Power Metering CTs | Current Transformers, 5 A Outputs
AL, BL, CL & H681X-A SERIES
Split-core and Solid-core Designs for Flexibility
AL BL
CL
Veris’ split-core and solid-core current transformers provide a 0 to 5A AC
output for use with transducers, data loggers, and chart recorders.
H681x-5A
Easy installation
Unique hinge design on split cores
5 Amps standard
5 Amp standard output…
compatible with existing systems
APPLICATIONS
• Data logging
• Recording
• Power monitoring
UL Recognized
UL Recognized
• Energy management
• Alternative energy monitoring
• Cost allocation
SPECIFICATIONS
Solid-core
INPUTS
Frequency Range 50 to 400 Hz
Leads 2 ft (0.6 m)
ACCURAC Y
Accuracy Specified at 60 Hz (see Ordering Information)
OUTPUTS
Output at Rated
Current
MECHANICAL
Insulation 600 Vac (basic)
ENVIRONMENTAL
Operating Temp Range -30 to 55 °C (-22 to 131 °F)
Storage Temp Range -30 to 105 °C (-22 to 221 °F)
WARRANTY
Limited Warranty 1 year
AGENCY APPROVALS
Agency Approvals ANSI/IEEE C57.13, “Standard Requirements for
5 A
Instrument Transformers,” IEEE C57.13.2, “IEEE Standard Conformance Test Procedures for Instrument
Transformers,” and cURus.
SPECIFICATIONS
Split-core
INPUTS
Frequency Range 50/60 Hz
Leads 6 ft (1.8 m)
ACCURAC Y
Accuracy ±1% of reading from 10% to 100% of rated current
OUTPUTS
Output at Rated
Current
MECHANICAL
Insulation 600 Vac (basic)
ENVIRONMENTAL
Installation Category Category III, Pollution Degree 2
Operating Temp Range 2400A models only: -15 to 50 °C (5 to 122 °F);
Storage Temp Range -40 to 70 °C (-40 to 158 °F)
Humidity Range 0 to 95% non-condensing
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals UL61010-1, EN61010-1
5 A
All other models: -15 to 60 °C (5 to 140 °F)
E93779
*
E207042
*The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
TM
HQ0001817.H 0117
A
B
E
F
C
D
B
E
F
C
D
A
A
B
E
C
F
D
Power Metering CTs | AL, BL, CL & H681x-A SeriesPower Metering CTs | Current Transformers, 5 A Outputs
WIRING EXAMPLE
One turn
customer
supplied
White
Black
X1
X2
ORDERING INFORMATION
Solid-core
MODEL RAT IO
AL500 50:5 3% 2.0
AL101 100:5
AL151 150 :5 4.0
AL201 200:5 4.0
AL251 250:5 6.0
AL301 300:5 8.0
AL401 400:5 10.0
BL501 500:5 12. 5
BL6 01 600:5 15.0
BL801 800:5 8.0
BL102 1000:5 10.0
BL122 1200: 5 12.5
CL12 2 120 0:5 10.0
CL152 150 0:5 12. 5
CL162 1600:5 12.5
CL202 2000:5 15 .0
Split-core
MODEL RAT IO
H6810-200A-5A 200:5
H6810-300A-5A 300:5 2.5
H6811- 40 0A- 5A 400:5 5.0
H6811- 60 0A-5 A 600:5 5.0
H6811-800A -5A 800:5 12.5
H6 812-80 0A- 5A 800:5 5.0
H6812-1000A-5A 1000:5 22.5
H6 812-1200A-5A 1200 :5 22.5
H6 812-16 00A -5A 1600:5 22.5
H6812-2000A-5A 2000:5 22.5
H6 812-240 0A-5A 2400:5 22.5
ACCURACY
AT 60 Hz
1%
ACCURACY FRO M
10% TO 100% OF MAX
LOAD
1%
CAPACITY IN
BURDEN
CA PACI TY
IN VA
2.0
BURDEN
VA
2.5
AL/BL/CL SOLID-CORE
Dimensional Drawings
AL/SMALL
50 Amp, 100 Amp, 150
Amp, 200 Amp, 250 Amp,
300 Amp, 400 Amp
A = 2.7” (70 mm)
B = 2.5” (63 mm)
C = 1.1” (26 mm)
D = 1.1” (26 mm)
BL/MEDIUM
500 Amp, 60 0 Amp, 800
Amp, 1000 Amp, 120 0 Amp
A = 3.7” (90 mm)
B = 3.4” (88 mm)
C = 2” (52 mm)
D = 1.1” (26 mm)
H681X-5A SPLIT-CORE
Dimensional Drawings
H6810/SMALL
200 Amp, 300 Amp
A = 3.8” (96 mm)
B = 1.2” (30 mm)
C = 1.3” (32 mm)
D = 1.2” (30 mm)
E = 4.0" (100 mm)
F = 4.8" (121 mm)
H6811/MEDIUM
400 Amp, 6 00 Amp,
800 Amp
A = 4.9” (125 mm)
B = 2.9” (73 mm)
C = 2.5” (62 mm)
D = 1.2" (30 mm)
E = 5.2” (132 mm)
F = 6.0" (151 mm)
CL/LARGE
1200 Amp, 1500 Amp, 1600
Amp, 2000 Amp
A = 4.9” (124 mm)
B = 4.5” (115 mm)
C = 3” (76 mm)
D = 1.1” (26 mm)
H6812/LARGE
800 Amp, 100 0 Amp, 1200
Amp, 1600 Amp, 2000 Amp,
2400 Amp
A = 4.9” (125 mm)
B = 5.5” (139 mm)
C = 2.5” (62 mm)
D = 1.2” (30 mm)
E = 7.9" (201 mm)
F = 6.0" (151 mm)
HQ0001817.H 0117
TM