Installation Guide
Temperature
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
TM
TJ Series
VAV Discharge Temperature Sensor
Product Overview
The TJ Series temperature sensor is designed for VAV systems. The cable is plenum rated, and the probe is stainless
steel for durabilit y. The TJ is warranted for a period of ve years.
Product Identification
TJ
B = 4" (102 mm)
D = 8" (204 mm)
Sensor Type OptionProbe Length
B = 100R platinum, RTD
C = 1k platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
I = 1k Balco (Nickel-iron) RTD
J = 10k Dale, Thermistor
K = 10k w/11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm, Thermistor
R = 10k US, Thermistor
S = 10k 3A221, Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor
CC = 15k, Thermistor
Output
R
= Resistive
Cal Certs
0 = None
1 = 1 Point Cal Cert
2 = 2 Point Cal Cert
0 = Standard 5 ft.
cable, no QDs
1 = 1/4" Female
Quick Discon nects (QD)
2 = 1/4” QDs with
8 ft. lead wires
3 = 10 ft. cable,
no QDs
Specifications
Wiring
Housing
Input Power
Output
Operating Temperature
Accuracy
Calibration Error
Error over Temperature
Increased cable length affects the readings of lower resistance RTDs (100R platinum RTD).
Room temperature error is documented on each unit.
Z203571-0J Page 1 of 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
22 AWG; 2-wire RT D/ Thermistor
Stainless Steel
LINITEM P OPTIO N
5- 30 VDC
1 µA /°S or 10 mV/ °C
Probe: -25° to 105°C (-13 to 221°F )
Range
Wiring side: up to 75°C (167°F)
1.5°C ( 35°F) typical; 2.5°C (37°F ) max. at 25°C (77°F)
1.8°C ( 35° F) ty pical; 3.0°C (34°F) max. over 0° to 70°C ( 32° to 158 °F) range;
2.0°C (35°F) t ypical ; 3.5°C (38°F ) max. over -25° to 105°C ( -13° to 221°F) range
Installation Guide
Temperature
TJSeries
TM
Dimensions
Installation
(38 mm)
2"
(51 mm)
1.1"
(28 mm)
1"
(26 mm)
Optional 1/4” female quick disconnect
0.3"
(6.3 mm)
L as ordered
1. Remove adhesive covering from foam gasket.
2. Push probe through hole in gasket until gasket adheres to underside of mounting ange.
3. Drill a 3/8” diameter hole in the duct for the sensor probe.
4. Mount ange to duct using screws provided.
5. Wire as shown.
Thermistor
RTD
Black
White
Z203571-0J Page 2 of 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.