MSCD2000D
TM
OCCUPANCY SENSORS
INSTALLATION GUIDE
MSC SerieS MSC SerieS
Ceiling Mounted Occupancy Sensors
Installer’s Specifications
Input Voltage 24 VDC
Current Consumption @ 24 VDC:
MSCP1000
MSCU2000
PIR 21 mA nominal
Ultrasonic 34 mA nominal
Dual 37 mA nominal
Isolated Relay Contact rating: 1A @ 24 VDC resistive
Operating Temperature Range 0° to 50°C (32° to 122°F)
Operating Humidity Range Max. 90% RH non-condensing
Agency Approvals UL and cUL listed; FCC part 15 for home and oce use (Class B)
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
Sensing Technology
MSC
U = Ultrasonic
D = Dual (PIR + Ultr asonic)
P= Passive In frared (PIR)
COVERAGE FEATURES
Model MSCP1000 MSCU2000 MSCD2000
Technology PIR Ultrasonic Dual
Coverage area 1000 sq. ft. 2000 sq. ft. 2000 sq. ft.
Field of view 360°
Ambient light level sensing 0.5 to 250 foot candles
Adjustable time delay 15 sec. to 30 min.
Adjustable sensitivity 600 to 1000 sq. ft.
Isolated relay Form C contacts for Class 2 signaling
LED motion indicators 1 (red) 1 (red) 2 (red/green)
Coverage
1000 = 1000 Sq . Ft. (Passive Infared o nly)
2000 = 200 0 Sq. Ft. (Ultrason ic or Dual technolog y only)
(60% to 100% of
max. coverage
200 to 2000 sq. ft.
(10% to 100% of
max. coverage)
200 to 2000 sq. ft.
(10% to 100% of
max. coverage)
OPERATION
MSC ceiling-mounted occupancy sensors are ideal for use in business and oce
environments to accurately detect occupancy and automatically control lighting. The
ceiling-mount design allows the greatest possible motion sensitivity. An adjustment
panel is on the front of the sensor provides easy access to controls after the sensor is
installed.
COVERAGE PATTERNS
For a 9 ft. ceiling
PIR
25 ft
(7.7m)
32 ft
(9.8m)
Minor Motion
Major Motion
Dual Technology
Ultrasonic
30 ft
(9.2m)
48 ft
(14.7m)
Minor Motion
Major Motion
24 ft
(7.4m)
42 ft
(12.8m)
Ultrasonic Major Motion
Ultrasonic Minor Motion
PIR Major Motion
PIR Minor Motion
ZL0030-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
MSC SERIES
INSTALLATION GUIDE
DIMENSIONS
4.6”
(117mm)
MSCU: 1.4” (36mm)
MSCD/MSCP: 1.8” (46mm)
INSTALLATION
Choose a location at least ve feet from air ow sources (HVAC vents, fans, etc.). Three
mounting options are available.
Mounting to a Junction Box
Junction Box
#8 x 32 screw
Mounting Adapter Plate
Keyhole Pin
Rotate Clockwise
1. Turn o the circuit breaker supplying power to the sensor’s power pack.
2. Attach the adapter plate to a standard 4-in. ceiling junction box using the two #8 x
32 screws supplied.
3. Wire the sensor (see Wiring section). Follow applicable national and local electrical
codes.
4. Attach the sensor to the adapter plate by inserting the pins on the adapter plate
into the keyholes on the back of the sensor. Rotate the sensor clockwise until it
locks in place.
Flush Mounting
Mounting with Supplied Mounting Post
Lock Nut
Mounting post
1. Turn o the circuit breaker supplying power to the sensor’s power pack.
2. Drill a 7/8” diameter hole at the mounting location. Note: For acoustical tile, use
the threaded mounting post to drill the mounting hole. Press the cutter end of the
post rmly against the tile and twist the post into the tile.
3. Feed sensor wire through the mounting post, then twist and lock the mounting
post to the back of the sensor.
4. Insert the mounting post into the hole drilled in step 2. Secure the sensor
assembly away from the top of the ceiling tile using the supplied washer and lock
nut.
5. Wire the sensor (see Wiring section). Follow applicable national and local electrical
codes.
Washer
Ceiling tile
Ceiling
Mounting Adapter Plate
Mounting Screw
Keyhole Pin
Rotate Clockwise
1. Turn o the circuit breaker supplying power to the sensor’s power pack.
2. Drill a hole large enough to accomodate wiring at the mounting location.
3. Attach the adapter plate to the ceiling using a secure method, such as with screws
and wall anchors (not provided).
4. Wire the sensor (see Wiring section). Follow applicable national and local electrical
codes.
5. Attach the sensor to the adapter plate by inserting the pins on the adapter plate
into the keyholes on the back of the sensor. Rotate the sensor until it locks in
place.
Black
Orange (N.O.)
Class 2
Red
Blue
Contact rating:
1A @ 24 Vdc Resistive
Yellow (Common)
Green (N.C.)
Blue
Black
Additional
Sensor(s)
(optional)
Red
WIRING
Class 1
Hot
Neutral
Black
White
Load
Red
Red
Blue
Black
Power Pack
AA47
ZL0030-0C PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.