Veris Industries H11D Data Sheet

Minimize Installed Cost
Current Monitoring | Current Switches: Auto Calibration with LCD Display
H11D
LCD Display
Maximize Reliability
H11D
TM
The Hawkeye TruStat H11D is a microprocessor based, self-learning, self-calibrating current switch. It is designed for user ease, providing calibration-free status for both under and overcurrent, an LCD display, and slide-switch selectable trip point limits. At initial power-up, the H11D automatically learns the average current on the line with no action required by the installer. Once a current is learned, the switch monitors for changes in current greater than the selected range.
Backlit LCD
View the monitored current (up to 200 A)…no need for expensive handheld meters and offers easy visibility in dark enclosures
Simplified troubleshooting
Records and displays the amperage level that trips the alarm
Microcontroller­based learning technology
Automatically learns load upon initial power-up…minimizes calibration labor
APPLICATIONS
Versatility
Slide-switch selectable trip point limits
Automatic calibration
Reduced errors and installation costs
Reset function
Reset function can be used when unpowered…reduces the possibility of an arc flash incident
Sensor Power Induced from monitored conductor
Response Time 1 sec.
Accuracy ±2% of full scale
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Off at low currents; illuminates when
LCD Backlight
On-State Resistance ≤1.0 Ω
Off-State Resistance ≥1. 0 MΩ
Setpoint Target Range, Switch Setting A
Setpoint Target Range, Switch Setting B
Switch Setting C
Alarm Reset Range
Setpoint Calibration Learn Period 30 sec.; self-learning, pushbutton reset
Normal-to-Alarm Output Delay 1 sec. maximum
Alarm-to-Normal Output Delay 30 sec. nominal
1
1
1
2
monitored current exceeds 4.5 A; flashes during an alarm state while current remains above 4.5 A
±40% of learned nominal current; max. learned current of 142 A to enable an upper trip limit at or below 200 A
±60% of learned nominal current;max. learned current of 125 A to enable an upper trip limit at or below 200 A
On/Off Status; contacts are closed while amperage is above 2.5 A
±5% of learned nominal current
• HVAC fans, pumps, and blowers
Insulation Class 600 Vac RMS (UL); 300 Vac RMS (CE3)
Hysteresis 10% (typical)
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals
1. Trip point switch positions A and B are not for use in applications where the current
will fluctuate by more than 40% (A) or 60% (B) of the nominal current. If the current will fluctuate by more than 60%, use the H11D for on/off status (position C) only.
2. The upper trip limit alarm resets when the current drops by 5% of the learned nominal
current limit. The lower trip limit alarm resets when the current rises by 5% of learned nominal current limit. 3 . The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details.
Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010-1
Do not use the LCD as evidence of applied voltage.
• Monitoring status of industrial process equipment
UL 508 open device listing; CE: EN61010-1, CAT III, Pollution Degree 2, basic insulation
TM
HQ0003679.G 0117
Current Monitoring | H11D
DIMENSIONAL DRAWING
Removable Mounting Bracket
Bracket can be mounted on three sides for added installation flexibility.
3.1”**
(79 mm)
1.1”
(26 mm)
0.8”
(21 mm)
1.0”
(25 mm)
Self-gripping Iris
2.8”
(70 mm)
Ø 0.3”
(8 mm)
3.0”
2.5”
(64 mm)
1.4”*
(36 mm)
(76 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown.
FUNCTIONAL DRAWING
WIRING DIAGRAM
Insulated Conductor
CONTROLLER
Digital Input
CONTACTOR
MOTOR
Fan or Pump
ALARM RESET 5% Typical
Upper Alarm Trip Limit
NOMINAL LEARNED CURRENT
ØAAC
POWER ON
LEARN (MODE) 30 SEC
NORMAL (CURRENT MONITOR MODE)
ALARM (MODE)
1 SEC. DELAY 30 SEC. DELAY
NORMAL (CURRENT MONITOR MODE)
POWER LOSS
ALARM (MODE)
ØAAC
Normal Current
Lower Alarm Trip Limit
ORDERING INFORMATION
MODEL AMPERAGE RANGE1STATUS OUTPUT
H11D
1. To enable the upper trip limit alarm, the max. learned current for switch setting “A” is 142 A, and the max. learned current for switch setting “B” is 125 A. Switch setting “C” is for on/off status only, so the upper trip limit alarm does not apply.
2. Listed for use on 75 °C insulated conductors.
2.5 to 200 A @ 60 Hz
3.0 to 200 A @ 50 Hz
N.O. 1.0 A @ 30 Vac/dc
NOMINAL TRIP POINT
TARGET RANGE
±40%, ±60%, or on/off (user selectable)
HOUSING
Split-core
STAT U S
LED
UL CE
2
HQ0003679.G 0117