Current Monitoring | Direct Current Transducers:
Split-Core, 4 to 20 mA Output
H971 & EA20 SERIES
DC Applications
pulse reset
technology™
U.S. Pat. #6,160,697; 6,522,517; 7,242,157
TM
Hawkeye DC Transducers provide accurate load level monitoring of
DC loads. The H971 and EA20 use Pulse Reset Technology™ with field
proven circuitry to provide a superior solution for DC applications with
minimal risk of permanent magnetization, providing longer life and
better accuracy.
The EA20 and the H971 have 4 to 20 mA output only. The H971 also
offers bi-directional sensing capability and a user-adjustable span to
allow greater application flexibility.
H971
Retrofit
Self-gripping iris for easy
installation
Flexibility
Bracket can be installed in three
different configurations
Pulse Reset
Technology™
Patented Pulse Reset Technology
significantly increases accuracy…
sensor is not affected by stray
magnetic fields, minimize
magnetization from over-current
faults
APPLICATIONS
• Battery chargers
• Motor armature current
• Motor field current
• Automotive loads
HOA
Bi-directional model…useradjustable span from ±20
to ±200 A (H971)
Status LED
Status LED ensures proper wiring
100, 150 and 200
Amp span
100, 150, and 200 A versions
available…application flexibility
(EA20 uni-directional model)
• Marine equipment
• Solar energy applications
• Telecom
• Electroplating
SPECIFICATIONS
System Technology Exclusive Pulse Reset Technology™
Amperage Range
Sensor Supply Voltage 12 to 24 Vdc
Supply Current 35 mA
Insulation Class H971: 600 Vdc, EA20: 1000 Vdc
Temperature Range -30 to 60 °C (-22 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Output
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Response Time Less than 150 msec
ACCURAC Y
Accuracy at Ranges
Below 100 A
Accuracy at Ranges
Above 100 A
Withstand Current 25,000 ADC
WARRANTY
Limited Warranty 5 years
H971: ±200 ADC;
EA20: 0 to 100 ADC/0 to 150 ADC/0 to 200
ADC
1
2
H971: Bidirectional 4 to 20mA (adjust.
3
; EA20: Unidirectional 4 to 20 mA
span)
±0.5 A (combined linearity, hysteresis,
and repeatability)
±0.5% full scale (combined linearity,
hysteresis, and repeatability)
5
5
AGENCY APPROVALS
Agency Approvals
Note: Do not use the LED status indicators as evidence of applied voltage.
1. For currents over 120A, supply voltage must be at least 15V.
2. For H971, at zero monitored current: 35mA max.; at 200A monitored current:
55mA to 100mA depending on supply voltage and current polarity.
3. Unless factory set per customer specifications (H971SP only).
4 . The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration
of Conformity for additional details.
5. For single conductor through product (no wraps).
CE 4: EN61010-1, CAT III, Pollution
Degree 2, basic insulation
TM
HQ0001768.G 0117
Current Monitoring | H971 & EA20 Series
H932/H952
Dimensional Drawing
Removable Mounting Bracket
1.0”
(25 mm)
1.1”
(26 mm)
0.8”
(21 mm)
3.1”**
(79 mm)
2.8”
(70 mm)
Ø 0.3”
(8 mm)
2.5”
(64 mm)
3.0”
(76 mm)
* Terminal block may extend up to 1/8” over the height
dimensions shown.
** Slide switch may extend up to 1/4” over the height
dimensions shown.
Bracket can
be mounted
on three sides
for added
installation
flexibility.
Self-gripping Iris
1.4”*
(36 mm)
EA20 LINE AR OUTPUT
Scale software as shown
20 mA
SENSOR OUTPUT
4 mA
0 A
SENSED AMPS
EA20: 100/150/200 A
H971 BIDIRECTIONAL OUTPUT
Scale software as shown
20 mA
12 mA
SENSOR OUTPUT
H971/EA20
Wiring Diagram
CONTROLLER
4 to 20 mA
Ground
Sensor Supply
DC
Load
SEIRT
SU
3
227
DN
I
9 n
S
655
I
o
ge
REV
8-4
rO
5
,d
3
-00
n
al
t
8
roP
1
179
rosneS tnerruC DC
200A
!
12-24 VDC
Current
4-20
Gnd Power
Flow
mA
Span
CONTACTOR
4 mA
1
-200 A
0 A
SENSED AMPS
1. Field Adjustable from ±20 A to ±200 A
(not applicable to customer-specified factory scaled models)
ORDERING INFORMATION
MODEL
PULSE RESET
TECHNOLOGY
H971 • 0 to 200 A Bidirectional 4 to 20 mA Split-core
H971SP • 0 to 200 A1 Bidirectional 4 to 20 mA Split-core
EA20BB010 • 0 to 100 A Unidirectional 4 to 20 mA Split-core
EA20BB015 • 0 to 150A Unidirectional 4 to 20 mA Split-core
EA20BB020 • 0 to 200A Unidirectional 4 to 20 mA Split-core
1. Range set in factory per customer specified value from 0 to ±20 A through 0 to ±199 A.
2. UL Recognized.
AMPE RAG E
RANGE (DC)
SENSOR OUTPUT HOUSING
Hawkeye Series
EA Series
+200 A
1
STAT U S
LED
UL CE ROHS
• • • •
• • • •
• •
• •
• •
2
2
2
• •
• •
• •
HQ0001768.G 0117
TM