Veris LD2100 Datasheet

LD1500 & LD2100
Distance Read Panel
VERIS INDUSTRIES
Helps Eliminate High
LD2100
Humidity False Alarms
Together with our SC, SC-C, or SC-H sensing cable, the LD1500 and LD2100 panels detect and report the presence and exact location of the cable-specic uid. When the uid comes in contact with the patented cable, the monitoring panel quickly pinpoints the location of the leak, triggering an alarm and displaying the location.
SPECIFICATIONS
Input Power 24VAC@600mA max., 50/60 Hz; 24VDC@600mA max.
Inputs:
Water Leak Detection Cable Requires 15 ft. (4.5 m) leader cable kit (LC-KIT or LC-KIT-M) Maximum Length 1500 ft. (457 m); LD2100: 20 00 ft. (609 m) Detection Accuracy ± 2 ft (0.6 m) + 0.5% of the cable length Detection Repeatability ± 2 ft (0.6 m) + 0.25% of the cable length
LEAK DETECTION
Detection Response Time 5-995 sec ± 2 sec
Outputs:
Relay (LD2100 only) 1A@24VDC, 0.5A re sistive@120VAC
Communications Ports:
RS -232 9600 baud, No parity, 8 data bits, 1 stop bit RS-485 1200, 2400, 9600, or 19200 baud (selec table); No parity, 8 data bits, 1 stop bit
Protocols:
Terminal Emulation (RS-232) VT100 compatible Modbus (RS-485) Slave; RTU Mode; Suppor ts function codes 03, 04, 06, and 16; Johnson N2 (LD2100 only)
Expanded Protocols:
TCP/IP, HTML, TFTP IPv4.0 SNMP V1: V2C MIB-2 compliant; NMS Manageable with Get, S et, Traps SMTP (email, LD2100 only) Support s client authentication (plain and login); compatible with ESMTP s ervers Modbus TCP/IP Modbus slave; TCP/IP transmission protocol BACnet/IP ASHRAE Std 135-2004 Annex J
Alarm Notication:
Audible Alarm LD2100: 70 dBA@2 ft. (0.6 m); re-sound congurable (disable d, 0 to 24 hour s, integer values only) Visual Alarm LD1500: Red, 4-digit; 7 segment LED display; bi-color s tatus LED; LD2100: bi-color status LED Email (LD1500/LD2100) 4 email recipients; email sent on Alarm and Return to Normal SNMP Traps (LD1500/LD2100) 4 community strings
Logging Capabilities:
Event Log LD1500: Last 10 events; LD210 0: Last 500 events Trend Log LD2100: Cable cur rent level every day, for the last 288 days
Login Security :
Display Access 1 Administrator (password for conguration, no password required to view panel status)
Front Panel Interface:
Display LD2100: green alphanumeric dot matrix Push Buttons LD2100: Test/Rest; LD5200: Up, down, right, left, enter LED Indicator LD1500: 1 tri-color Power/Status (green = power on; red = alarm; yellow = cable fault; LD2100: 1 bi-color Power/Status (green=power on, red=alarm)
Operating Environment:
Temperature 0° to 50°C (32° to 122°F) Humidity 5% to 95% RH non-condensing Altitude 15000 ft. (4572 m) max. Mounting Vertical wall mount (DIN rail mounting option available on LD2100 only) Agency Approvals CE; ETL listed: conforms to UL 61010-1, EN 61010-1; CSA C22.2; RoHS compliant,
FEATURES
Adjustable leak and contamination alarm thresholds to prevent false alarms
due to high humidity...high detection accuracy
RS-232 port allows conguration with PC
LD1500
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001796.B 0 1131
800.354.8556
RoHS
Compliant
Power supply (PS24-7.5W )
+1 503.598.4564
LD1500/LD2100 Basic SC Installation
www.veris.com
DIMENSIONAL DRAWINGSAPPLICATION/WIRING DIAGRAMS
LD15 00
7.0”
(176 mm)
Power supply (PS24-7.5W )
Cable
W B G R
Cable
W B G R
Leader Cable (LC-KIT) (included with LD1500 and LD2100)
Sensing Cable
(SC)
LD1500/LD2100 Basic SC-C Installation
Leader Cable (LC-KIT-M) (not included with LD1500 and LD2100)
Sensing Cable
(SC-C)
LD1500/LD2100 Basic SC-H Installation
End Terminator (EOL)
(included with LC-KIT)
End Terminator (EOL)
(included with LC-KIT-M)
3.7”
(94 mm)
LD2100
8.0”
(203 mm)
4.25”
(108 mm)
Power supply (PS24-7.5W )
Cable
W B G R
Leader Cable (LC-KIT-M) (not included with LD1500 and LD2100)
ORDERING INFORMATION
Sensing Cable
(SC-H)
End Terminator (EOL)
(included with LC-KIT-M)
C
T
N
I
L
LISTED
3037024
R
T
E
E
K
CM
US
D
I
S
E
T
MODEL MANUF. PART # DESCRIPTION
U006-0038* LD1500* Leak Panel, 1500’ Distance Read, Modbus, BACnet, SNMP, SMTP, and relay outputs
U006-0047* LD2100* Leak Panel, 2000’ Distance Read, Modbus, BACnet, SNMP, SMTP, and relay outputs
U006-0035†LC-KIT
U006-0061††LC-KIT-M
U006-0004 FM1114 Reference map, framed (11” x 14”)
* Power supply not included. Use LD-ENC (U006-0045) wall mount enclosure with built-in power supply or Veris PS24-7.5W power supply or equivalent.
Included with LD1500 and LD2100.
††
Not included with LD1500 or LD2100. Required for installation of SC-C ad SC-H cables.
††
Leader cable kit for SC cables (connects from leak panel to SC or NSC cable)
Leader cable kit for SC-C and SC-H cables (connects from leak panel to SC-C or SC-H cable)
LEAK DETECTION
HQ0001796.B 0 1131