Veris PW2 Datasheet

PW2 SERIES
Wet Media Differential Pressure Transducer
VERIS INDUSTRIES
4-20 mA, 2-Wire Device
The PW2 Series 2-wire, 4-20mA wet/wet pressure transducers incorporate microprocessor proled sensors for exceptional accuracy and reliability. Easy to use and designed to provide exceptional installation savings, the PW2 Series is ideal for measuring pressure across pumps, lters, heat exchangers, compressors, and other non-corrosive wet media applications.
Output Clamping
F.S.
Noise Rejection
PRESSURE
Surge Damping
0
Actual Pressure Digitally Conditioned Output
PRESSURE
Microproce ssor provides digita l signal condition ing
Noise rejection reduces uctuating readings due to noise or turbulence
Surge damping prevents false alarms by averaging fast peaks
TIME
PW2
APPLICATIONS
Monitoring and controlling pump dierential pressure
Chiller/boiler dierential pressure drop
CW/HW system dierential pressure
FEATURES
The jumper-selectable output switch for normal (4-20mA) or reverse
(20-4mA) operation provides application exibility
Rugged, die-cast enclosure provides NEMA 4 sealing
Selectable dierential units: psid or bard
Dual sensor design for improved overpressure tolerance... eliminates
the requirement for a bypass valve assembly in most applications
Jumper-controlled electronic surge dampening for high stability
Pushbutton zero calibration – no trim pots to adjust......maintain
accuracy and prevent callbacks with automatic zero calibration
Jumper-selectable port swap feature eliminates costly replumbing when
the high and low ports are improperly plumbed...change the jumper position from normal to swap – problem solved!
Switch-selectable pressure ranges...fewer models to order and stock
LCD displays high pressure, low pressure, and dierential pressure
with easy readability
Year
5
SPECIFICATIONS
Input Power 12 to 24VDC, loop powered Maximum Current Draw 29mA Output 2-wire transmitter; user s electable 4-20mA (clipped and c apped) † Accurac y @ 25°C* Range A, B, C: ±1% F.S.; Range D: ±2% F.S.** Surge Damping Electronic; 5-second averaging
Pressure Ranges (Selectable):
0-50 psi (0-3.45 bar) 0-5/10/25/50 psid (0-0.34/0.69/1.72/3.45 bard) 0-100 psi (0-6.89 bar) 0-10/20/50/100 psid (0- 0.69/1.38/3.45/6 .89 bard ) 0-250 psi (0-17.24 bar) 0-25/50/125/250 psid (0-1.72/3.45/8.62/17.24 bard) Product Operating Environment -10° to 55°C (14° to 130°F); 0 to 90%RH noncondensing Long Term Stability ±0.25% pe r year Zero Adjust Pushbutton auto-zero Housing Material White powder-coated aluminum
Sensor:
Media Compatibility Media compatible with 17-4 PH stainless steel Proof Pressure Max. 2x F.S. range Burst Pressure Max. 5x F.S. range Temperature Compensated Range 0° to 50°C (32° to 122°F); TC Zero <±1.5% of product F.S. per sensor ; TC Span<±1.5% of produc t F.S. per sensor, (2 sensors per unit) Media Temperature Limits -20° to 85°C (-4° to 185°F); 0 to 90% RH non-condensing Fittin gs 1/8" NPT female thread, 17-4 PH stainless
† Minimum inp ut voltage: 250 Ω loop = 12VDC; 50 0 Ω loop = 17VDC * Accuracy combine s linearity, hysteresis, and repe atability. ** FS is den ed as full span of selected ra nge in bi-directio nal mode. EMC Conformance: Low voltag e directive 2006/95/EC; EMC directive 2004/108/EC. EMC Special Note: Conne ct this product to a DC dist ribution network or a n AC/DC power adaptor with pro per surge protection (EN 61000-6 -1:2007 specication req uirements).
800.354.8556
Warranty
+1 503.598.4564
www.veris.com
HQ0001832.B 01131
800.354.8556
+1 503.598.4564
APPLICATION/WIRING DIAGRAM
www.veris.com
Polarity
Insensitive
REMOTE
4-20mA
ZERO
POWER SOURCE
12 to 24 VDC
4-20mA IN
DIGITAL CONTROL
Digital Output
DIMENSIONAL DRAWING
ZERO
A-High B-Mid High C-Mid Low D-Low
Pressure Range
Model PW2-03 PW2-04 PW2-05
Model PW2-03 PW2-04 PW2-05
Port Swap/Norm Bi-Dr/Normal Slow Avg/Fast Norm Analog Rev/Norm Bar/PSI
Settings
Default Settings in bold. Insert jumper to activate other features.
A
50
100 250
A
3.45
6.89
17.24
1.72
3.45
8.62
Range (psi)
B 25 50
125
Range (bar)
B
C 10 20 50
C
0.69
1.38
3.45
D
5 10 25
D
0.34
0.69
1.72
Bidirectional Operation
Input Conditions Result Outputs Read
HI PORT
100 psi 100 psi 50 psi 50 psi 0 psi
LO PORT
0 psi 50 psi 50 psi 100 psi 100 psi
DP
+100 psi +50 psi 0 psi
-50 psi
-100 psi
4-20mA
20mA 16mA 12mA 8mA 4mA
WET DIFFERENTIAL PRESSURE
5.8"
(147 mm)
LOW
ORDERING INFORMATION
Local Display
PW2
L = LCD Display X = No Display
Example:
PW2 L X 04 C
NIST
N = NIST X = None
Operational Range
03 = 0-50 psi/ 3.45 bar 04 = 0-100 psi/6.89 bar 05 = 0-250 psi/17.24 bar
HIGH
2.2"
(57 mm)
pressure
4"
(102 mm)
Available
1
US or EU
S = Standard C = CE
ACCESSORIES
Bypass Valve assemblies (AA14A) PW installed on bypass valve manifold (AA16A) Snubbers (AA11, AA12), steam siphon (AA13)
AA11
AA13
AA14A
1
Select operational range according to maximum gauge pressure, NOT dierential pressure.
Example: High gauge pressure=90 psig, Select 100 psig model (04).
HQ0001832.B 01131
Loading...