Veris TD Installation Instructions

Installation Guide
Temperature
TG
TF
TD
• This product is not intended for life or safety applications.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
TM
TD/TF/TG Series
Duct Mounted Temperature Sensors
Product Overview
TD, TF, and TG temperature sensors monitor the temperature of the air inside a duct. The probe is available in multiple lengths to suit multiple applications. All models have standard resistive outputs compatible with building control systems, and all models are warranted for a period of ve years.
Product Identification
Enclosure
T
D = Duct F = Duct w/ mounting box G = Duct w/ water resistant housing
Probe Length
B = 4" (102 mm) C = 6" (152 mm) D = 8" (203 mm) E = 12” (305 mm) F = 18” (457 mm) G = 24” 610 mm) K = 36” (914 mm)
Sensor Type Output
B = 100R platinum, RTD C = 1k platinum, RTD D = 10k T2, Thermistor E = 2.2k, Thermistor F = 3k, Thermistor G = 10k CPC, Thermistor H = 10k T3, Thermistor I = 1k Balco (Nickel-iron) RTD J = 10k Dale, Thermistor K = 10k w/11k shunt, Thermistor M = 20k NTC, Thermistor N = 1800 ohm, Thermistor R = 10k US, Thermistor S = 10k 3A221, Thermistor T = 100k, Thermistor U = 20k “D”, Thermistor W = 10k T2 high accuracy, Thermistor Y = 10k T3 high accuracy, Thermistor Z = 10k E1, Thermistor CC = 15k, Thermistor
= Resistive
Cal Certificate
0 = None 1 = 1 point Cal validation 2 = 2 point Cal validation
Specifications
Wiring
Housing
Approvals
Z205467-0D Page 1 of 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08132
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
22 AWG; 2-wire RT D/ Thermistor
Stainless Steel
COMPLIANCE INFORMATION
CE
Installation Guide
1.5"
Temperature TD/TF/TGSeries
TM
Dimensions
2"
(51 mm)
4.3"
(109 mm)
(74 mm)
(117 mm)
(28 mm)
2.9"
4.6"
1.1"
0.7"
(18 mm)
(38 mm)
2.3" (59 mm)
Foam Gasket
2.5" x 2.5" (62 mm x 62 mm)
1.1"
1.1"
(28 mm)
(28 mm)
TD Model
TF Model
TG Model
0.25" Dia. (6 mm)
0.25" Dia. (6 mm)
0.25"Dia. (6 mm)
L
0.25"Dia. (6 mm)
L
Installation
2.0"
(51 mm)
1. Drill a 3/8” diameter hole into a duc t for the sensor probe.
2. Insert the probe into the duct.
3. Secure the junction box housing (TF/TG) or the mounting ange (TD) to the outer surface of the duct using the self-tapping screws provided.
4. Wire as shown.
Thermistor
RTD
Orange
Orange
Z205467-0D Page 2 of 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08132
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Loading...