PW2 SERIES
Wet Media Differential
Pressure Transducer
VERIS INDUSTRIES
4-20 mA, 2-Wire Device
DESCRIPTION
The PW2 Series 2-wire, 4-20mA wet/wet pressure transducers incorporate
microprocessor proled sensors for exceptional accuracy and reliability. Easy to use
and designed to provide exceptional installation savings, the PW2 Series is ideal for
measuring pressure across pumps, lters, heat exchangers, compressors, and other
non-corrosive wet media applications.
Output Clamping
F.S.
Noise Rejection
PRESSURE
Surge Damping
0
Actual Pressure
Digitally Conditioned Output
PRESSURE
Microproce ssor provides digita l signal condition ing
● Noise rejection reduces uctuating readings due to noise or turbulence
● Surge damping prevents false alarms by averaging fast peaks
TIME
PW2
APPLICATIONS
● Monitoring and controlling pump dierential pressure
● Chiller/boiler dierential pressure drop
● CW/HW system dierential pressure
FEATURES
● The jumper-selectable output switch for normal (4-20mA) or reverse
(20-4mA) operation provides application exibility
● Rugged, die-cast enclosure provides NEMA 4 sealing
● Selectable dierential units: psid or bard
● Dual sensor design for improved overpressure tolerance... eliminates
the requirement for a bypass valve assembly in most applications
● Jumper-controlled electronic surge dampening for high stability
● Pushbutton zero calibration – no trim pots to adjust......maintain
accuracy and prevent callbacks with automatic zero calibration
● Jumper-selectable port swap feature eliminates costly replumbing when
the high and low ports are improperly plumbed...change the jumper
position from normal to swap – problem solved!
● Switch-selectable pressure ranges...fewer models to order and stock
● LCD displays high pressure, low pressure, and dierential pressure
with easy readability
Year
5
SPECIFICATIONS
Input Power 12 to 24VDC, loop powered
Maximum Current Draw 29mA
Output 2-wire transmitter; user s electable 4-20mA (clipped and c apped) †
Accurac y @ 25°C* Range A, B, C: ±1% F.S.; Range D: ±2% F.S.**
Surge Damping Electronic; 5-second averaging
Pressure Ranges (Selectable):
0-50 psi (0-3.45 bar) 0-5/10/25/50 psid (0-0.34/0.69/1.72/3.45 bard)
0-100 psi (0-6.89 bar) 0-10/20/50/100 psid (0- 0.69/1.38/3.45/6 .89 bard )
0-250 psi (0-17.24 bar) 0-25/50/125/250 psid (0-1.72/3.45/8.62/17.24 bard)
Product Operating Environment -10° to 55°C (14° to 130°F); 0 to 90%RH noncondensing
Long Term Stability ±0.25% pe r year
Zero Adjust Pushbutton auto-zero
Housing Material White powder-coated aluminum
Sensor:
Media Compatibility Media compatible with 17-4 PH stainless steel
Proof Pressure Max. 2x F.S. range
Burst Pressure Max. 5x F.S. range
Temperature Compensated Range 0° to 50°C (32° to 122°F); TC Zero <±1.5% of product F.S. per sensor ; TC Span<±1.5% of produc t F.S. per sensor, (2 sensors per unit)
Media Temperature Limits -20° to 85°C (-4° to 185°F); 0 to 90% RH non-condensing
Fittin gs 1/8" NPT female thread, 17-4 PH stainless
† Minimum inp ut voltage: 250 Ω loop = 12VDC; 50 0 Ω loop = 17VDC
* Accuracy combine s linearity, hysteresis, and repe atability. ** FS is den ed as full span of selected ra nge in bi-directio nal mode.
EMC Conformance: Low voltag e directive 2006/95/EC; EMC directive 2004/108/EC.
EMC Special Note: Conne ct this product to a DC dist ribution network or a n AC/DC power adaptor with pro per surge protection (EN 61000-6 -1:2007 specication req uirements).
800.354.8556
Warranty
+1 503.598.4564
www.veris.com
HQ0001832.B 01131
800.354.8556
+1 503.598.4564
APPLICATION/WIRING DIAGRAM
www.veris.com
Polarity
Insensitive
REMOTE
4-20mA
ZERO
POWER SOURCE
12 to 24 VDC
4-20mA IN
DIGITAL CONTROL
Digital Output
DIMENSIONAL DRAWING
ZERO
A-High
B-Mid High
C-Mid Low
D-Low
Pressure
Range
Model
PW2-03
PW2-04
PW2-05
Model
PW2-03
PW2-04
PW2-05
Port Swap/Norm
Bi-Dr/Normal
Slow Avg/Fast Norm
Analog Rev/Norm
Bar/PSI
Settings
Default Settings in bold.
Insert jumper to activate
other features.
A
50
100
250
A
3.45
6.89
17.24
1.72
3.45
8.62
Range (psi)
B
25
50
125
Range (bar)
B
C
10
20
50
C
0.69
1.38
3.45
D
5
10
25
D
0.34
0.69
1.72
Bidirectional Operation
Input Conditions Result Outputs Read
HI PORT
100 psi
100 psi
50 psi
50 psi
0 psi
LO PORT
0 psi
50 psi
50 psi
100 psi
100 psi
DP
+100 psi
+50 psi
0 psi
-50 psi
-100 psi
4-20mA
20mA
16mA
12mA
8mA
4mA
WET DIFFERENTIAL PRESSURE
5.8"
(147 mm)
LOW
ORDERING INFORMATION
Local Display
PW2
L = LCD Display
X = No Display
Example:
PW2 L X 04 C
NIST
N = NIST
X = None
Operational Range
03 = 0-50 psi/ 3.45 bar
04 = 0-100 psi/6.89 bar
05 = 0-250 psi/17.24 bar
HIGH
2.2"
(57 mm)
pressure
4"
(102 mm)
Available
1
US or EU
S = Standard
C = CE
ACCESSORIES
Bypass Valve assemblies (AA14A)
PW installed on bypass valve manifold (AA16A)
Snubbers (AA11, AA12), steam siphon (AA13)
AA11
AA13
AA14A
1
Select operational range according to maximum gauge pressure, NOT dierential pressure.
Example: High gauge pressure=90 psig, Select 100 psig model (04).
HQ0001832.B 01131