Veris TB Installation Instructions

Installation Guide
Temperature
TB
TRA
• This product is not intended for life or safety applications.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
TB/TRA Series
Speciality Temperature Sensors
Product Overview
The TB Series temperature sensor is designed to strap onto a pipe. The copper sensing plate provides a secondary measurement of the temperature inside the pipe. The TRA Series temperature sensor is designed for remote sensing applications. Both devices have output options compatible with building control systems and both are warranted to meet accuracy specications for a period of ve years.
Product Identification
Bracket
Diameter
TB
A = 2 ½" (6.4 cm) max. D = 8" (20 cm) max. E = 12” (31 cm) max.
Sensor
Type
B = 100R platinum, RTD C = 1k platinum, RTD D = 10k T2, Thermistor E = 2.2k, Thermistor F = 3k, Thermistor G = 10k CPC, Thermistor H = 10k T3, Thermistor I = 1k Balco (Nickel-iron) RTD J = 10k Dale, Thermistor K = 10k w/11k shunt, Thermistor
Cal Certificate
M = 20k NTC, Thermistor N = 1800 ohm, Thermistor R = 10k US, Thermistor S = 10k 3A 221, Thermistor T = 100k, Thermistor U = 20k “D”, Thermistor W = 10k T2 high accuracy, Thermistor Y = 10k T3 high accuracy, Thermistor Z = 10k E1, Thermistor CC = 15k, Thermistor
0 = None 1 = 1 point Cal validation 2 = 2 point Cal validation
TM
Sensor Type
Cal Certificate
Cable Length
TRA
B = 100R platinum, RTD C = 1k platinum, RTD D = 10k T2, Thermistor E = 2.2k, Thermistor F = 3k, Thermistor G = 10k CPC, Thermistor H = 10k T3, Thermistor I = 1k Balco (Nickel-iron) RTD J = 10k Dale, Thermistor K = 10k w/11k shunt, Thermistor
M = 20k NTC, Thermistor N = 1800 ohm, Thermistor R = 10k US, Thermistor S = 10k 3A 221, Thermistor T = 100k, Thermistor U = 20k “D”, Thermistor W = 10k T2 high accuracy, Thermistor Y = 10k T3 high accuracy, Thermistor Z = 10k E1, Thermistor CC = 15k, Thermistor
0 = None 1 = 1 point Cal validation 2 = 2 point Cal validation
* Not available f or sensor types B, C, & I. ** Not availabl e for sensor types B, C, E, F, I, & N.
None = 3 ft (0.9 m) A = 6 ft (1.8 m)* B = 10 ft (3.1 m)* C = 20 ft (6.1 m)** D = 25 ft (7.6 m)** E = 50 ft (15 m)** F = 100 ft (30 m)**
Specifications
Wiring
Z205464-0F Page 1 of 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09134
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
22 AWG; 2-wire R TD / Thermistor
Installation Guide
2.9"
(74 mm)
4"
(102 mm)
strap fits pipe diameters up to 12”
Temperature TB/TRASeries
TM
Dimensions
Installation
TRA ModelTB Model
2"
(51 mm)
0.3"
(6 mm)
TB:
1. Clamp the sensor around the pipe to be monitored. Make sure the copper sensing plate is in contact with the pipe surface.
2. Wire the sensor to the controller as shown.
Thermistor
RTD
Orange
Orange
TRA:
1. Set the stainless steel sensing probe in contact with the area to be monitored. No mounting necessary.
2. Wire the sensor to the controller as shown.
Red
Thermistor
RTD
Black
Z205464-0F Page 2 of 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09134