Current Monitoring | Field Mount Status Relay
H12 0 S E RI E S
SPST Status Relay with Integral Current Switch
TM
The H120 and H120NC offer a fixed current switch and SPST relay in a
single externally mounted housing. Combining the current sensor and
relay in one easy-to-install package eliminates the need to fit multiple
devices into small electrical enclosures and simplifies the installation.
Remove the labor associated with installing a separate current sensor.
2-in-1
Current switch and relay are in
series…connect the contacts to
the load and your current switch is
automatically installed
Nipple mount
The nipple mount housing can
be connected to any 1/2” conduit
knockout for installation versatility
Relay coil LED
Relay coil LED streamlines job
commissioning and check out
APPLICATIONS
• Unit ventilators
• Fan coil units
• Exhaust fans
HP ratings
HP ratings make the H120 ideal
for control and status of
fractional HP motors
0.1A turn-on
Easily monitors the smallest loads
NEMA 1 rated
NEMA 1 rated housing may be
used in plenum spaces
• Fan terminal units
• Fractional HP motors
• Light resistive loads
SPECIFICATIONS
Sensor Power Induced from relay coil power
Operating Temperature
Operating Humidity 10 to 90% RH non-condensing
Expected Relay Life
(mechanical)
Relay Status LED ON=energized
LEAD WIRE SPECIFICATIONS
Lead Length 14” (356 mm) min.
Style and Gauge
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals
Note: Do not use the LED status indicators as evidence of applied voltage.
-15 to 60 °C (5 to 140 °F) (13.8 A max.),
-15 to 50 °C (5 to 12 °F) (2 A max.)
10 million cycles
UL1015; Coil: 18 AWG; Contacts: 12 AWG;
Status: 16 AWG
UL 508 closed type device listing, CAT III,
Pollution Degree 2, basic insulation
TM
HQ0001772.F 0117
Current Monitoring | H120 SeriesCurrent Monitoring | Field Mount Status Relay
NIPPLE MOUNT DIRECTLY TO A PANEL
Wiring Diagrams
NIPPLE MOUNT TO 4X ELEC TRICAL BOX
Wiring Diagrams
WIRE COLOR CODES
DIMENSIONAL DRAWING
RELAY CONTACT RATINGS
Resistive 20 A (r)• @ 277 Vac/28Vdc
(250,00 Cycles)
Motor 120 Vac, 1HP
208 Vac, 1HP
250 Vac, 2HP
277 Vac, 2HP
Ballast 277 Vac, 20 A
Tungsten 120 Vac, 10 A
TYPICAL COIL PERFORMANCE
Voltage Coil Current
AC DC
24V 75 mA 32 mA
*See operating temperature specifications
ORDERING INFORMATION
MODEL
H120
H120N C N.C. 100 mA @ 30 Vac/dc • •
HQ0001772.F 0117
AMPE RAG E
RANGE
0.1 to 20 A 24 Vac/d c SPST, N.O.
COIL RE LAY STATUS OUTPUT
TM
N.O. 100 mA @ 30 Vac/dc
TRIP
POINT
0.1 A or Less Nipple Mount
HOUSING
RELAY POWER
LED
• •
UL