Veris PXR Installation Instructions

TM
PXR PXR
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
ENVIRONMENTAL SENSORS
Local Display
PXR
L = LCD Display X = No Display
NIST
N = NIST X = None
3.1”
(78 mm)
Range
01 = 0-1”W.C./0-250Pa 02 = 0-10”W.C./0-2.500k Pa
Response
S
= Selectable
INSTALLATION GUIDE
Digital Pressure Transducer
Dry Media
Installer’s Specifications
Media Compatibilit y Dry air or inert gas Input Power 12-30VDC, or 24VAC nominal; 2-wire: 20mA max.; 3-wire: 30mA max. Output Field-selectable: 2-wire, loop-powered 4-20mA (DC only, clipped and capped), or 3-wire 0-5V/0-10V*
Pressure Ran ges:
PXR: 01 Unidirec tional: 0.1/0.25/0.5/1.0” W.C. F.S., switch selectable Bidirectional: ±0.1/±0.25/±0.5/±1.0” W.C. F.S., switch selec table Unidirectional: 25 Pa/50 Pa/100 Pa/250 Pa, F.S., switch sele ctable Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, F.S., switch selectable PXR: 02 Unidirec tional: 1.0/2.5/5.0/10” W.C. F.S., switch selec table Bidirectional: ±1.0/±2.5/±5.0/±10” W.C. F.S., switch selectable Unidirectional: 0.250 kPa/0.500 kPa/1.000 kPa/2.500 kPa, F.S., switch selec table Bidirectional: ±0.250 kPa/±0.500 kPa/±1.000 kPa/±2.500 kPa, F.S., switch selec table Response Time Standard: T95 in 20 sec, Fast: T95 in 2 se c, jumper selectable Mode Unidirectional or bidirectional, jumper selectable Display (option) Signed 3½ digit LCD, indicates pressure, overrange indicator Proof Pressure 3 psid (20.6 kPa) Burst Pressure 5 psid (34.5 kPa) Accuracy ±1% F.S. of selected range (combined linearity and hysteresis) Temperature Eect 1” (250 Pa) range: 0.05%/°C; 10” (2.5 kPa) range: 0.01%/°C (Relative to 25°C) 0° to 50°C (32° to 122°F) Zero Drif t (1-year) 1” (250 Pa) range: 2.0% max.; 10” (2.5 kPa) range: 0.5% max. Zero Adjust Pushbutton auto-zero and digital input (2-pos terminal block) Operating Environment 0° to 60°C (32° to 140°F); 0 to 90% RH non-condensing Fittings Barb, 0.205” (5.2 mm) and 0.125” (3.2 mm) o.d.
EMC Conformance: Emissions EN 61000-6-3:2007 and A1:2011 Class B. Radiated Immu nity EN 61000-4-3:2008; Conducted Immunity EN61000-4-6:2008; EFT EN61000-4-4:2004; Magnetic Field Immunity EN61000-4-8:2001. EMC Special Note: Connect this produc t to a DC distribution network or an AC/DC powe r adaptor with proper surge protection (EN 61000-6-1:2007 specication requirements).
* Minimum input voltage for 4 -20 mA operation: 250 Ω loop = 13 VDC; 500 Ω loop = 19 VDC
Note: If using thi s device with a Siemens Un iversal input contro ller in mA mode, contact Veris Tech nical Support for a pplication assista nce.
2.5 “
(63 mm)
2.9 “
(72 mm)
QUICK INSTALL
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
1. Mount the PXR onto DIN rail.
2. Congure the tubing for dierential or static pressure monitoring.
2.5 “
(63 mm)
3. Wire the PXR.
4. Congure the jumpers for operation.
Z206317-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09123
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
PXR
OPERATION
PX Series devices employ ceramic capacitive sensors and sophisticated temperature compensation circuitry to achieve accurate pressure readings in dry media applications. For best results, allow an initial warm-up period to ensure accuracy at the lowest pressure ranges.
The PXR has a ZERO pushbutton to reset the output and display to zero pressure. Press and hold the ZERO pushbutton for 2 seconds or provide contact closure on the “AUX ZERO” terminal. To protect the unit from accidental zero, this feature is enabled only when the detected pressure is within about 0.1 in. W.C. (25 Pa) of the factory calibration. The optional LCD displays the current reading and the selec ted units. “SET” appears each time a selection is made. “OVER” appears when the measured pressure is over the device’s range.
INSTALLATION
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
Disconnect power to the panel.
1. Select a location in the panel, near the area to be monitored. Mount the PXR onto DIN Rail.
INSTALLATION GUIDE
Wire the PXR: connect the transmitter to the control system and the power supply as indicated below. Optional: Connect the ZERO terminals to the digital output (contact closure) of the control system.
2-wire, 4-20 mA
ZERO
WARNING: Do not apply power to output terminal! Permanent damage will result.
Digital
Output
DIGITAL CONTROL
Return
POWER (4-20mA)
OUT (0-10v)
V+
3-wire, 0-5 V/0-10 V
1.000
ZERO
COM
mA
7
6
5
OUTPUT
RESPONSE
FAST/STD
JP8
UNITS
IN W.C./PA
0
1
JP7
2
MODE
3
4
BI/UNI
JP5
VOLT
5V/10V
Volt
JP4
2. Determine the length of tubing needed for dierential or static pressure. Congure as shown:
High Port
Low Port
Static
Pressure
(low port)
AIR FLOW
Differ-
ential
Pressure (high and low ports)
FILTER
AIR FLOW
HIGH
LOW
Digital
Output
DIGITAL CONTROL
V IN
POWER SOURCE
24VAC/DC
ZERO
1.000
0
7
6
5
ZERO
POWER (4-20mA)
OUT (0-10v)
COM
mA
OUTPUT
-
-
+
RESPONSE
FAST/STD
JP8
UNITS
IN W.C./PA
1
JP7
2
3
4
MODE
BI/UNI
JP5
VOLT
5V/10V
Volt
JP4
3.
Z206317-0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09123
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.