Air Quality / Gas Detection | Deluxe Duct & Wall CO2 Sensors
C SERIES
Individual or 3-in-1 CO2, RH and Temperature
CWL
CDL
CDL/CWL carbon dioxide (CO2) sensors maximize energy savings, while
helping optimize ventilation. These sensors allow ventilation systems
to be controlled by the amount of CO
Series detect fluctuations in CO
provide an inlet of fresh air optimal for the space at a given time saving
energy and increasing tenant comfort.
SPECIFICATIONS
present in a space. The CWL/CDL
2
levels and signal ventilation systems to
2
Microprocessor
based
Microprocessor-based design
increases accuracy and reduces
installation time
Self-calibrating
Innovative self-calibration
algorithm…easy to maintain
NDIR
Non-dispersive infrared
technology (NDIR) repeatable to
±20 ppm ±1% of measured
value…high accuracy
measurement
APPLICATIONS
• Controlling ventilation in
response to occupancy
• ASHRAE 62.1 air quality
standard compliance
Snap-on
faceplate
Snap-on faceplate…no screws
required, making installation and
service easy
Field-selectable
Field-selectable outputs for
operation flexibility
Integrated probe
Integrated transducer and
probe…eliminates the need to
install a separate pick-up tube
• Office buildings, conference
rooms, schools, retail stores, etc.
Input Power
Analog Output
Operating Temp Range:
CDL
CWL
Operating Humidity Range 0 to 95% RH non-condensing
Housing Material High impact ABS plastic
Terminal Block Torque:
CDL
CWL
Terminal Block Wire Size:
CDL
CWL
CO2 TRANSMITTER
Sensor Type
Output Range 0 to 2000/5000 ppm (programmable)
Accuracy ±30 ppm ±2% of measured value*
Repeatability ±20 ppm ±1% of measured value
Response Time <60 seconds for 90% step change
RH TRANSMITTER OPTION
HS Sensor
Accuracy
Class 2; 20 to 30 Vdc/24 Vac 50/60 Hz;
100 mA max.
4 to 20 mA (clipped and capped)/0 to 5 Vdc/
0 to 10 Vdc (selectable)
0 to 50 °C (32 to 122 °F)
No humidity option: 0 to 50 °C (32 to 122 °F);
With humidity option: 10 to 35 °C (50 to 95 °F)
0.2 N-m (2.0 in-lbf) max.
0.22 N-m (2.0 in-lbf) max.
28 to 14 AWG (0.5 to 1.5mm2)
30 to 18 AWG (0.08 to 0.5mm2)
Non-dispersive infrared (NDIR), diffusion sampling
Fully replaceable, digitally profiled thin-film
capacitive (32-bit mathematics) U.S. Patent
5,844,138
±2% from 10 to 80% RH @ 25 °C; NIST
traceable multi-point calibration
Hysteresis 1.5% typical
Stability ±1% @ 20 °C (68 °F) annually for two years
Output Range 0 to 100% RH
Temperature Coefficient ±0.1% RH/°C above or below 25 °C (typical)
TEMPERATURE TRANSMITTER OPTION
Sensor Type Solid-state, integrated circuit
Accuracy ±0.5 °C (±1 °F) typical
Resolution 0.1 °C (0.2 °F)
Output Range 10 to 35°C (50 to 95°F)
RELAY CONTACTS
1 Form C (SPDT)
(on wall models, relay is
only available in units
without the setpoint slider
option)
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
**
RTD/Thermistors in wall packages are not compensated for internal heating of product.
EMC Conformance: Low voltage direc tive 2014/35/EU and EMC directive 2014/30/EU.
EMC Special Note: Connect this product to a DC distribution network or an AC DC power
adaptor with proper surge protec tion (EN 61000 -6-1 specification requirements).
* Measured at NTP.
**The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
Note: Rough handling and transpor tation may cause a temporary reduction of CO
accuracy. With time, the ABC function will tune the readings back to the correct accuracy
range. The default tuning speed is limited to 30 ppm per week.
1 A@30 Vdc, resistive; 30 W max.
sensor
2
TM
HQ0001739.G 0117

Air Quality / Gas Detection | C Series
CDL (CO2 ONLY)
Wiring Diagram
CONFIGURATION
PUSHBUTTONS
PLUS
ENTER
MINUS
CWL
CO2, RH, Thermistor, Pushbutton
Override, and Relay Options
RH OUT
RTD/THERMISTOR/OVERRIDE OUT
Power (+24)
CO2 OUT
COMMON
RTD/THERMISTOR/OVERRIDE OUT
RELAY N.O.
RELAY COM
RELAY N.C.
V+ CO2-OUT GND
NC COMM NO
mA Volt
ABC
ON
LOW
OFF
1/2” NPT MALE CONDUIT ADAPTER
1/2” NPT FEMALE COUPLER
CWL
CO2, RH, Thermistor, Pushbutton
Overrde, and Setpoint Slider Options
RH OUT
RTD/THERMISTOR/OVERRIDE OUT
Power (+24)
CO
COMMON
RTD/THERMISTOR/OVERRIDE OUT
OUT
2
SLIDER RIGHT
SLIDER WIPER
SLIDER LEFT
CDL (TEMP AND/OR RH OPTIONS)
Wiring Diagram
PLUS
CONFIGURATION
PUSHBUTTONS
ENTER
MINUS
V+
CO2 OUT
GND
RH OUT
TEMP OUT/RTD
RTD
CWL
CO2, RH, Temperature Transmitter
Options, and Relay Options
RH OUT
T OUT
Power (+24)
CO
OUT
2
COMMON
RELAY N.O.
RELAY COM
RELAY
N.C.
NC COMM NO
mA
Volt
CWL
CO2, RH, Temperature
Transmitter, and Setpoint Slider Options
RH OUT
OUT
2
COMMON
T OUT
SLIDER RIGHT
SLIDER WIPER
SLIDER LEFT
Power (+24)
CO
Optional *
Optional *
Optional *
*Connector blocks and headers for optional features are not included with non-option models.
CWL WALL MOUNT
Dimensional Drawing
4.8"
(122 mm)
3.5"
(89 mm)
1.2"
(30 mm)
CDL DUCT MOUNT
Dimensional Drawing
6.7"
(170 mm)
3.1"
(78 mm)
2.4"
(61 mm)
ORDERING INFORMATION
Duct Mo unt Wall Mount
RH Optio n
CDLS CWLS
H = RH2%
X = No RH
*The Push B utton Overrid e feature is not avail able with temper ature transmit ter models. Onl y resistive tempe rature models qua lify for this fea ture.
**Not ava ilable with W and Y hi gh accuracy ther mistors.
Tem p
T = Temp
X = No Temp
(Stop he re)
Sensor Type
A = Transmitte r
B = 100R Platinu m, RTD
C = 1k Platinum, RT D
D = 10k T2, Ther mistor
E = 2.2k, T hermistor
F = 3k, The rmistor
G = 10k CPC, The rmistor
H = 10k T3, Ther mistor
J = 10k Dale, The rmistor
K = 10k w/11k shunt, T hermistor
M = 20k NTC, T hermistor
N = 1800 ohm, Th ermistor
R = 10k US, Ther mistor
S = 10k 3A221, Thermis tor
T = 100k, Th ermistor
U = 20k “D”, Ther mistor
W = 10k T2 high acc uracy, Thermis tor
Y = 10k T3 high acc uracy, Thermist or
Optiona l
Cal Cert
Blank = Non e
1 = 1 pt Temp Cert* *
2 = 2 pt Temp Cert* *
RH
Option
H = RH 2%
X = No RH
Example:
CDLS H T B 2
Tem p.
T = Temp
X = No
(stop h ere)
Sensor
Typ e
A = Transmitte r
B = 100R Platinu m, RTD
C = 1k Platinum, RT D
D = 10k T2, Ther mistor
E = 2.2k, T hermistor
F = 3k, The rmistor
G = 10k CPC, The rmistor
H = 10k T3, Ther mistor
J = 10k Dale, The rmistor
K = 10k w/11k shunt, T hermistor
M = 20k NTC, T hermistor
N = 1800 ohm, Th ermistor
R = 10k US, Ther mistor
S = 10k 3A221, Thermis tor
T = 100k, Th ermistor
U = 20k “D”, Ther mistor
W = 10k T2 high acc uracy, Thermis tor
Y = 10k T3 high acc uracy, Thermist or
10.2"
(258 mm)
(198 mm)
Temp Cal
Cert
X = No
1 = 1pt Temp
Cert**
2 = 2pt Temp
Cert**
Example:
CWLS
7.8"
Available Options
Setpoint
Option
1 = Push But ton
Override*
2 = Set Point
Slider
3 = Push But ton
Override*+Set
Point Slider
Slider Value
A =1k
F =10 k
G =20k
K =50k
M =10 0k
H T C 2 2 A
Optional *
-
Blank = Clo ud white
B = Black
Options
Housing
HQ0001739.G 0117
TM