LD1500 & LD2100
Distance Read Panel
VERIS INDUSTRIES
Helps Eliminate High
LD2100
Humidity False Alarms
DESCRIPTION
Together with our SC, SC-C, or SC-H sensing cable, the LD1500 and LD2100 panels
detect and report the presence and exact location of the cable-specic uid. When
the uid comes in contact with the patented cable, the monitoring panel quickly
pinpoints the location of the leak, triggering an alarm and displaying the location.
SPECIFICATIONS
Input Power 24VAC@600mA max., 50/60 Hz; 24VDC@600mA max.
Inputs:
Water Leak Detection Cable Requires 15 ft. (4.5 m) leader cable kit (LC-KIT or LC-KIT-M)
Maximum Length 1500 ft. (457 m); LD2100: 20 00 ft. (609 m)
Detection Accuracy ± 2 ft (0.6 m) + 0.5% of the cable length
Detection Repeatability ± 2 ft (0.6 m) + 0.25% of the cable length
LEAK DETECTION
Detection Response Time 5-995 sec ± 2 sec
Outputs:
Relay (LD2100 only) 1A@24VDC, 0.5A re sistive@120VAC
Communications Ports:
RS -232 9600 baud, No parity, 8 data bits, 1 stop bit
RS-485 1200, 2400, 9600, or 19200 baud (selec table); No parity, 8 data bits, 1 stop bit
Protocols:
Terminal Emulation (RS-232) VT100 compatible
Modbus (RS-485) Slave; RTU Mode; Suppor ts function codes 03, 04, 06, and 16; Johnson N2 (LD2100 only)
Expanded Protocols:
TCP/IP, HTML, TFTP IPv4.0
SNMP V1: V2C MIB-2 compliant; NMS Manageable with Get, S et, Traps
SMTP (email, LD2100 only) Support s client authentication (plain and login); compatible with ESMTP s ervers
Modbus TCP/IP Modbus slave; TCP/IP transmission protocol
BACnet/IP ASHRAE Std 135-2004 Annex J
Alarm Notication:
Audible Alarm LD2100: 70 dBA@2 ft. (0.6 m); re-sound congurable (disable d, 0 to 24 hour s, integer values only)
Visual Alarm LD1500: Red, 4-digit; 7 segment LED display; bi-color s tatus LED; LD2100: bi-color status LED
Email (LD1500/LD2100) 4 email recipients; email sent on Alarm and Return to Normal
SNMP Traps (LD1500/LD2100) 4 community strings
Logging Capabilities:
Event Log LD1500: Last 10 events; LD210 0: Last 500 events
Trend Log LD2100: Cable cur rent level every day, for the last 288 days
Login Security :
Display Access 1 Administrator (password for conguration, no password required to view panel status)
Front Panel Interface:
Display LD2100: green alphanumeric dot matrix
Push Buttons LD2100: Test/Rest; LD5200: Up, down, right, left, enter
LED Indicator LD1500: 1 tri-color Power/Status (green = power on; red = alarm; yellow = cable fault; LD2100: 1 bi-color Power/Status (green=power on, red=alarm)
Operating Environment:
Temperature 0° to 50°C (32° to 122°F)
Humidity 5% to 95% RH non-condensing
Altitude 15000 ft. (4572 m) max.
Mounting Vertical wall mount (DIN rail mounting option available on LD2100 only)
Agency Approvals CE; ETL listed: conforms to UL 61010-1, EN 61010-1; CSA C22.2; RoHS compliant,
FEATURES
● Adjustable leak and contamination alarm thresholds to prevent false alarms
due to high humidity...high detection accuracy
● RS-232 port allows conguration with PC
LD1500
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001796.B 0 1131
800.354.8556
Power supply
(PS24-7.5W )
+1 503.598.4564
LD1500/LD2100 Basic SC Installation
www.veris.com
DIMENSIONAL DRAWINGSAPPLICATION/WIRING DIAGRAMS
LD15 00
7.0”
(176 mm)
Power supply
(PS24-7.5W )
Cable
W B G R
Cable
W B G R
Leader Cable (LC-KIT)
(included with LD1500
and LD2100)
Sensing Cable
(SC)
LD1500/LD2100 Basic SC-C Installation
Leader Cable (LC-KIT-M)
(not included with LD1500
and LD2100)
Sensing Cable
(SC-C)
LD1500/LD2100 Basic SC-H Installation
End Terminator (EOL)
(included with LC-KIT)
End Terminator (EOL)
(included with LC-KIT-M)
3.7”
(94 mm)
LD2100
8.0”
(203 mm)
4.25”
(108 mm)
Power supply
(PS24-7.5W )
Cable
W B G R
Leader Cable (LC-KIT-M)
(not included with LD1500
and LD2100)
ORDERING INFORMATION
Sensing Cable
(SC-H)
End Terminator (EOL)
(included with LC-KIT-M)
C
T
N
I
L
LISTED
3037024
R
T
E
E
K
CM
US
D
I
S
E
T
MODEL MANUF. PART # DESCRIPTION
U006-0038* LD1500* Leak Panel, 1500’ Distance Read, Modbus, BACnet, SNMP, SMTP, and relay outputs
U006-0047* LD2100* Leak Panel, 2000’ Distance Read, Modbus, BACnet, SNMP, SMTP, and relay outputs
U006-0035†LC-KIT
U006-0061††LC-KIT-M
U006-0004 FM1114 Reference map, framed (11” x 14”)
* Power supply not included. Use LD-ENC (U006-0045) wall mount enclosure with built-in power supply or Veris PS24-7.5W power supply or equivalent.
†
Included with LD1500 and LD2100.
††
Not included with LD1500 or LD2100. Required for installation of SC-C ad SC-H cables.
†
††
Leader cable kit for SC cables (connects from leak panel to SC or NSC cable)
Leader cable kit for SC-C and SC-H cables (connects from leak panel to SC-C or SC-H cable)
LEAK DETECTION
HQ0001796.B 0 1131