QUICK START GUIDE
S D s e r i e s
SD – Spot Detector
1. Installation
Determine a location. Ram set 6/32 threaded studs in floor on 2.5 inch (63.5mm) centers. Place SD over studs and
secure. Adjust the sense probes to desired height. Connect the white/red and black leads to the FMS, F-Series or
LDRA6 panel. A 24VAC power supply is required for use with a Falcon RA1x2. Test the SD by placing water
under the sense probes.
24 VDC
( Polarity is
Not important )
NC Reset
Push Button
White/Red (+)
Black (-)
SD Diagram 1
P1
EXTERNAL
TB1
VDC
VDC
+ -
TB2 Input 1-4
24VDC
Ch1
Ch2
Ch3
+ -
Black
+ -
Ch4
+ -
+ +
+ -
White/Red
SD Diagram 2: Falcon Wiring
SD-Z – Zone Spot Detector
1. Installation
Determine a location. Ram set 6/32 threaded studs in floor on 2.5 inch (63.5mm) centers. Place SD-Z over studs
and secure. Adjust the sense probes to desired height. Connect the SD-Z to the LDZ control panel by connecting
the two cable connectors to SeaHawk Water Leak Detection Cable (SC), or SeaHawk Non-Sensing Cable (NSC), or
an end terminator (EOL) as shown in SD-Z Diagram 2. Test the SD-Z by placing water under the sense probes.
SD-Z simulates 50 feet (15.24m) of SC cable: 25 feet in and 25 feet out (7.62m in/out) from device.
SD-Z Diagram 1: Pins
S D S D - Z S D - R O 1
Once triggered, latches on, until
power is removed (VDC)
TB3 Input 5-8
Ch5
Ch6
+ -
+ -
Ch7
+ -
EXTERNAL
Ch8
+ -
GND
- -
RELAY 1
NC NO C
TB4
RELAY 2
NC NO C
Specifications
SD-Z Diagram 2: Basic Installation Components
SD-RO1 – Spot Detector with Relay Output
1. Installation
Determine a location. Ram set 6/32 threaded studs in floor on 2.5 inch (63.5mm) centers. Place SD-RO1 over
studs and secure. Adjust the sense probes to desired height. Connect the white (N/O) and green (Com) or blue
(N/C) leads to the alarm device. Connect the black (-) and red (+) leads to the power source. Test the SD-RO1
by placing water under the sense probes.
24 VAC / DC
Reset Push Button
VDC applications only)
(Normally Closed
,
Red (+)
Black (-)
White (N.O .)
Green (Com )
Blue (N. C.)
Brown (Not Used )
SD-RO1 Diagram 1: Basic Wiring
Once triggered, latches on, until
power is removed (VDC)
Power
SD, SDZ
SDRO1
Outputs
Solid State
SD
SDZ, SDRO1
Relay
SD, SDZ
SDRO1
Leader Cable (Non-sensing)
Length
SD, SDRO1
SDZ
Connector
SD, SDRO1
SDZ
Operating Environment
Temperature
Humidity
Altitude
Storage Environment -4° to 158°F (-20° to 70°C)
Dimensions 1.55”W x 2.0”H x 1.0”D (39.37mmW x 50.8mmH x 25.4mmD)
Weight
SD
SDZ
SDRO1
Certifications CE; RoHS compliant
N/A
24VAC/VDC ± 10%, 0.1A max.; requires power supply: WA-DC-24 or WA-DC-24-ST (not included)
12-36VAC @ 0.01A min., 0.1A max.; 18-36VDC @ 0.01A min., 0.1A max.
N/A
N/A
Dry Contact, Form C; 1A @ 24VDC, 0.5A resistive @ 120VAC
14ft (4.27m)
10in (0.25m); quantity 2
N/A
1 Male, 1 Female; 4 pin, 0.96in (24.38mm) diameter; connects to SeaHawk SC Cable or Non-Sensing Cable
32° to 122°F (0° to 50°C)
5% to 95% RH, non-condensing
15,000ft (4,572m) max.
4 oz. (113g)
3 oz. (85g)
7 oz. (198g)
S D S D - Z S D - R O 1
FORT COLLINS CO
970 484-6510
970 484-6650 FAX
WWW.RLETECH.COM
©2008 RLE Technologies 110055 Rev 2.3 (07/2008)
lthough the information contained in this document is believed to be accurate and correct, RLE Technologies assumes no responsibility, and disclaims
all liability, for any damages resulting from the use of this information or any error or omission in this document. RLE Technologies does not warrant,
guarantee, or make any representations as to the performance, fitness for use, safety, or reliability of any existing or future wiring, equipment, additions
or modifications to equipment, or any other component of the original or modified system.