SC, SC-C, SC-H, & NSC
VERIS INDUSTRIES
Cables
Highly Flexible, Resists Bends
and Kinks, Abrasion Resistant
DESCRIPTION
Sensing and non-sensing cables are designed for use with Zone and Distance Read
panels. The sensing cables detect the presence of liquid, and send a signal to the
panel. The panel generates an alarm and pinpoints the exact location of the leak or
spill along the cable’s length. Sensing cables are designed for the highest accuracy
and maximum reliability.
SC water detection cable senses the presence of water or other conductive uid. SC-C
chemical sensing cable detects the presence of chemicals (see Specications for list).
SC-H hydrocarbon sensing cable locates hydrocarbons within 1 foot (0.33 m) of the
actual leak, with as little as 2 inches (51 mm) of wetted cable, and is impervious to
the presence of water.
NSC non-sensing cable is used to extend the control panel’s leader cable to an area
where SC detection cable is needed. It also bridges lengths of SC detection cable in
areas where sensing is not required. Invisible to the control panel, the non-sensing
cable does not aect the accuracy of readings or limit the amount of water detection
cable that can be connected to a control panel. NSC cables are only compatible with
LEAK DETECTION
systems using SC water detection cables.
SC- H
SC- C
NSC
SC
FEATURES
● Strong, durable, and abrasion resistant
● Expansion with mating end connectors...easy installation
● Available in pre-measured and custom lengths with pre-installed end
connectors...installation exibility
● Plenum rated and UL listed
● Highly accurate alarm notication...no false alarms
● SC, SC-C, and SC-H cables detect the presence of specic uids...application
versatility
All cables are highly exible, durable, and kink-resistant. They lie at after
installation, and they are abrasion resistant. The cables are plenum rated and UL
listed making them ideal for use under raised oors and areas where plenum rated
cable is required. Choose a pre-specied cable length or a custom length for your
convenience and installation exibility.
SPECIFICATIONS
Plenum Rating SC: CL2P/CMP C(UL); NSC: CL3P/CMP C(UL) California State Fire Mar shall approved
Shear Strength SC/NSC: >180 lbs (>81.65 kg); SC-C: 160 lb (72.6 kg)
Cut Through Resistance SC/NSC: >40 lbs (>18.2 kg) with 0.005” (0.13 mm) blade; SC-C: >50 lbs (>27.7 kg) with 0.005” (0.13 mm) blade
Abrasion Resistance SC/NSC: 60 cycles per UL 719; SC-C : >65 cycles per UL719
Connector SC/NSC: 4 pin, 1” (25.4 mm) diameter, circular, locking, 4 pin; S C-C: 0.5” (13 mm) diameter
Operating Environment:
Temperature SC/NSC: 0° to 75°C (32° to 167°F); SC-C: 90°C (194°F) max.; SC- H: -20° to 90°C (-4° to 140°F)
Humidity SC/NSC: 5% to 95% RH non-condensing
Altitude SC/NSC: 10,000 ft. (3,048 m) max.
Storage Environment SC: -30° to 85°C (-22° to 185°F); NSC: 0° to 75°C (32° to 167°F)
Standard Lengths:
SC -10/ NSC -10 10 ft. (3.1 m)
SC-2 5/NS C-25 25 ft. (7.7 m)
SC-50/N SC-50 50 ft. (15.3 m)
SC-100/NSC-100 100 ft. (30.5 m)
Weigh t 0.02 lbs/ft (29.7 g/m)
Chemical Resistance, SC-C* In accordance with ASTM D543, cable functions normally after seven days’ ex posure to the following:
Fresh deionized water, tap water, sulfuric acid (98%), sulfuric acid (50%), hydrochloric acid (37%),
sodium hydroxide (10%), aqua regia, ethylene glycol (60% in DI water)
Chemical Resistance, SC-H* In accordance with ASTM D543, cable functions normally after seven days’ ex posure to the following:
Unleaded gasoline, #1 diesel fuel, #2 diesel fuel, JP5 jet f uel, JP8 jet fuel, Jet-A jet fuel, x ylene, kerosene, cigaret te lighter fuel (completely water resistant)
Agency Approvals SC: CE; UL E162948; RoHS compliant
NSC: UL E118871; UL 13, power limited circuit cable; UL 4 44, communication cables; NFPA 262; plenum ame test (UL 910); NEC Articles 725 and 800; RoHS compliant
* Prolonged exposure to concentrated ketones may cause temporary reduction of sensitivity; call for details.
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001799.B 011 31
800.354.8556
+1 503.598.4564
DIMENSIONAL DRAWINGS
1”
(25.4mm)
Not > 0.25”
(6.4mm)
www.veris.com
1”
(25.4mm)
NSCSC
0.13”
(3.3mm)
0.51”
(13 mm)
10’, 25’, 50’, or 100’
(3.1m, 7.7m, 15.3m, or 30.5m)
SC- C
Not > 0.25”
(6.4 mm)
3’, 10’, 17’, 25’, 50’, or 100’
(0.9 m, 3.1 m, 5.2 m, 7.7 m, 15.3 m, or 30.5 m)
0.51”
(13 mm)
10’, 25’, 50’, or 100’
(3.1m, 7.7m, 15.3m, or 30.5m)
SC- H
Not > 0.32”
(8.1 mm)
3’, 10’, 17’, 25’, 50’, or 100’
(0.9 m, 3.1 m, 5.2 m, 7.7 m, 15.3 m, or 30.5 m)
ORDERING INFORMATION
Sensing Cable
MODEL MANUF. PART # DESCRIPTION
U006-0009 SC-10 Sensing Cable, Water, 10 feet
U001-0048 SC-17 Sensing Cable, Water, 17 ft
U006-0013 SC-25 Sensing Cable, Water, 25 feet
U006-0014 SC-50 Sensing Cable, Water, 50 feet
U006-0010 SC-100 Sensing Cable, Water, 100 feet
U006-0011* SC-1000* Sensing Cable, Water, 1000 feet, bulk
U006-0012* SC-2000* Sensing Cable, Water, 2000 feet, bulk
U006-0049 SC-C-3 Sensing Cable, Chemical, 3 ft
U006-0050 SC-C-10 Sensing Cable, Chemical, 10 ft
U006-0051 SC-C-17 Sensing Cable, Chemical, 17 ft
U006-0052 SC-C-25 Sensing Cable, Chemical, 25 ft
U006-0053 SC-C-50 Sensing Cable, Chemical, 50 ft
U006-0054 SC-C-100 Sensing Cable, Chemical, 100 ft
U006-0055 SC-H-3 S ensing Cable, Hydrocarbons, 3 ft
U006-0056 SC-H-10 Sensing Cable, Hydrocarbons, 10 ft
U006-0057 SC-H-17 Sensing Cable, Hydrocarbons, 17 ft
U006-0058 SC-H-25 Sensing Cable, Hydrocarbons, 25 ft
U006-0059 SC-H-50 Sensing Cable, Hydrocarbons, 50 ft
U006-0060 SC-H-100 Sensing Cable, Hydrocarbons, 100 ft
Non-sensing Cable
MODEL MANUF. PART # DESCRIPTION
U006-0017 NSC-10 Non-Sensing Cable, 10 feet
U006-0021 NSC-25 Non-Sensing Cable, 25 feet
U006-0022 NSC-50 Non-Sensing Cable, 50 feet
U006-0018 NSC-100 Non-Sensing Cable, 100 feet
U006-0019* NSC-1000* Non-Sensing Cable, 1000 feet, bulk
U006-0020* NSC-2000* Non-Sensing Cable, 2000 feet, bulk
* CPCE (U006-0039), SPSL (U006-0040), and SCCS (U006-0041) tools are required
for installation. LCDE (U006-0029) is highly recommended.
LEAK DETECTION
HQ0001799.B 011 31