Veris Industries FSRxxxx SERIES Installation Guide

TM
FLOW SENSORS
INSTALLATION GUIDE
FSRxxxx SERIES
Ultrasonic Flow Meter
PRODUCT IDENTIFICATION
Monitor: FSR Series
Transducers: FST1, FST2, FST3, FST4, FST5
FSR
Note: Do not cut transducer cables to alter length. This will void the factory warranty. Cables are available in several lengths. Assess the installation location prior to ordering to determine the optimum length. If the wrong length is ordered, contact the factory.
FST1, 2, 3
Temp Sensors
FST4, 5
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DIMENSIONS
(163 mm)
(153 mm)
FSR Monitor
(105 mm)
(110 mm)
 0.75”
(19 mm)
(53 mm)
2x  0.5”
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations other than those listed in Specications.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
(35 mm)
(13 mm)
Z205739-0D PAGE 1 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
INSTALLATION GUIDE
FST(1, 2, 3) Insert Temperature SensorFST(1, 2, 3) Transducer
A
C
A
C
D
B
B
D
U-Bolt Connection
(2” Pipe Only)
Cable Diameter
0.3 “ (7 mm)
0.5 “
(13 mm)
0.2 “
(5 mm)
Pipe
Size
½”
¾”
1”
1¼”
1½”
2” (U-bolt
only)
Pipe
A B C D
Material
ANSI 2.46” (63 mm) 2.36” (60 mm) 2.66” (68 mm) 0.840 (22 mm)
Copper 2.46” (63 mm) 2.36” (60 mm) 3.33” (85 mm) 0.625” (16 mm)
Tubing 2.46” (63 mm) 2.28” (58 mm) 3.33” (85 mm) 0.500” (13 mm)
ANSI 2.46” (63 mm) 2.57” (66 mm) 2.66” (68 mm) 1.050” (27 mm)
Copper 2.46” (63 mm) 2.50” (64 mm) 3.56” (91 mm) 0.875” (23 mm)
Tubing 2.46” (63 mm) 2.50” (64 mm) 3.56” (91 mm) 0.750” (19 mm)
ANSI 2.46” (63 mm) 2.92” (75 mm) 2.86” (73 mm) 1.315” (34 mm)
Copper 2.46” (63 mm) 2.87” (73 mm) 3.80” (97 mm) 1.125” (29 mm)
Tubing 2.46” (63 mm) 2.75” (70 mm) 3.80” (97 mm) 1.000” (26 mm)
ANSI 2.79” (71 mm) 3.18” (81 mm) 3.14” (80 mm) 1.660” (43 mm)
Copper 2.46” (63 mm) 3.00” (77 mm) 4.04” (103 mm) 1.375” (35 mm)
Tubing 2.46” (63 mm) 3.00” (77 mm) 4.04” (103 mm) 1.250” (32 mm)
ANSI 3.02” (77 mm) 3.42” (87 mm) 3.33” (85 mm) 1.900” (49 mm)
Copper 2.71” (69 mm) 2.86” (73 mm) 4.28” (109 mm) 1.625” (42 mm)
Tubing 2.71” (69 mm) 3.31” (85 mm) 4.28” (109 mm) 1.500” (39 mm)
ANSI 3.71” (95 mm) 3.42” (87 mm) 5.50” (140 mm) 2.375” (61 mm) *
Copper 3.71” (95 mm) 3.38” (86 mm) 5.50” (140 mm) 2.125” (54 mm) *
Tubing 3.21” (82 mm) 3.85” (98 mm) 4.75” (121 mm) 2.000” (51 mm) *
2.7”
(67 mm)
FST(4, 5) Transducer
2.9”
(74 mm)
0.75”
(19 mm)
1.6”
(40 mm)
2.2”
(56 mm)
* Varies due to U-bolt feature
Z205739-0D PAGE 2 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
TABLE OF CONTENTS
Quick Install ................................................................................................................4
1 - Transducer Location .................................................................................................4
2 - Electrical Connections..............................................................................................4
3 - Pipe Preparation and Transducer Mounting ............................................................4
4 - Startup.....................................................................................................................5
Introduction ................................................................................................................6
General .........................................................................................................................6
Application Versatility ..................................................................................................6
User Safety....................................................................................................................6
Data Integrity ...............................................................................................................6
Product Identification ...................................................................................................6
Part 1 - Transmitter Installation ...............................................................................7
Transducer Connections ................................................................................................7
AC Power Connections ..................................................................................................8
DC Power Connections ..................................................................................................8
Part 2 – Transducer Installation ................................................................................9
General .........................................................................................................................9
Step 1 - Mounting Location ..........................................................................................9
Step 2 - Transducer Spacing ..........................................................................................9
Step 3 - Entering Pipe and Liquid Data .......................................................................10
Step 4 - Transducer Mounting ..................................................................................... 11
V-Mount and W-Mount Installation ........................................................................... 11
FSTxxxx Small Pipe Transducer Installation ................................................................12
Mounting Transducers in Z-Mount Configuration ....................................................... 12
Part 3 - Inputs/Outputs ............................................................................................ 14
General ....................................................................................................................... 14
4-20 mA Output ..........................................................................................................14
Control Outputs (non BTU only) ..................................................................................14
Frequency Output (non BTU only) ...............................................................................15
RS-485 ........................................................................................................................16
Heat Flow (BTU only) ..................................................................................................16
INSTALLATION GUIDE
Part 5 - Software Utility ...........................................................................................28
Introduction................................................................................................................28
System Requirements .................................................................................................28
Installation .................................................................................................................28
Initialization ...............................................................................................................28
Basic Tab .....................................................................................................................28
Flow Tab......................................................................................................................30
Filtering Tab ................................................................................................................30
Output Tab ..................................................................................................................31
Channel 1 - 4-20 mA Configuration ............................................................................ 31
Channel 2 - RTD Configuration (BTU only) ..................................................................32
Channel 2 - Control Output Configuration (non BTU only) ..........................................33
Setting Zero and Calibration .......................................................................................33
Target Dbg Data Screen - Definitions ..........................................................................34
Saving Meter Configuration on a PC ...........................................................................35
Printing a Flow Meter Configuration Report ............................................................... 35
Appendix ...................................................................................................................35
Specifications .............................................................................................................35
Menu Maps .................................................................................................................37
Communications Protocols .........................................................................................40
Heating and Cooling Measurement ............................................................................44
Meter Error Codes .......................................................................................................46
Control Drawings ........................................................................................................47
K-Factors Explained .................................................................................................... 51
Fluid Properties ..........................................................................................................52
Pipe Charts..................................................................................................................53
CE Compliance Drawings .............................................................................................58
PART 4 - Startup and Configuration ........................................................................ 18
Before Starting the Instrument .................................................................................. 18
Instrument Startup ..................................................................................................... 18
Keypad Programming .................................................................................................18
Menu Structure ........................................................................................................... 18
BSC Menu -- Basic Menu ............................................................................................. 19
CH1 Menu -- Channel 1 Menu .....................................................................................20
CH2 Menu -- Channel 2 Menu .....................................................................................23
SEN Menu -- Sensor Menu .......................................................................................... 24
SEC Menu -- Security Menu ........................................................................................24
SER Menu -- Service Menu ..........................................................................................25
DSP Menu -- Display Menu .........................................................................................27
Z205739-0D PAGE 3 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
QUICK INSTALL
This manual contains detailed operating instructions for all aspects of the FSR Series. The following condensed instructions are provided to assist the operator in getting the instrument started up and running as quickly as possible. This pertains to basic operation only. If specic instrument features are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate sec tion in the manual for complete details.
Note: The following steps require informati on supplied by the meter itself, so it is necessary to supply power to the unit, at least temp orarily, to obtain setup informatio n.
1 - Transducer Location
1. In general, selec t a mounting location on the piping system with a minimum of 10 pipe diameters (10x the pipe inside diameter) of straight pipe upstream and 5 straight diameters downstream. See Table 2.1 for additional congurations.
2. Select a mounting method for the transducers based on pipe size and liquid characteristics. See Table 2.2. Transducer congurations are illustrated in Figure Q.1 below. The V-mount conguration is usually the rst choice, with W-mount and Z-mount used if needed to boost signal strength.
Note: All FST1xxxx, FST2xxx x, and FST3xxxx transducers use V-Mount congu ration.
3. Enter the following data into the meter via the integral keypad or the software utility (if not entered by the factory)
INSTALLATION GUIDE
2 - Electrical Connections
Transducer/Power Connections
1. Route the transducer cables from the transducer mounting location back to the enclosure. Connect the transducer wires to the terminal block in the enclosure.
Note: Do not cut transducer cables to alter length. This will void the factory warranty. Cables are available in several lengths. Assess the installation location prior to ordering to determine the optimum length. If the wrong length is ordered, contact the factory.
2. Verify that power supply is correct for the meters power option.
AC units require 95 to 265 VAC, 47 to 63 Hz @ 17 VA maximum. DC units require 10 to 28 VDC @ 5 Watts maximum.
3. Connect power to the ow meter.
Downstream+ Downstream­Upstream­Upstream+
1. Transducer mounting method
2. Pipe O.D. (Outside Diameter)
3. Pipe wall thickness
4. Pipe material
5. Pipe sound speed*
6. Pipe relative roughness*
7. Pipe liner thickness
8. Pipe liner material
9. Fluid type
10. Fluid sound speed*
11. Fluid viscosity*
12. Fluid specic gravity*
* Nominal values for these parameters are included within the operating system. Modify if the exact system values a re known.
TOP VIEW
OF PIPE
TOP VIEW
OF PIPE
TOP VIEW
OF PIPE
Figure Q.2 - Transducer Connections
3 - Pipe Preparation and Transducer Mounting
FST4xxxx, FST5xxxx Transducers
1. Place the ow meter in signal strength measuring mode. This value is available on the display (Service Menu) or in the data display of the software utility.
2. The pipe surface, where the transducers are to be mounted, must be clean and dry. Remove scale, rust or loose paint to ensure satisfactory acoustic conduction. Wire brushing the rough surfaces of pipes to smooth bare metal may also be useful. Plastic pipes do not require preparation other than cleaning.
3. Apply a single ½” (12 mm) bead of acoustic couplant grease to the upstream transducer and secure it to the pipe with a mounting strap.
4. Apply acoustic couplant grease to the downstream transducer and press it onto the pipe using hand pressure at the lineal distance calculated in Step 1.
5. Space the transducers according to the recommended values found on the product conguration sheet or from the software utility. Secure the transducers with the mounting straps at these locations.
W-Mount V-Mount Z-Mount
Figure Q.1 - Transducer Mounting Congurations
4. Record the value calculated and displayed as Transducer Spacing (FST4, FST5 only).
Z205739-0D PAGE 4 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
FST1xxxx, FST2xxxx, and FST3xxxx Transducers
1. Place the ow meter in signal strength measuring mode. This value is available on the display (Service Menu) or in the data display of the software utility.
2. The pipe surface, where the transducers are to be mounted, must be clean and dry. Remove scale, rust or loose paint to ensure satisfactory acoustic conduction. Wire brushing the rough surfaces of pipes to smooth bare metal may also be useful. Plastic pipes do not require preparation other than cleaning.
3. Apply a single ½” (12 mm) bead of acoustic couplant grease to the top half of the transducer and secure it to the pipe with bottom half or U-bolts.
4. Tighten the nuts so that the acoustic coupling grease begins to ow out from the edges of the transducer and from the gap between the transducer and the pipe. Do not over tighten.
4 - Startup
Initial Settings and Power Up
1. Apply power to the monitor.
2. Verify that SIG STR is greater than 5.0.
INSTALLATION GUIDE
3. Input proper units of measure and I/O data.
Z205739-0D PAGE 5 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
INTRODUCTION
General
The Veris ultrasonic ow meter is designed to measure the uid velocity of liquid within a closed conduit. The transducers are a non-contacting clamp-on or clamp­around type that does not foul and is easy to install.
The Veris family of transit time ow meters utilize two transducers that function as both ultrasonic transmitters and receivers. The transducers are clamped on the outside of a closed pipe at a specic distance from each other. The transducers can be mounted in V-Mount where the sound transverses the pipe two times, W-Mount where the sound transverses the pipe four times, or in Z-Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. The selection of mounting method is based on pipe and liquid characteristics that both have an eect on how much signal is generated. The ow meter operates by alternately transmitting and receiving a frequency modulated burst of sound energy between the two transducers and measuring the time interval that it takes for sound to travel between the two transducers. The dierence in the time interval measured is directly related to the velocity of the liquid in the pipe.
INSTALLATION GUIDE
Because the transducers are non-contacting and have no moving parts, the ow meter is not aected by system pressure, fouling, or wear. FST4 and FST5 transducers are rated to a pipe surface temperature of -40 to +250 °F (-40 to +121 °C). FST1, FST2, and FST3 small pipe transducers are rated from -40 to +185 °F (-40 to +85 °C).
Frequency Transducers Transmission
Modes
2 MHz All ½” thru 1½”
2” Tubing
1 MHz
500 kHz larger than 24” W, V, and Z 24” and Greater
2” ANSI and Copper
all 2” to 24” W, V, and Z 2” to 24”
Selected by
Firmware
Selected by
Firmware
User Safety
The FSR Series employs modular construction and provides electrical safety for the operator. The display face contains voltages no greater than 28 VDC. The display face swings open to allow access to user connections.
Pipe Size and
Type
Specic to
Transducer
Specic to
Transducer
TOP VIEW
OF PIPE
W-Mount V-Mount Z-Mount
Figure 1.1 - Ultrasound Transmission
TOP VIEW
OF PIPE
TOP VIEW
OF PIPE
Application Versatility
The FSRxxxx ow meter can be successfully applied on a wide range of metering applications. The simple-to-program monitor allows the standard product to be used on pipe sizes ranging from ½ inch to 100 inches (12 mm to 2540 mm) pipe*. A variety of liquid applications can be accommodated:
ultrapure liquids
potable water
chemicals
sewage
reclaimed water
cooling water
river water
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Disconnect electrical power before opening the instrument enclosure.
• Wiring mus t conform to applicable codes.
Failure to follow these instructions will result in death or serious injury.
Data Integrity
Non-volatile ash memory retains all user-entered conguration values in memory for several years at 77°F (25°C), even if power is lost or turned o. Password protection is provided as part of the Security menu (SEC MENU) and prevents inadvertent conguration changes or totalizer resets.
Product Identification
The serial number and complete model number of the monitor are located on the top outside surface of the housing. If technical assistance is required, please provide the Customer Service Department with this information.
plant euent
others
Z205739-0D PAGE 6 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
PART 1 - MONITOR INSTALLATION
After unpacking, save the shipping carton and packing materials in case the instrument is stored or re-shipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
Mount the enclosure in an area that is convenient for servicing, calibration, and observation of the LCD readout.
1. Locate the monitor within the length of transducer cables supplied. If this is not possible, it is recommended that the cable be exchanged for one that is of proper length. If additional cable is added, utilize RG59 75 Ω coaxial cable and BNC connections. Transducer cables that are up to 990 feet (300 meters) can be accommodated.
2. Mount the monitor in a location:
• Where little vibration exists.
• That is protected from corrosive uids.
• That is within the monitor’s ambient temperature limits -40 to +185°F
(-40 to +85°C).
• That is out of direct sunlight. Direct sunlight may increase monitor temperature to above the maximum limit.
3. Mounting - Refer to Figure 1.2 for enclosure and mounting dimension details. Ensure that enough room is available to allow for door swing, maintenance and conduit entrances. Secure the enclosure to a at surface with two appropriate fasteners.
INSTALLATION GUIDE
Transducer Connections
To access terminal strips for wiring, loosen the two screws in the enclosure door and open.
Guide the transducer terminations through the monitor conduit hole located in the bottom-left of the enclosure. Secure the transducer cable with the supplied conduit nut (if exible conduit was ordered with the transducer).
The terminals within the unit are of a screw-down barrier terminal type. Connec t the appropriate wires at the corresponding screw terminals in the monitor. Observe upstream and downstream (+/–) orientation. See Figure 1.3.
372
VE D
ACL
C US
E167432
PRODUCT SERVICE
TUV
RoHS
R
AC IN : 100-240VAC,50/60Hz
DC OUT :
PWC-15E
R
+15V / 0.3A
$
0.15A
R2807
-Vo
1500mA250V
C US
W
www.astrodyne.com
strodyne
ACN
+Vo
O
N
1 2 3 4
+
+
-
-
-
-
+
+
Downstream
Downstream
Upstream
Upstream
Modbus B
Modbus A
TFX Rx
TFX Tx
Reset Total
Modbus Gnd
Modbus
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
95 - 264 VAC
AC Neutral
Figure 1.2 - FSR Dimensions
(163 mm)
(153 mm)
(105 mm)
(110 mm)
 0.75”
(19 mm)
2x  0.5” (13 mm)
(53 mm)
To Transducers
Note: Wire colors may va ry! (+) connectio n with be either red or blue; (–) connection will be e ither black or clear.
Figure 1.3 - Transducer Connections.
Note: The transducer cable carries low level, high freque ncy signals. Do not add length to the cable supplied with the transducers. If additional cable is required, contact the manufacturer to arrange an exchange for a transducer with the a ppropriate length of cable. Cables to 990 feet (300 meters) are available. If adding cabl e, ensure that it is RG59 75 Ω compatible and uses BNC terminations.
Connect power to the screw terminal block in the monitor. See Figure 1.4 and Figure
1.5. Utilize the conduit hole on the right side of the enclosure for this purpose. Use wiring practices that conform to local and national codes (e.g., The National Electrical Code® Handbook in the U.S.).
CAUTION
• HAZARD OF IMPROPER OR UNSAFE OPERATION
• This instrument requires clean electric al line power. Do not operate this unit on circuit s with noisy compone nts (e.g., fluores cent lights, relays, compressors, or variable frequency drives).
• Do not use with high current step-down transformers from high voltage sources.
• Do not run signal wires with line power in the s ame wiring tray or conduit.
Any other wiring method may be unsafe or cause improper operation of the instrument.
4. Conduit Holes - Conduit holes should be used where cables enter the enclosure. Holes not used for cable entry should be sealed with plugs.
Note: Use NEMA 4 [IP-65] rated ttings/plugs to maintain the watertight integrity o f the enclosure. Generally, the right conduit hole (viewed from fro nt) is used for power, the left conduit hole for transducer connectio ns, and the center hole is utilized fo r I/O wiring.
Z205739-0D PAGE 7 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
INSTALLATION GUIDE
AC Power Connections
Connect 90 to 265 VAC, AC Neutral and Chassis Ground to the terminals referenced in Figure 1.4. Do not operate without an earth (chassis) ground connection.
ACN
1500mA250V
372
W
C US
VE
D
R
AC IN : 100-240VAC,50/60Hz DC OUT :
C US
ACL
95 - 264 VAC
95 - 264 VAC
AC Neutral
AC Neutral
www.astrodyne.com
PWC-15E
E167432
Signal Gnd. Control 1 Control 2 Frequency Out 4-20 mA Out Reset Total Modbus Gnd Modbus B Modbus A
O
1 2 3 4
N
Figure 1.4 - AC Power Connections
strodyne
+15V / 0.3A
$
R
TUV
PRODUCT SERVICE
+Vo
-Vo
0.15A
R2807
RoHS
Modbus
TFX Rx TFX Tx
Downstream
Upstream
-
-
+
+
DC Power Connections
The device can be operated from a 10 to 28 VDC source, as long as the source is capable of supplying a minimum of 5 Watts of power.
Connect the DC power to 10 to 28 VDC In, Power Gnd., and Chassis Gnd., as in Figure
1.5.
10 - 28 VDC
10 - 28 VDC
Power Gnd.
Power Gnd. Signal Gnd. Control 1 Control 2 Frequency Out 4-20 mA Out Reset Total
O
1 2 3 4
N
Modbus Gnd Modbus B Modbus A
Modbus
TFX Rx
TFX Tx
Downstream
Upstream
-
-
+
+
Power
Ground
10 -28 VDC
Note: In electrically noisy ap plications, ground the meter to the pipe where the transducers are mounted to provide additio nal noise suppression. This approach is only eective with conduc tive metal pipes. Remove the ear th (chassis) ground derived from the line voltage p ower supply at the meter and connect a new ea rth ground between the meter and the pipe b eing measured.
Note: The terminal blocks accomodate wire ga uges up to 14 AWG.
Note: AC powered versions are protected by a eld replaceabl e fuse. This fuse is equivalent to Littelfuse/Wick mann P.N. 3720500041 or 37405000410.
Figure 1.5 - DC Power Connections
Note: DC powered versions are protected by an au tomatically reset ting fuse. This fuse does not require replacement.
Z205739-0D PAGE 8 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
PART 2 - TRANSDUCER INSTALLATION
INSTALLATION GUIDE
General
The FST transducers contain piezoelectric crystals for transmitting and receiving ultrasonic signals through walls of liquid piping systems. FST transducers are relatively simple and straightforward to install, but spacing and alignment of the transducers is critical to the system’s accuracy and performance. Take care to ensure that these instructions are carefully executed. FST1, FST2, and FST3 small pipe transducers have integrated transmitter and receiver elements that eliminate the requirement for spacing measurement and alignment.
Mounting of the FST4 and FST5 clamp-on ultrasonic transit time transducers is a three-step process:
1. Select the optimum location on a piping system.
2. Enter the pipe and liquid parameters into either the sof tware utility or key the parameters into the transmitter using the keypad. The software utility or the monitor’s rmware calculates proper transducer spacing based on these entries.
3. Pipe preparation and transducer mounting.
BTU meters require two RTDs to measure heat usage. The ow meter utilizes 1,000 Ω, three-wire, platinum RTDs in two mounting styles. Surface mount RTDs are available for use on well insulated pipes. Mounting the RTD in an uninsulated area causes inconsistent temperature readings. Insertion (wetted) RTDs should be sued in these areas instead.
Step 1 - Mounting Location
The rst step in the installation process is the selection of an optimum location for the ow measurement to be made. This requires a basic knowledge of the piping system and its plumbing.
Piping Configuration and Transducer Positioning Upstream
Pipe
Diameters
* **
25 5
Flow
*
Flow
*
**
14 5
**
10 5
Flow
*
**
10 5
Flow
*
Flow
*
Flow
*
**
10 5
**
24 5
**
Downstream
Pipe
Diameters
An optimum location is dened as:
• A piping system that is completely full of liquid when measurements are being taken. The pipe may become completely empty during a process cycle, which results in the error code 0010 (Low Signal Strength) being displayed on the ow meter while the pipe is empty. This error code clears automatically once the pipe rells with liquid. It is not recommended to mount the transducers in an area where the pipe may become par tially lled. Partially lled pipes cause erroneous and unpredictable operation of the meter.
• A piping system that contains lengths of straight pipe such as those described in Table 2.1. The optimum straight pipe diameter recommendations apply to pipes in both horizontal and vertical orientation. The straight runs in Table 2.1 apply to liquid velocities that are nominally 7 FPS (2.2 MPS). As liquid velocity increases above this nominal rate, the requirement for straight pipe increases proportionally.
• Mount the transducers in an area where they will not be inadvertently bumped or disturbed during normal operation.
• Avoid installations on downward owing pipes unless adequate downstream head pressure is present to overcome partial lling of or cavitation in the pipe.
• Note: Do not cut transducer cables to alter length. This will void the factory warranty. Cables are available in several lengths. Assess the installation location prior to ordering to determine the optimum length. If the wrong length is ordered, contact the factory.
Table 2.1 - Piping Conguration and Transducer Positioning
The ow meter system provides repeatable measurements on piping systems that do not meet these requirements, but accuracy of these readings may be inuenced to various degrees.
Step 2 - Transducer Spacing
Transit time ow meters can be used with two dierent transducer types. Meters that utilize the FST4 and FST5 transducer sets consist of two separate sensors that function as both ultrasonic transmitters and receivers. FST1, FST2, and FST3 transducers integrate both the transmitter and receiver into one assembly that xes the separation of the piezoelectric crystals. These transducers are clamped on the outside of a closed pipe at a specic distance from each other.
The FST4 and FST5 transducers can be mounted in:
W-Mount where the sound traverses the pipe four times. This mounting method produces the best relative travel time values but the weakest signal strength.
V-Mount where the sound traverses the pipe twice. V-Mount is a compromise between travel time and signal strength.
Z-Mount where the transducers are mounted on opposite sides of the pipe and the sound crosses the pipe once. Z-Mount will yield the best signal strength but the smallest relative travel time.
Z205739-0D PAGE 9 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
INSTALLATION GUIDE
Mounting
Mode
W-Mount
V-Mount
Z-Mount
Pipe Material Pipe Size Liquid
Composition
Plastic (all types)
Carbon Steel
Stainless Steel
Copper
Ductile Iron
Cast Iron
Plastic (all types)
Stainless Steel
Copper 4-30 in. (100-750 mm)
Ductile Iron
Cast Iron
Plastic (all types) > 30 in. (>750 mm)
Carbon Steel
Stainless Steel
Copper > 30 in. (>750 mm)
Ductile Iron
Cast Iron
2-4 in. (50-100 mm)
Not Recommended
4-12 in. (100-300 mm)Carbon Steel
Low TSS; non-aerated
2-12 in. (50-300 mm)
>12 in. (>300 mm)
>12 in. (>300 mm)
Size Frequency
1/2 2 MHz
3/4 2 MHz
1 2 MHz
1 1/4 2 MHz
1 1/2 2 MHz
2
1 MHz
2 MHz FST3
Setting
Transducer Mounting Mode
FST1
FST2
FST3
FST1
FST2
FST3
FST1
FST2
FST3
FST1
FST2
FST3
FST1
FST2
FST3
FST1
FST2
V
Table 2.2 - Transducer Mounting Modes — FST4, FST5
For further details, reference Figure 2.1. The appropriate mounting conguration is based on pipe and liquid characteristics. Selection of the proper transducer mounting method is not entirely predictable and many times is an iterative process. Table 2.2 contains recommended mounting congurations for common applications. These recommended congurations may need to be modied for specic applications if such things as aeration, suspended solids, out of round piping or poor piping conditions are present. Use of meter diagnostics in determining the optimum transducer mounting is covered later in this section.
TOP VIEW
OF PIPE
W-Mount V-Mount Z-Mount
Figure 2.1- Transducer Mounting Modes — FST4, FST5
TOP VIEW
OF PIPE
TOP VIEW
OF PIPE
Table 2.3 - Transducer Mounting Mod es — FST1, FST2, FST3
Step 3 - Entering Pipe and Liquid Data
The system calculates proper transducer spacing by utilizing piping and liquid information entered by the user. Enter this information via the keypad or via the optional software utility.
The best accuracy is achieved when transducer spacing is exactly what the meter calculates, so use the calculated spacing if signal strength is satisfactory. If the pipe is not round, the wall thickness is not correct, or the actual liquid being measured has a dierent sound speed than the liquid programmed into the transmitter, the spacing can vary from the calculated value. If that is the case, place the transducers sat the highest signal level obser ved by moving the transducers slowly around the mount area.
Note: Transducer spacing is calculated on “ideal” pipe. Ideal p ipe is almost never found so the transducer spacing distances may need to be altered. An eec tive way to maximize signal strength is to congure the display to show signal strength, x o ne transducer on the pipe and then starting at the calculated spacing, move the rema ining transducer small distances forward and back to
nd the maximum signal s trength point.
Important! Enter all of the data on this list, save the data, and reset the meter before mounting transducers.
Z205739-0D PAGE 10 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
INSTALLATION GUIDE
The following information is required before programming the instrument:
Transducer mounting conguration Pipe O.D. (Outer Diameter)
Pipe wall thickness Pipe material
Pipe sound speed
1
Pipe relative roughness
1
Pipe liner thickness (if present) Pipe liner material (if present)
Fluid type Fluid sound speed
Fluid viscosity
1
Fluid specic gravity
1
1
Note: Much of the data relating to material sound spee d, viscosity, and specic gravity is pre-programmed into the o w meter. This data only needs to be modied if it is kn own that a particular ap plications data varies from the reference values. Refer to Part 4 of this man ual for instructions on entering conguration data into the ow meter via the monitor’s keypad. Refer to
Part 5 for data entry via the sof tware.
1
Nominal values for these parameters are included within the operating system. The nominal
values may be used as they appear o r may be modied if exact system values are kno wn.
After entering the data listed above, the meter calculates proper transducer spacing for the particular data set. This distance is in inches if it is congured in English units, or millimeters if congured in metric units.
Step 4 - Transducer Mounting
Pipe Preparation
TOP OF PIPE
45°
YES
45°
45°
YES
45°
FLOW METER MOUNTING
ORIENTATION
FST4, FST5 TRANSDUCERS
TOP OF PIPE TOP OF PIPE
45°
YES
45°
FLOW METER
MOUNTING ORIENTATION
2” FST1, FST2, FST3 TRANSDUCERS
Figure 2.2 - Transducer Orientation — Horizontal Pipes
Alignment
Marks
45°
YES
45°
45°
YES
45°
FLOW METER
MOUNTING ORIENTATION
<2” FST1, FST2, FST3 TRANSDUCERS
45°
YES
45°
Before mounting the transducers onto the pipe surface, clean an area slightly larger than the at surface of each transducer to eliminate all rust, scale and moisture. For pipes with rough surfaces, such as ductile iron pipe, wire brush the surface to a shiny nish. Paint and other coatings need not be removed unless aked or bubbled. Plastic pipes typically do not require surface preparation other than soap and water cleaning.
Properly orient the transducers and spaced them on the pipe to provide optimum reliability and per formance. On horizontal pipes, when Z-Mount is required, mount the transducers 180 radial degrees from one another and at least 45 degrees from the top-dead-center and bottom-dead-center of the pipe. See Figure 2.2 Also see Z-Mount Transducer Installation. On vertical pipes the orientation is not critical.
Measure the spacing between the transducers using the two spacing mark s on the sides of the transducers. These marks are approximately 0.75” (19 mm) back from the nose of the FST4/FST5 transducers. See Figure 2.3.
Mount FST1, FST2, and FST3 transducers with the cable exiting within ±45 degrees of the side of a horizontal pipe. See Figure 2.2. On vertical pipes the orientation does not apply.
Figure 2.3 - Transducer Alignment Marks
V-Mount and W-Mount Installation
Application of Couplant
For FST4 and FST5 transducers, place a single bead of couplant, approximately ½ inch (12 mm) thick, on the at face of the transducer. See Figure 2.4. Generally, a silicone-based grease is used as an acoustic couplant, but any grease-like substance that is rated not to “ow” at the temperature that the pipe may operate at will be acceptable. For pipe surface temperature over 130°F (55°C) Sonotemp® (P.N. D002­2011-010) is recommended.
½”
(12 mm)
Figure 2.4 - Application of Couplant
Z205739-0D PAG E 11 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
INSTALLATION GUIDE
Transducer Positioning
1. Place the upstream transducer in position and secure with a mounting strap. Place straps in the arched groove on the end of the transducer. A screw is provided to help hold the transducer onto the strap. Tighten the transducer strap securely.
2. Place the downstream transducer on the pipe at the calculated transducer spacing. See Figure 2.5. Apply rm hand pressure. If signal strength is greater than 5, secure the transducer at this location. If the signal strength is not 5 or greater then using rm hand pressure, slowly move the transducer both towards and away from the upstream transducer while observing signal strength. Clamp thetransducer where the highest signal strength is observed. Signal levels much less than 5 may not yield acceptable data.
Note: Signal strength readings upd ate only every few seconds, so it is advisable to move the transducer 1/8”, wait, see if signal is increasing or decreasing and then repeat unti l
the highest level is achieved.
3. If after adjustment of the transducers the signal strength does not rise to above 5, then select an alternate transducer mounting method. If the mounting method was W-Mount, then re-congure the monitor for V-Mount, move the downstream transducer to the new spacing distance and repeat Step 4.
Small Pipe Transducer Installation
The small pipe transducers are designed for specic pipe outside diameters. Do not attempt to mount a transducer onto a pipe that is either too large or too small for the transducer.
FST1, FST2, and FST3 installation consists of the following steps:
1. Apply a thin coating of acoustic coupling grease to both halves of the transducer housing where the housing will contact the pipe. See Figure 2.6.
1/16” (1.5 mm)
Acoustic Couplant Grease
Figure 2.6 - Application of Acoustic Couplant — FST1, FST2, FST3 Transducers
2. On horizontal pipes, mount the transducer in an orientation such that the cable exits at ±45 degrees from the side of the pipe. Do not mount with the cable exiting on either the top or bottom of the pipe. On vertical pipes the orientation does not matter. See Figure 2.2.
Transducer
Spacing
Figure 2.5 - Transducer Positioning
3. Tighten the wing nuts or “U” bolts so that the acoustic coupling grease begins to ow out from the edges of the transducer or from the gap between the transducer halves. Do not over tighten.
4. If signal strength is less than 5, remount the transducer at another location on the piping system.
5. Conguration Procedure:
a. Establish communications with the transit tme meter. See Part 5 ­Software Utility.
b. From the tool bar, select calibration.
USP - Device Addr 127
Configuration CalibrationStrategy
Device Addr 127
1350 Gal/Min
Flow:
Pos: Neg:
Margin:
Delta T:
0 OB 0 OB 0 OB
15.6% 100%
-2.50 ns 09:53:39
Totalizer Net:
Sig. Strength:
Last Update:
Errors
2000
1600
1200
HelpWindowCommunicationsViewEditFile
!
Print PreviePrint
Scale:60 MinTime:
200
c. On the pop-up screen, click Next twice to get to page 3 of 3. Click Edit in this screen.
Z205739-0D PAGE 12 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
INSTALLATION GUIDE
Calibration (Page 3 of 3) - Linearization
28.2
Gal/M
Delta Time
1) Please establish a reference flow rate.
1FPS / 0.3MPS Minimum.
2) Enter the reference flow rate below. (Do not enter 0)
3) Wait for flow to stabilize.
4) Press the Set button.
Flow:
Set
Edit
Export...
d. In the Calibration Points Editor screen, use the Add and Remove buttons as needed. Click OK when complete.
e. The display returns to Calibration (Page 3 of 3). Click nish
f. Power cycle the unit to activate the new settings.
Mounting Transducers in Z-Mount Configuration
Installation on larger pipes requires careful measurements of the linear and radial placement of the FST4 and FST5 transducers. Failure to properly orient and place the transducers on the pipe may lead to weak signal strength and/or inaccurate readings.
1. Place the transducers on opposite sides of the pipe. This distance around the pipe is calculated by multiplying the pipe diameter by 1.57. The transducer spacing along the pipe is the same as found in the Transducer Positioning section.
2. For FST4 and FST5 transducers, place a single bead of couplant, approximately ½ inch (12 mm) thick, on the at face of the transducer. See Figure 2.4. Generally, a silicone-based grease is used as an acoustic couplant, but any good quality grease-like substance that is rated to not “ow” at the temperature that the pipe may operate at is acceptable.
3. Place the upstream transducer in position and secure with a stainless steel strap or other fastening device. Place straps in the arched groove on the end of the transducer. A screw is provided to help hold the transducer onto the strap. Tighten transducer strap securely. Larger pipes may require more than one strap to reach the circumference of the pipe.
4. Place the downstream transducer on the pipe at the calculated transducer spacing. See Figure 2.7. Using rm hand pressure, slowly move the transducer both towards and away from the upstream transducer while observing signal strength. Clamp the transducer at the position where the highest signal strength is observed. Signal strength of between 5 and 98 is acceptable. The fac tory default signal strength setting is 5, however there are many application specic conditions that may prevent the signal strength from attaining this level.
A minimum signal strength of 5 is acceptable as long as this signal level is maintained under all ow conditions. On certain pipes, a slight twist to the transducer may cause signal strength to rise to acceptable levels.
5. Certain pipe and liquid characteristics may cause signal strength to rise to greater than 98. At this level, the signals may saturate the input ampliers and cause erratic readings. To lower the signal strength, change the transducer mounting method to the next longest transmission path. For example, if there is excessive signal strength and the transducers are mounted in a Z-Mount, try changing to V-Mount or W-Mount. Finally you can also move one transducer slightly o line with the other transducer to lower signal strength.
6. Secure the transducer with a stainless steel strap or other fastener.
TOP OF PIPE
TOP VIEW
OF PIPE
Distance = Pipe Outer Diameter * 1.57
Figure 2.7 - Z-Mount Transducer Placement
PIPE CROSS SECTIONAL
VIEW
Z205739-0D PAGE 13 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
1 2 3 4
O N
PART 3 - INPUTS/OUTPUTS
FSRxxxx SERIES
INSTALLATION GUIDE
General
The FSR1 is available in two congurations: the ow model and the energy model. The ow model is equipped with a 4-20 mA output, two open collec tor outputs, a rate frequency output, and RS-485 communications using the Modbus RTU command set. The energy version has inputs for two 1,000 Ω RTD sensors in place of the rate frequency and alarm outputs. This version allows the measurement of pipe input and output temperatures for calculating energy usage calculations.
4-20 mA Output
The 4-20 mA output interfaces with most recording and logging systems by transmitting an analog current signal that is propor tional to system ow rate. The 4-20 mA output is internally powered (current sourcing) and can span negative to positive ow/energy rates.
For AC powered units, the 4-20 mA output is driven from a +15 VDC source located within the meter, isolated from earth ground connections. The AC powered model accommodates loop loads up to 400 Ω. DC powered meters utilize the DC power supply voltage to drive the current loop. The current loop is not isolated from DC ground or power. Figure 3.1 shows graphically the allowable loads for various input voltages. The combination of input voltage and loop load must stay within the shaded area of Figure 3.1.
Supply Voltage - 7 VDC
1100
1000
900
800
700
600
500
400
Loop Load (Ohms)
300
200
100
10 12 14 16 18 20 22 24 26 28
0.02
Supply Voltage (VDC)
= Maximum Loop Resistance
Operate in the
Shaded Regions
90-265 VAC
Loop
Resistance
Figure 3.2 - 4-20 mA Output
AC Neutral Signal Gnd. Control 1 Control 2 Frequency Out 4-20 mA Out Reset Total
Signal Ground
Meter Power
7 VDC
Drop
The 4-20 mA output signal is available between the 4-20 mA Out and Signal Gnd. terminals as shown in Figure 3.2.
Control Outputs
Two independent open collector transistor outputs are included with the ow meter. Each output can be congured for one of the following four functions:
Rate Alarm
Signal Strength Alarm
Totalizing/Totalizing Pulse
Errors
None
Both control outputs are rated for a maximum of 100 mA and 10 to 28 VDC. A pull-up resistor can be added externally or an internal 10 kΩ pull-up resistor can be selected using DIP switches on the power supply board.
Figure 3.1 - Allowable Loop Resistance (DC Powered Units)
Figure 3.3 - Switch Settings
Switch S1 S2 S3 S4
On Control 1 pull-up;
Resistor IN circuit
O Control 1 pull-up;
Resistor OUT OF
circuit
Table 3.1 - DIP Switch Functions
Control 2 pull-up; Resistor IN circuit
Control 2 pull-up; Resistor OUT OF
circuit
Frequency output
pull-up;
Resistor IN circuit
Frequency output
pull-up;
Resistor OUT OF
circuit
Z205739-0D PAGE 14 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Square wave
output
Simulated turbine
output
TM
FSRxxxx SERIES
INSTALLATION GUIDE
Set the on/o values for the Rate Alarm and Signal Strength Alarm using either the keypad or the software utility.
Typical control connections are illustrated in Figure 3.4. Please note that only the Control 1 output is shown. Control 2 is identical except the pull-up resistor is governed by SW2.
VCC
10K
O
90-265 VAC AC Neutral Signal Gnd. Control 1 Control 2 Frequency Out 4-20 mA Out Reset Total
N
1 2 3 4
SW1/SW2
Figure 3.4 - Typical Control Connections
10 - 28
VDC
100 mA Maximum
90-265 VAC AC Neutral Signal Gnd. Control 1 Control 2 Frequency Out 4-20 mA Out Reset Total
O N
VCC
10K
1 2 3 4
SW1/SW2
Alarm Output
The ow rate output permits output changeover at two separate ow rates allowing operation with an adjustable switch deadband. Figure 3.5 illustrates how the setting of the two set points inuences rate alarm operation.
A single-point ow rate alarm places the ON setting slightly higher than the OFF setting, establishing a switch deadband. If a deadband is not established, switch chatter (rapid switching) may result if the ow rate is very close to the switch point.
Minimum
Flow
Maximum
Flow
Totalizer Output for Energy Meter
Energy units can be ordered with a totalizer pulse output option. This option is installed in the position where the Ethernet option would normally be; therefore, the totalizer pulse output option and the Ethernet communications output cannot be installed simultaneously.
Optional totalizing pulse specications:
Signal 1 pulse for each increment of the totalizer’s least signicant digit
Type Opto-isolated, open collector transistor
Pulse Width 30 msec, max. pulse rate 16 Hz
Voltage 28 VDC max.
Current 100 mA max. (current sink)
Pull-up Resistor 2.8 kΩ to 10 kΩ
Wiring and conguring this option is similar to the totalizing pulse output for the ow only version. This option must use an external current limiting resistor.
Totalizing
Pulse Output
Option
Internal
RxD
TB1
Total Pulse
100 mA
Maximum
V
CC
2.8K to 10K
Isolated Output
Total Pulse
Pull-up
Resistor
Set OFF
Set ON
Output ON
Output OFF
Deadband
Figure 3.5 - Single Point Alarm Operation
Batch/Totalizer Output
Totalizer mode congures the output to send a 33 mSec pulse each time the display totalizer increments divided by the TOT MULT. The TOT MULT value must be a whole, positive, numerical value.
Fir example, If the totalizer exponent (TOTL E) is set to E2 (×100) and the totalizer multiplier (TOT MULT) is set to 1, then the control output pulses each time the display totalizer increments or once per 100 measurement units totalized.
Signal Strength Alarm
The SIG STR alarm provides an indication that the signal level reported by the transducers has fallen to a point where ow measurements may not be possible. It can also be used to indicated that the pipe has emptied. Like the rate alarm described previously, the signal strength alarm requires that two points be entered, establishing an alarm deadband. The ON value must be lower than the OFF value. If a deadband is not established and the signal strength decreases to approximately the value of the switch point, the output may “chatter.”
Error Alarm Outputs
When a control output is set to ERROR mode, the output activates when an error causes the meter to stop measuring reliably. See the Appendix of this manual for a list of potential error codes.
Z205739-0D PAGE 15 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
FSRxxxx SERIES
INSTALLATION GUIDE
Frequency Output [FSRxxx1x only]
The frequency output is an open-collector transistor circuit that outputs a pulse waveform that varies proportionally with ow rate. This type of frequency output is also know as a “Rate Pulse” output. The frequency output is proportional to the max ow rate entered into the meter. The maximum output frequency is 1000 Hz.
In addition to the control outputs, the frequency output can be used to provide total information by use of a K-factor that relates the number of pulses from the frequenc y output to the number of accumulated pulses that equates to a specic volume.
This relationship is described by the following equation: K-factor = 60,000 / full scale units. The 60,000 relates to measurement units in volume/min. Measurement units in seconds, hours or days would require a dierent numerator.
If the frequency output is to be used as a totalizing output, then the meter and the receiving instrument must have identical K-factor values programmed into them to ensure that accurate readings are recorded by the receiving instrument. Unlike standard mechanical ow meters such as turbines, gear or nutating disk meters, the K-factor can be changed by modifying the MAX RATE ow rate value.
Note: For a full treatment of K-factors p lease see the Appendix of this manual.
There are two frequency output types available:
1.) Turbine meter simulation - This option is utilized when a receiving instrument is capable of interfacing directly with a turbine ow meter’s magnetic pickup. The output is a relatively low voltage AC signal whose amplitude swings above and below the signal ground reference. The minimum AC amplitude is approximately 500 mV peak-to-peak. To activate the turbine output circuit, turn SW4 OFF .
To interconnect meters, utilize three-wire shielded cable such as Belden® 9939 or equal. In noisy environments, connect the shield on one end to earth ground. Use a USB to RS-485 converter to communicate with a PC running Windows 98, Windows ME, Windows 2000, Windows NT, Windows XP, Windows Vista, or Windows 7. For computers with RS-232C serial ports, use an RS-232C to RS-485 converter to interconnect the RS-485 network to a communication port on a PC. If monitoring more than 126 meters, use an additional converter and communication port.
4-20 mA Out Reset Total Modbus Gnd Modbus B Modbus A
RS232 to RS485
Model 485USBTB-2W
USB to RS485
TD(A)-
TD(B)+
GND
GND
4-20 mA Out Reset Total
A (-)
B (+)
A (-)
B (+)
GND
Modbus Gnd Modbus B Modbus A
+12V
RS-485
To 12 VDC
Supply
Model 485SD9TB
RS-232
RS-485 Converter
Figure 3.9 - RS-485 Network Connectio ns
Heat Flow [BTU meters only]
The BTU meter allows the integration of two 1000 Ω, 3-wire, platinum RTDs with the ow meter, providing a means of measuring energy consumed in liquid heating and cooling systems. The RTDs are attached at the factory to a simple plug-in connector eliminating the possibility of mis-wiring. Simply install the RTDs on or in the pipe as recommended, and then plug the RTDs into the meter. The surface mount versions are available in standard lengths of 20 feet (6 meters), 50 feet (15 meters) and 100 feet (30 meters) of attached shielded cable.
BACK OF
CONNECTOR
500 mV
0
p-p
Figure 3.7 - Frequency Output Waveform (Simulated Turbine)
2.) Square-wave frequency - This option is utilized when a receiving instrument requires that the pulse voltage level be either of a higher potential and/or referenced to DC ground. The output is a square-wave with a peak voltage equaling the instrument supply voltage when the SW3 is ON. If desired, an external pull-up resistor and power source can be utilized by leaving SW3 OFF. Set SW4 to ON for a square-wave output.
+V
0
Figure 3.8 - Frequency Output Waveform (Square Wave)
RS-485
The RS-485 feature allows up to 126 metering systems to be placed on a single three­wire cable bus. Each meter is assigned a unique numeric address that allows all of the meters on the cable network to be independently accessed. A Modbus RTU command protocol is used to interrogate the meters. An explanation of the command structure is detailed in the APPENDIX of this manual. Flow rate, total, signal strength and temperature (if so equipped) can be monitored over the digital communications bus. Baud rates up to 9600 and cable lengths to 5,000 feet (1,500 meters) are supported without repeaters or “end of line” resistors.
1000 Ω
RETURN LINE
RTD #2
1000 Ω
SUPPLY LINE
RTD #1
Figure 3.10 - RTD Schematic
Installation of Surface Mount RTDs
Only use surface mount RTDs on well insulated pipe. Installing the RTD in an uninsulated area causes inconsistent temperature readings.
Select areas on the supply and return pipes to mount the RTDs. Remove or peel back the insulation all the way around the pipe in the installation area. Clean an area slightly larger than the RTD down to bare metal on the pipe.
Place a small amount of heat sink compound on the pipe in the RTD installation location. See Figure 3.11. Press the RTD rmly into the compound. Fasten the RTD to the pipe with the included stretch tape.
Z205739-0D PAGE 16 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
Area to Bare Metal Surface
FSRxxxx SERIES
INSTALLATION GUIDE
Route the RTD cables back to the ow meter and secure the cable so that it will not be pulled on or abraded inadvertently. Replace the insulation on the pipe, ensuring that the RTDs are not exposed to air currents.
Heat Tape
MINCO
Heat Sink
Clean RTD Mounting
Compound
Figure 3.11 - Surface Mount RTD Installation
Installation of Insertion RTDs
Insertion RTDs are typically installed through ¼ inch (6 mm) compression ttings and isolation ball valves. Inser t the RTD suciently into the ow stream such that a minimum of ¼ inch (6 mm) of the probe tip extends into the pipe diameter. Only use insertion (wetted) RTDs on pipes that are not insulated.
Mount RTDs within ±45 degrees of the side of a horizontal pipe. On vertical pipes the orientation is not critical. Route the RTD cables back to the ow meter and secure the cable so that it will not be pulled on or abraded inadvertently.
If the cables are not long enough to reach the meter, route the cables to an elec trical junction box and add additional cable from that point. Use three-wire shielded cable, such as Belden® 9939 or equal, for this purpose.
Note: Adding cable adds to the resistance the meter reads and may h ave an eect on absolute accuracy. If cable is added, ensure that the same length is ad ded to both RTDs to minimize errors
due to changes in cable resistance.
Wiring to Meter
After the RTDs have been mounted to the pipe, route the cable back to the meter through the middle hole in the enclosure. Connect to the meter inserting the RTD connector into the mating connector on the circuit board.
ACN
AC IN : 100-240VAC,50/60Hz DC OUT :
C US
ACL
E167432
95 - 264 VAC
AC Neutral
Signal Gnd. 4-20 mA Out Reset Total Modbus Gnd Modbus B Modbus A
www.astrodyne.com
PWC-15E
1500mA250V
372
W
C US
VE
D
R
Figure 3.13 - Connecting RTDs
strodyne
+15V / 0.3A
R
+Vo
-Vo
0.15A
R2807
$
TUV
RoHS
PRODUCT SERVICE
RTD 1
RTD 2
Exc.
Exc.
Sig.
Sig.
Gnd.
Gnd.
Shield
Shield
0 to 50°C
TEMP. SET
0 to 100°C
-40 to 200°C
Modbus
TFX Rx
TFX Tx
Downstream
Upstream
-
-
+
+
RTD’s
SUPPLY LINE
MINCO
MINCO
RETURN LINE
RTD #1
RTD #2
Replacement RTDs
Complete RTD kits, including the energy meters plug-in connector and calibration values for the replacements, are available from the manufacturer.
It is also possible to use other manufacturer’s RTDs. The RTDs must be 1000 Ω platinum RTDs suitable for a three-wire connection. A connection adapter is available to facilitate connection to the meter. See Figure 3.14.
WHITE
PIN #8
PIN #6
PIN #4
PIN #2
PIN #5
PIN #3
PIN #1
RED
BLACK
GREEN
BROWN
BLUE
DRAIN
RTD2
RTD1
WHITE BLACK RED
DRAIN
Figure 3.12 - Insertion Style RTD Installation
GREEN BLUE BROWN
Figure 3.14 - RTD Adapter Connections
Note: It will be necessary to calibrate third par ty RTDs to the meter for proper operation. See the Appendix of this manual for the calibration procedure.
Z205739-0D PAGE 17 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
PIN#5 PIN#3 PIN#1
PIN#8 PIN#6 PIN#4
PIN#2
TM
FSRxxxx SERIES
PART 4 - STARTUP AND CONFIGURATION
Before Starting the Instrument
Note: Flow meter systems require a full pipe of l iquid before a successful start-up can be completed. Do not at tempt to make adjustmen ts or change congurations until a full pipe is veried.
Note: If Dow 732 RTV was used to couple the transducers to the pipe, the adhesive must be fully cured before readin gs are attempted. Dow 732 requires 24 hours to cure satisfactoril y. If
Sonotemp® acoustic coupling grease was utilized as a coupla nt, curing is not required.
INSTALLATION GUIDE
Instrument Startup
1. Verify that all wiring is properly connec ted and routed, as described in Part 1 of this manual.
2. Verify that the transducers are properly mounted, as described in Part 2 of this manual.
3. Apply power. The display briey shows a software version number and then all of the segments illuminate in succession.
Important!: In order to complete the installation of the ow meter, the pipe must be full of liquid.
To verify proper installation and ow measurement operation:
1. Go to the SER MENU and conrm that signal strength (SIG STR) is between 5 and
98. If the signal strength is lower than 5, verify that proper transducer mounting methods and liquid/pipe characteristics have been entered. To increase signal strength, if a W-Mount transducer installation was selected, re-congure for a V-Mount installation (standard from factory); if V-Mount was selected, re­congure for Z-Mount.
Note: Mounting conguration change s apply only to FST4, FST5 transducer sets.
2. Verify that the actual measured liquid sound speed is within 2% of the value entered as FLUID SS in the BSC MENU. The measured liquid sound speed (SSPD FPS and SSPD MPS) is displayed in the SER MENU. The pipe must be full of liquid in order to make this measurement.
Keypad Programming
Congure units with keypads using the keypad interface or by using the Windows® compatible software utility. Units without a keypad can only be congured using the software utility. See Part 5 of this manual for software details. Of the two methods of conguration, the sof tware utility provides more advanced features and oers the ability to store and transfer meter congurations between meters. All entries are saved in non-volatile ash memor y and are retained indenitely in the event of power loss.
The four-key tactile feedback keypad interface allows the user to view and change conguration parameters used by the operating system.
Mode
Indicators
Figure 4.1 - Keypad Interface
Keypad
1. Press the MENU key from RUN mode to enter PROGRAM mode. Press the MENU key in PROGRAM mode to exit from conguration parameter selection and menus. If changes to any conguration parameters are made, the user is prompted with a SAVE? when returning to RUN mode. Choose YES to save the new parameters in program memory.
2. The arrow ▼ keys are used to scroll through menus and conguration parameters. The arrow keys are also used to adjust parameter numerical values.
3. The ENTER key functions are:
• Pressed from the RUN mode to view the current software version operating in the instrument.
• Used to access the conguration parameters in the various menus.
• Used to initiate changes in conguration parameters.
• Used to accept conguration parameter changes.
Menu Structure
The ow meter rmware uses a hierarchical menu struc ture. A map of the user interface is included in the Appendix of this manual. The map provides a visual path to the conguration parameters that users can access. Employ this tool each time conguration parameters are accessed or revised.
The seven menus used in the software are as follows:
Menu Description
BSC Basic. Contains all of the conguration parameters necessary to initially program
CH1 Channel 1. Congures the 4-20 mA output.
CH2 Channel 2. Congures the type and operating parameters for channel 2 output
SEN Sensor. Used to select the sensor type (i.e. FST1, FST2, etc.).
SEC Security. Used for resetting totalizers, returning ltering to factory settings, and
SER Service. Contains system settings used for advanced conguration and zeroing
DSP Display. Used to congure meter display functions.
the meter to measure ow.
options. Channel 2 parameters are specic to the model used.
revising the security password.
the meter on the pipe.
Z205739-0D PAGE 18 ©2013 Veris Industries 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Loading...
+ 41 hidden pages