Veris TSERIES Installation Instructions

TDDA
TM
ENVIRONMENTAL SENSORS
T SerieS
Temperature Transmitters
TWxA
TOA
INSTALLATION GUIDE
SPECIFICATIONS
Input Power 4-20mA version: Loop p owered 12-30VDC only, 30mA max; 0-5/0-10V versions: 12-30VDC/24VAC, 15mA max Temp Output 2-wire loop powered 4-20mA or 3-wire 0-5V/0-10VDC (switch selectable in TWx A) Sensor Type Solid-state, integrated circuit (Transmitter) Accuracy ±0.5°C (±1°F) typical Ranges 0° to 50°C (32° to 122°F), -40° to 50°C (-40° to 122°F) Wiring (TOA and TDDA) 22 AWG; 2-wire: 4-20mA; 3-wire: Voltage output models
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
PRODUCT IDENTIFICATION
Output
TDDA
M = 4-20mA V = 0-5/10VDC
Output
TOA
M = 4-20mA V = 0-5/10VDC
Local Display
TW
L = LCD X = No
Range
1 = -40° to 50 ° C (-40° to 122°F ) 2 = 0° to 50°C (32° to 122°F)
Range
1 = -40 to 50° C (-40° to 122°F ) 2 = 0° to 50°C (32° to 122°F)
Sensor Type
A
= Transmitte r selectable outputs
Cal Certificate
0 = None 1 = 1 point Cal v alidation 2 = 2 point Cal v alidation
Cal Certificate
0 = None 1 = 1 point Cal v alidation 2 = 2 point Cal v alidation
Setpoint/Override
0 = None 2 = 1k Setpoint 3 = 10k Setpoi nt 4 = 1k Setpoint w ith override 5 = 10k Setpoi nt with override
PRODUCT OVERVIEW
The TDDA, TOA, and TWxA temperature sensors are equipped with a highly accuracy temperature transmitter with analog output compatible with most building control systems. To maintain accurate func tionality, keep all vents free of dust, debris, etc. These units are warranted for a period of ve years.
INSTALLATION
TDDA
1. Drill a hole in the duct.
2. Insert the temperature probe until the junction box is at against the outer surface of the duct.
3. Use screws to secure the junction box to the duct.
4. Wire as shown (see Wiring section).
TOA
1. Locate the sensor in an outside area, out of direct sunlight (e.g. under an eave, north side of the building).
2. Mount the housing.
3. Wire as shown (see Wiring section).
TWxA
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
1. Mount the housing vertically on an interior wall in the area to be monitored, in a location where air circulates freely. Locate unit away from air outlets, corners, exterior walls, windows, and doors.
2. Wire as shown (see Wiring section).
Cal Certificate
0 = None 1 = 1 point Cal v alidation 2 = 2 point Cal v alidation
Housing Color
None = Cloud White B = Black
Z201986-0P PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
1.2"
(30 mm)
3.5"
(89 mm)
4.8"
(121 mm)
POWER SUPPLY
12 To 30 VDC
DIGITAL CONTROL
Temperature
0-10V
+
Veris #PS-24
0-5V
RED
BLACK
ORANGE
YELLOW
POWER SUPPLY
12 To 30 VDC
DIGITAL CONTROL
Temperature
4-20mA return
+
ORANGE
ORANGE
Veris #PS-24
POWER SOURCE 12 to 24VAC/DC
DIGITAL CONTROL
Temperature
0-5/0-10V
-
-
Thermistor, RTD or Override
Setpoint
Veris PS-24 Series, or Panel
+
RIGHT
WIPER
LEFT
-
POWER SOURCE
12 to 24VDC Only
DIGITAL CONTROL
Temperature
4-20mA
-
-
Thermistor, RTD or Override
Setpoint
Veris PS-24 Series, or Panel
-
+
RIGHT
WIPER
LEFT
T SERIES
INSTALLATION GUIDE
DIMENSIONS
3.4"
(86 mm)
4.6"
(116 mm)
4.6"
(116 mm)
2.8"
(71 mm)
3.4"
(86 mm)
2.8"
(71 mm)
3.9"
(100 mm)
(100 mm)
WIRING - TWXA
TDDA
0.5" Dia. (13 mm.)
8.5"
(216 mm)
TOA
0.9"
3.9"
9.3"
(237 mm)
(22 mm)
TWxA
TWxA – 4-20mA
TWxA – 0-5/0-10V
WIRING - TDDA AND TOA
Z201986-0P PAGE 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05131
NOTE: For 24 VAC transformer powered applicatio ns, connect one si de of the transformer secondary to the common. An isolati on transformer or a dedicated power supply may be required.
CONFIGURATION - TWXA
TDDA/TOA – 4-20mA
Output Select
Volts
Temp Range
32° to 122°F 50° to 95°F
TDDA/TOA – 0-5/0-10V
0° to 50°C 10° to 35°C
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
10V
mA
Temp
5V
Temp
°C °F