
An optional mo unting kit is available for th ese devices (Veris part number AH 06).
Ratings
These products provide basic insulation to 600 VAC between the sensed conductor and the output leads. For reinforced applications, the installer must provide appropriate insulation. Reinforced insulation is provided for applications to 300 VAC between the sensed conductor and the output leads.
Z201970-0H Page 2 of 2 ©2014 Veris Industries 05142
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.