Air Quality / Gas Detection | Deluxe Duct & Wall CO2 Sensors, Protocol Communication
CW PROTOCOL SERIES
Individual or 3-in-1 with Modbus or BACnet
Protocol
CWLP
CWXP
CW Protocol Series is a non-dispersive infrared (NDIR) sensor designed
for measuring CO
living spaces. Its measurement range of 0 to 5000 ppm makes it the
premier solution for meeting ASHRAE and other ventilation efficiency
standards.
CW Protocol devices feature embedded BACnet and Modbus
communication protocols, as well as optional temperature and humidity
sensors. An adjustable setpoint relay is provided for direct control and
alarm applications, and the optional setpoint slider and pushbutton
override offer additional local input.
concentration in ventilation systems and indoor
2
Communicating
Embedded BACnet and Modbus
communication protocols…easy
systems integration
Configurable
baud rates
Configurable to multiple baud
rates…transfer data at the
right speed for the system
CO2, RH, temp
CO2, humidity, and temperature
sensors in one device at one
address…provides more
information and maximizes
system capacity
APPLICATIONS
• Controlling ventilation in
response to occupancy
Feature override
Local feature override capability
from the building control
system…added control and
flexibility
Self-calibrating
Innovative self-calibration
algorithm…maximizes
performance. Field calibratable…
minimizes downtime.
NIST or standard
Available with 2% NIST or
2% standard RH
• Office buildings, conference
rooms, schools, retail stores, etc.
SPECIFICATIONS
Input Power
Operating Temp Range
Operating Humidity Range 0 to 95% RH non-condensing
Housing Material High impact ABS plastic, UL 94 V0
Terminal Block Torque 0.22 N-m (2.0 in-lbf) max.
Terminal Block Wire Size 30 to 18 AWG (0.08-0.5mm2)
Protocol BACnet or Modbus (selectable)
Connection 2-wire RS-485
Data Rate
Parity
Address Range 1 to 127
Setpoint Slider Resolution
Option
Override Button Option Remotely readable and resettable
Class 2; 12 to 30 Vdc, 24 Vac 50/60 Hz; 100 mA
max.
No humidity option: 0 to 50 °C (32 to 122 °F);
With humidity option: 10 to 35 °C (50 to 95 °F)
9600, 19200, 38400, 57600 (Modbus),
bps (selectable);
9600, 19200, 38400, 76800 (BACnet),
bps (selectable)
None/Odd/Even (selectable-Modbus); None
(BACnet)
1% full scale
CO2 TRANSMITTER
Sensor Type
Measurement Range 0 to 5000 ppm
Accuracy* ±30 ppm ±2% of measured value
Repeatability ±20 ppm ±1% of measured value
RH TRANSMITTER OPTION
HS Sensor
Accuracy**
Reset Rate*** 24 hours
Stability ±1%@ 20 °C (68 °F) annually for two years
Hysteresis 1.5% typical
Temperature Coefficient ±0.1% RH/°C above/below 25 °C (typical)
TEMPERATURE TRANSMITTER OPTION
Sensor Type Solid-state, integrated circuit
Accuracy ±0.5 °C (±1 °F) typical
Non-dispersive infrared (NDIR) diffusion
sampling
Replaceable digitally profiled thin-film
capacitive ; (32-bit mathematics); U.S. Patent
5,844,138
±1% from 12 to 60% RH; ±2% from 10 to 80%
RH; NIST traceable multi-point calibration
TM
HQ0001721.F 0117

Relay N.O.
Relay N.C.
COMMON
Air Quality / Gas Detection | CW Protocol Series
SPECIFICATIONS, CONT.
Resolution 0.1 °C (0.2 °F)
Range 10 to 35 °C (50 to 95 °F)
RELAY CONTACTS
1 Form C (SPDT) 1 A@30 Vdc, resistive; 30 W max.
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
†
EMC Conformance: Low voltage directive 2014/35/EU and EMC directive 2014/30/EU.
EMC Special Note: Connec t this product to a DC distribution network or an AC/DC power
adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements)
* Measured at NTP
** Specified accuracy with 24 Vdc supplied power with rising humidity.
*** Reset rate is the time required to recover to 50% RH after exposure to 90% RH for 24
hours.
† The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformit y
for additional details.
Note: Rough handling and transportation may cause a temporar y reduction of CO
accuracy. With time, the ABC function will tune the readings back to the correct accuracy
range. The default tuning speed is limited to 30 ppm per week.
WIRING DIAGRAM DIMENSIONAL DRAWING
+
POWER SUPPLY
12 to 30 Vdc, 24 Vac
-
CONTROL SYSTEM
COMMON
-
RS-485+
RS-485 -
SHIELD
K1 N.O.
COMMON
K1 N.C.
3.5"
4.8"
(122 mm)
1.2"
(30 mm)
sensor
2
PWR
GND
RS-485+
RS-485-
SHIELD
ORDERING INFORMATION
Local
Display
CW
L = LCD
X = No Display
Example:
CW
Protocol
P= Protocol
H
T X 3PL
RH Optio n
X = No RH
2 = RH 2% NIST
H = RH 2%
Temp. Option
X = No Temp
T = Temp Transmitte r
*Only available if temperature option is selected.
Temp Cal. Cer t.
X = None
1 = 1 pt. cal. ce rt.*
2 = 2 pt. cal. ce rt.*
Option
Blank = Non e
1 = Pushbut ton override
2 = Set point s lider
3 = Pushbut ton override
+ setpoi nt slider
Housing
Blank = Clo ud white
B = Black
HQ0001721.F 0117
TM