Current Monitoring | Current Switches: Auto Calibration with LCD Display
H11D
LCD Display
Maximize Reliability
H11D
TM
The Hawkeye TruStat H11D is a microprocessor based, self-learning,
self-calibrating current switch. It is designed for user ease, providing
calibration-free status for both under and overcurrent, an LCD display,
and slide-switch selectable trip point limits. At initial power-up, the
H11D automatically learns the average current on the line with no action
required by the installer. Once a current is learned, the switch monitors
for changes in current greater than the selected range.
Backlit LCD
View the monitored current (up
to 200 A)…no need for expensive
handheld meters and offers easy
visibility in dark enclosures
Simplified
troubleshooting
Records and displays the
amperage level that trips the alarm
Microcontrollerbased learning
technology
Automatically learns load upon
initial power-up…minimizes
calibration labor
APPLICATIONS
Versatility
Slide-switch selectable trip point
limits
Automatic
calibration
Reduced errors and installation
costs
Reset function
Reset function can be used
when unpowered…reduces the
possibility of an arc flash incident
Sensor Power Induced from monitored conductor
Response Time 1 sec.
Accuracy ±2% of full scale
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Off at low currents; illuminates when
LCD Backlight
On-State Resistance ≤1.0 Ω
Off-State Resistance ≥1. 0 MΩ
Setpoint Target Range, Switch
Setting A
Setpoint Target Range, Switch
Setting B
Switch Setting C
Alarm Reset Range
Setpoint Calibration Learn Period 30 sec.; self-learning, pushbutton reset
Normal-to-Alarm Output Delay 1 sec. maximum
Alarm-to-Normal Output Delay 30 sec. nominal
1
1
1
2
monitored current exceeds 4.5 A;
flashes during an alarm state while
current remains above 4.5 A
±40% of learned nominal current; max.
learned current of 142 A to enable an
upper trip limit at or below 200 A
±60% of learned nominal current;max.
learned current of 125 A to enable an
upper trip limit at or below 200 A
On/Off Status; contacts are closed
while amperage is above 2.5 A
±5% of learned nominal current
• HVAC fans, pumps, and
blowers
Insulation Class 600 Vac RMS (UL); 300 Vac RMS (CE3)
Hysteresis 10% (typical)
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals
1. Trip point switch positions A and B are not for use in applications where the current
will fluctuate by more than 40% (A) or 60% (B) of the nominal current. If the current will
fluctuate by more than 60%, use the H11D for on/off status (position C) only.
2. The upper trip limit alarm resets when the current drops by 5% of the learned nominal
current limit. The lower trip limit alarm resets when the current rises by 5% of learned
nominal current limit.
3 . The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
Specification Note: For CE compliance, conductor shall be insulated according to
IEC 61010-1
Do not use the LCD as evidence of applied voltage.
• Monitoring status of industrial
process equipment
UL 508 open device listing; CE:
EN61010-1, CAT III, Pollution Degree 2,
basic insulation
TM
HQ0003679.G 0117
Current Monitoring | H11D
DIMENSIONAL DRAWING
Removable Mounting Bracket
Bracket can
be mounted
on three sides
for added
installation
flexibility.
3.1”**
(79 mm)
1.1”
(26 mm)
0.8”
(21 mm)
1.0”
(25 mm)
Self-gripping Iris
2.8”
(70 mm)
Ø 0.3”
(8 mm)
3.0”
2.5”
(64 mm)
1.4”*
(36 mm)
(76 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown.
FUNCTIONAL DRAWING
WIRING DIAGRAM
Insulated Conductor
CONTROLLER
Digital
Input
CONTACTOR
MOTOR
Fan or Pump
ALARM RESET
5% Typical
Upper Alarm
Trip Limit
NOMINAL
LEARNED
CURRENT
ØAAC
POWER
ON
LEARN
(MODE)
30 SEC
NORMAL
(CURRENT
MONITOR
MODE)
ALARM
(MODE)
1 SEC. DELAY 30 SEC. DELAY
NORMAL
(CURRENT
MONITOR MODE)
POWER LOSS
ALARM (MODE)
ØAAC
Normal
Current
Lower Alarm
Trip Limit
ORDERING INFORMATION
MODEL AMPERAGE RANGE1STATUS OUTPUT
H11D
1. To enable the upper trip limit alarm, the max. learned current for switch setting “A” is 142 A, and the max. learned
current for switch setting “B” is 125 A. Switch setting “C” is for on/off status only, so the upper trip limit alarm does not apply.
2. Listed for use on 75 °C insulated conductors.
2.5 to 200 A @ 60 Hz
3.0 to 200 A @ 50 Hz
N.O. 1.0 A @ 30 Vac/dc
NOMINAL TRIP POINT
TARGET RANGE
±40%, ±60%, or on/off
(user selectable)
HOUSING
Split-core •
STAT U S
LED
UL CE