EP Series transducers are sold as an open device.
Pressure Monitoring | Electropneumatic Transducers
EP3 SERIES
Micro-Controlled with High-Performance,
Low-Power Coil Poppet Valve Technology
EP3
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.
Field-selectable
Field-selectable 4 to 20 mA/
0-5 V/0-10 Vdc input for
application exibility
Quiet operation
Poppet valve technology for quiet
operation
Manual override
Manual override with set and hold
feature…great for commissioning
leaky systems
APPLICATIONS
Multi-point
calibration
3 to 15 psi (5-point calibration)
and 0 to 20 psi (6-point
calibration)
Pressure loss
alarm
Pressure loss alarm provides a
contact closure if the EP3 is unable
to achieve the desired output
within a fixed length of time
Fail-safe vent
Fail-safe vent solenoids bleed
branch pressure on power failure
for added safety
The EP3 Series combines a microcontroller with high performance,
low power coil poppet valve technology to create a system with
unparalleled accuracy and proven reliability. The poppet valves used
in the EP3 consume no air, eliminating unnecessary air losses in the
system and allowing for efficient, long-term operation. The EP3 permits
versatility, since all models feature manual override and a tri-state
control option. The LCD provides easy visibility and the LED indicators
provide visual status of valve operation in manual or automatic mode.
All models come with SnapTrack housing and optional covers are
available.
SPECIFICATIONS
GENERAL
Input Power Class 2; 22 to 30 Vdc/20 to 30 Vac, 47 to 63
Hz,150 mA max. average, 350 mA peak
Control Input Class 2; 4 to 20 mA/0-5 V/0-10 Vdc; switch-
selectable, Tri-State, PWM
Input Impedance 4 to 20 mA, 250 Ω; 0-5 V/0-10 Vdc, 10 kΩ
Manual Override Digital pushbutton adjust, switch-selectable
mode
Alarm Contact 100 mA@30 Vac/dc (Pressure loss, manual mode,
jumper selectable)
Accuracy 1% FS; combined linearity, hysteresis,
repeatability @20 °C (68 °F) ambient
Temperature Coefficient ±0.1%/°C
Operating Temp Range 41 to 140 °F (5 to 60 °C)
Operating Hum. Range 10 to 90% RH non-condensing
• Hospitals
• Schools
SCIM 523 in3/min @ 45 psi; (8570 cm3/min @ 310.3
kPa); 333 in3/min @ 20 psi (5457 cm3/min @
137.9 kPa)
Supply Pressure Min (0.1 psi + user F.S. pressure); Max 45 psig
Control Range User programmable zero selectable from
0 to 25 psi: Full scale 0 to 25 psi
Pressure Differential 0.1 psig (supply to branch)
Pressure Indication Electronic, 3-½ digit backlit LCD
Min. Tubing Length 15 feet*
Port Connection 1/8” I.D. poly tubing
Media Connection Clean, dry air, or inert gas. Do not use with
oxygen service
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
**
Available
*For shorter tubing runs use the Veris A A45 Pneumatic Capacitor
EMC Conformance: Low voltage direc tive 2014/35/EU; EMC directive 2014/30/EU.
EMC Special Note - CE option: Connect this product to a DC distribution network or an AC/DC
power adaptor with proper surge protection (EN 61000-6-1 specif ication requirements).
**The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
• Pneumatic dampers/actuators
TM
HQ0001829.E 0117
Pressure Monitoring | EP3 Series
CURRENT/VOLTAGE CONTROL
Wiring Diagrams
• Input switch set to voltage (0 to 5 Vdc or 0 to 10 Vdc)
• Input volt jumper set to either 0 to 5 Vdc or 0 to 10 Vdc
• Input switch set to 4 to 20 mA
• Output jumper set to 0 to 10 Vdc
TRI-STATE CONTROL
Wiring Diagrams
DIMENSIONAL DRAWINGS
DUST COVER
Dimensional Drawings (Front View)
Side View
ORDERING INFORMATION
Output
EP3
0 = None
3 = Ana log output:
0-10VDC, or 4 -20mA,
selectable
Example:
EP 3 3 3 1 S 2
Feedback
3
= Pressure Loss
Alarm, or Manual
Mode Alarm
Option = Cov er Plate
• Input switch set to "TRI-STATE"
• Tri-state jumper set to "ON "
Fails afe
0 = None
1 = Vent on
Powe r Fail
US or EU
S = Standard
C = CE,includes
cover plate
Option
Blank = Non e
2 = EP Cover Plate
CONFIGURATION
HQ0001829.E 0117
TM