Veris PW2 Installation Instructions

VERIS INDUSTRIES
environmental SenSorS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
2.2"
(57 mm)
4"
(102 mm)
5.8"
(147 mm)
LOW HIGH
WET DIFFERENTIAL PRESSURE
inStallation GUiDe
PW2 SerieS PW2 SerieS
Wet Media Differential Pressure Transducer
Installer's Specifications
Media Compatibility 17-4 PH stainless steel Input Power 12 to 24VDC, 29mA max.; loop powered Output 2-wire transmitter; 4-20mA (clipped and cappe d)
Pressure Ranges:
0-50 psi (0-3.45 bar) 5/10/25/50 psid (0-0.34/0.69/1.72/3.45 bar) 0-100 psi (0-6.89 bar) 10/20/50/100 psid (0-0.69/1.38/3.45/6.89 bar) 0-250 (0-17.24 bar) 25/50/125/250 psid (0-1.72/3.45/8.62/17.24 bar) Proof Pressure 2x max. F.S. range Burst Pre ssure 5x max. F.S. range Accuracy at 2 5°C* Ranges A, B, C: ±1% F.S.**
available
Range D: ±2% F.S.** Surge Damping Electronic; 5-second averaging Temperature Compensated Range 0° to 50°C (32° to 122°F); TC Zero <1.5% of product F.S. per sensor; TC Span <1.5% of product F.S. per sensor Sensor Operating Range -20° to 85°C (-4° to 185°F) Long Term Stability ±0.25% per year Zero Adjust Pushbutton auto-zero Operating Environment -10° to 55°C (14° to 131°F); 10-90% RH noncondensing Fittings 1/8” NPT female, stainless steel 17-4 PH Physical White powder-coated aluminum
ProDuct iDentification
Local Display
PW2
L = LCD Display
X = No Display
* IMPORTANT! Select operationa l range according to maximum gauge p ressure, NOT d ifferential pressure. Example: High gauge p ressure=90 psig, Select 100 psig model (04).
NIST
Operational Range
N = NIST
X = None
*
03 = 0-50 psig
04 = 0-100 psig
05 = 0-250 psig
US or EU
S = Standard
C = CE
Dimensions
To conform to EMC Standards, use shielded cabling. Technical information is avai lable from the factory on request o r on our website (www.veris.com/ce)
* Accuracy combines linearit y, hys teresis, and repeatabilit y. ** F.S. is defined as full span of selected rang e in bidirectional mode.
The PW2 Series sensor is designed to accept high differential pressure. Install the sensor on a duct or pipe across a pump, filter, heat exchanger, compressor, or other non-corrosive wet media. The dual sensor design eliminates the need for a bypass valve, and the bi-directional capability reduces installation errors. A pushbutton allows easy zero adjustment.
Mount sensor on a duct or pipe, across the pump, filter, or other pressure 1.
differential.
Wire as shown (see page 2).2.
Configure the jumpers (see page 2).3.
Z204201-0G PAGE 1 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08102
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
VERIS INDUSTRIES
DIGITAL CONTROL
Digital Output
4-20mA IN
POWER SOURCE
12 to 24 VDC
Port Swap/Norm Bi-Dr/Normal Slow Avg/Fast Norm Analog Rev/Norm Bar/PSI
ZERO
A-High B-Mid High C-Mid Low D-Low
REMOTE
ZERO
4-20mA
Pressure Range
Settings
Polarity
Insensitive
Default Settings in bold. Insert jumper to activate other features.
Model PW2-03 PW2-04 PW2-05
A
50
100 250
B 25 50
125
C 10 20 50
D
5 10 25
Model PW2-03 PW2-04 PW2-05
A
3.45
6.89
17.24
B
1.72
3.45
8.62
C
0.69
1.38
3.45
D
0.34
0.69
1.72
Range (PSI)
Range (bar)
HI PORT
100 psi 100 psi 50 psi 50 psi 0 psi
LO PORT
0 psi 50 psi 50 psi 100 psi 100 psi
4-20mA
+100 psi +50 psi 0 psi
-50 psi
-100 psi
Bidirectional Operation
Input Conditions Result Outputs Read
DP
20mA 16mA 12mA 8mA 4mA
Wiring
Note: Use of a
housing grounding
screw is required
for CE applications
PW2 SerieS
inStallation GUiDe
Output is mA only. Example: PW2-04
Optional: Connect Zero terminals to digital output (contact closure) of control system.
Caution: Zero input is for dry-contact only. Do not apply voltage to the Zero terminals.
configuration
Jumper Notes
Port Swap/Norm Reverses polarity of the pressure ports (i.e. makes the LO port
Bi-Dr/Normal Normal: 0 to F.S. pressure
Slow Avg/Fast Norm Slow mode provides 5 second averaging for surge damping.
Analog Rev/Norm Normal: output increases as pressure increases;
Bar/PSI Select output units.
oPeration
Auto-Zero: Press and hold the Zero button for 2 seconds or provide contact closure on the auxiliary ‘Remote Zero’ terminal to reset the output to zero pressure. To protect the device from accidental zeroing, this feature is only enabled when the detected pressure is within 5% of fac tory calibration.
Z204201-0G PAGE 2 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08102
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
operate as the HI port and vice versa); used when the sensor is incorrectly plumbed.
Bidirectional: -F.S. pressure to +F.S. pressure; output reads ½ when
pressure is zero.
Reverse: output is maximum when pressure differential is zero and
decreases as pressure increases.
Range: Use the Range switch to select F.S. differential pressure.