Veris TP Installation Instructions

TM
ENVIRONMENTAL SENSORS
TP
Flush Mounted Temperature Sensor
INSTALLATION GUIDE
SPECIFICATIONS
Wiring 22 AWG; 2-wire: RTD/Thermis tor Housing Brushed 430 Stainless Steel Operating Temperature Range -10° to 50°C (14° to 122°F)
PRODUCT OVERVIEW
TP ush mounted temperature sensors monitor the temperature of the air in a room. They are ideal for spaces where moisture and vapor are concerns. The back of the TP is insulated to reduce interior wall temperature inuence. The TP is for indoor use only, and it is warranted for a period of ve years.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
Sensor Type
TP
B = 100R platin um, RTD C = 1k platinum, RTD D = 10k T2, Therm istor E = 2.2k, Ther mistor F = 3k, Therm istor G = 10k CPC, Ther mistor H = 10k T3, Thermi stor J = 10k Dale, Ther mistor K = 10k w/11k shunt, Thermist or M = 20k NTC, Ther mistor N = 1800 ohm, Ther mistor R = 10k US, Thermis tor S = 10k 3A221, Thermis tor T = 100k, The rmistor U = 20k “D”, Thermis tor W = 10k T2 high acc uracy, Thermist or Y = 10k T3 high acc uracy, Thermist or Z = 10k E1, Thermisto r
Cal Certificate
0 = None 1 = 1 point Cal v alidation 2 = 2 point Cal v alidation
INSTALLATION
1. Wire the TP as shown.
DIGITAL CONTROL
Thermistor/RTD
Back of TP steel plate
Orange
2. Using the screws provided, mount the TP to a single-gang box on an interior wall in the area to be monitored, in a location where air circulates freely. Locate the unit away from air outlets, corners, exterior walls, windows, and doors. Make sure the foam insulation is placed inside the steel plate, allowing access to the screw holes.
DIMENSIONS
2.8”
(72 mm)
2x Ø 0.175”
(5 mm)
4.5”
(115 mm)
3.3”
(84 mm)
1.4”
(36 mm)
Z206424-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10121