Veris Industries E681X SERIES, E682X SERIES Data Sheet

Power Metering CTs | Current Tranducers, Voltage
E681X & E682X SERIES
Medium Current Ranges
E681x
E682x
The E681x and E682x Series of current transducers provide a standard voltage output for use with data loggers, chart recorders, and power monitoring equipment. Both series have 0.333 V output. E682x devices are solid-core, while E681x CTs are split-core.
High accuracy
±0.5% from 5% to 120% of rated current for E682x or ±1% from 10% to 100% of rated current for E681x
0.333 V output
0.333 V output
APPLICATIONS
• Data logging
• Recording
• Power monitoring
SPECIFICATIONS
Solid- Core
UL Recognized
UL Recognized
• Energy management
• Alternative energy monitoring
• Cost allocation
SPECIFICATIONS
Split-Core
Output at Rated Current 0.333 Vac
Accuracy 1% from 10% to 100% of rated current
Frequency Range 50/60 Hz
Leads 22 AWG, 600 Vac, UL 1015 bonded pair, 6 ft.
Max. Voltage L-N Sensed Conductor*
Operating Temp Range 0 to 70 °C (32 to 158 °F)
Storage Temp Range -40 to 105 °C (-40 to 221 °F)
Humidity Range 0 to 95% non-condensing
Altitude of Operation 3 km max.
Installation Category Category III, pollution degree 2
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals UL61010-1, EN61010-1
207042
(1.8 m) standard length
E681A051V3: 300 Vac (basic insulation rating), 150 Vac (reinforced insulation rating) E681B101V3 and E681C201V3: 600 Vac (basic insulation rating), 300 Vac (reinforced insulation rating)
*
50
Output at Rated Current 0.333 Vac
Accuracy ±0.5% of reading from 5% to 120% of rated
Frequency Range 50/60 Hz
Leads 22 AWG, 600 Vac, UL 1015 bonded pair,
Max. Voltage L-N Sensed Conductor**
Operating Temp Range -40 to 85 °C (40 to 185 °F)
Storage Temp Range -50 to 105 °C (-58 to 221 °F)
Humidity Range 0 to 95% non-condensing
Altitude of Operation 3 km max.
Agency Approvals UL61010-1, EN61010-1
Installation Category Category III, pollution degree 2
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
207042
*The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details.
** Do not apply these current transducers to circuits having a phase-to-phase voltage greater than the maximum rated voltage (300 Vac or 600 Vac, see above), unless adequate additional insulation is applied between the primary conductor and the current transducers. Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.
current
6 ft. (1.8 m) standard length
*
TM
HQ0004948.G 0117
50 Amp
Power Metering CTs | E681x & E682x SeriesPower Metering CTs | Current Tranducers, Voltage
E6 81X
Dimensional Drawings
D
C
B
B
B
E
D
C
E
D
C
WIRING EXAMPLE
One turn customer supplied
E682X
Dimensional Drawing
A
A
E
A
A = 1.0” (26 mm) B = 0.5” (11 mm) C = 0.4” (10 mm) D = 0.9” (23 mm) E = 1.6” (40 mm)
100 Amp
A = 1.5” (37.5 mm) B = 0.6” (16 mm) C = 0.6” (16 mm) D = 1.85” (47 mm) E = 2.1” (53 mm)
200 Amp
A = 1.5” (39 mm) B = 1.25” (32 mm) C = 1.25” (32 mm) D = 2.5” (64 mm)
White
A
C
B
Ø = E
D
L
0.250” nominal
(6.35 mm nominal)
MODEL L A B C D E
E682A051V3
X1
E6 82A101V3
E682C201V3
E682D401V3
6’
(1.8 m)
6’
(1.8 m)
6’
(1.8 m)
1.3"
(33 mm)
2.3"
(59 mm)
2.8"
(70 mm)
1.
5"
(38 mm)
2.6
"
(66 mm)
2"
3.
(82 mm)
0.7"
(18 mm)
0.7"
(18 mm)
1.0"
(25 mm)
0.8"
(21 m m)
1.2"
(31 m m)
1.4"
(36 mm)
0.4"
(10 mm)
1.0"
(25 mm)
1.25"
(31 m m)
X2
Black
ORDERING INFORMATION
Split-core
MODEL DESCRIPTION
E681A051V 3 Split-core CT, 50 A: 0.333 V, 0.4 in ID, 6 ft leads
E681B101V3 Split-core CT, 100 A: 0.333 V, 0.6 in ID, 6 ft leads
E681C201V3 Split-core CT, 200 A: 0.333 V, 1.25 in ID, 6 ft leads
ORDERING INFORMATION
Solid-core
MODEL DESCRIPTION
E682A051V3 Solid-core CT, 50 A: 0.333 V, 0.4 in ID, 6 ft leads
E6 82A101V3 Solid-core CT, 100 A: 0.333 V, 0.4 in ID, 6 ft leads
E682C201V3 Solid-core CT, 200 A: 0.333 V, 1.0 in ID, 6 ft leads
E682D401V3 Solid-core CT, 400 A: 0.333 V, 1.25 in ID, 6 ft leads
Note: Other lead lengths are available. Consult factory.