Veris Hx21SP Datasheet

SENSED AMPS
100 to 300A (H221/H221SP) 300 to 800A (H321/H321SP) 1000 to 2400A (H421/H421SP)
0A *
4mA
20mA
SENSOR OUTPUT
*Adjusted with Span Potentiometer for Hx21 models;
Factory-set per customer specification for Hx21SP models
Hx & HxSPSERIES
VERIS INDUSTRIES
Current Sensors: 4-20mA Analog Output, High Current Monitoring
Large Load Trending With 4-20mA Output
DESCRIPTION
Hawkeye x21/x21SP analog current sensors provide reliable load trending information for large motor loads (up to 2400A), with a proportional 4-20mA signal. Three devices are available, each with a dierent amperage range. The Hx21 versions include a span potentiometer that allows each sensor to be calibrated for maximum resolution. The Hx21SP versions are factory-calibrated at a range specied by the customer.
APPLICATIONS
Load trending of large motors and other loads up to 2400 Amps
Monitor critical motors (compressor, fuel, etc.)
current monitoring
EXAMPLE LINEAR OUTPUT
Scale software as shown
TM
H321
FEATURES
Split-core design for easy installation and fast retrots
Large openings for heavy conductors
Loop powered 4-20mA output
Two-wire design reduces wiring cost
Hx21 models oer zero and span adjustments for eld exibility
Hx21SP models are factory-set at a range specied by the customer for easy
setup and high condence
100% solid state...no moving parts to fail
5-year warranty
SPECIFICATIONS
Sensor Power 30mA (max)@12-30VDC Insulation Class 60 0VAC RM S Frequency Range 50/60 H z Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH, non-condensing Accurac y ±2% from 10 to 100% of full scale Response Time 2 sec. Zero Adjustment nominal output@0A: 4mA ± 0.5 Terminal Block Maximum Wire Size 12 AWG (3.3 mm2) Terminal Block Torque 7 to 8 in-lbs (0.8 to 0.9 N-m) Agency Approvals UL 508 open device listing
Year
5
Warranty
Maximize Reliability
Minimize Installed Cost
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01763.B 01131
800.354.8556
H221
H
321
H421
A = 3.7" (94 mm) B = 1.6" (40 mm) C = 1.4" (35 mm) D = 1.1" (29 mm) E = 4.2" (106 mm) F = 4.7" (120 mm)
A = 4.9" (124 mm) B = 2.9" (75 mm) C = 2.5" (63 mm) D = 1.2" (29 mm) E = 5.5" (140 mm) F = 6.0" (151 mm)
A = 4.9" (124 mm) B = 5.5" (141 mm) C = 2.5" (65 mm) D = 1.1" (29 mm) E = 8.1" (206 mm) F = 6.0" (151 mm)
E150462
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWINGS
H221
H321
H421
APPLICATION/WIRING DIAGRAM
Monitoring Fan /Pump Motor Loads
CONTACTOR
+
-
12-30VDC Power Source
Fan or Pump
Motor
CONTROLLER
+
AI
ORDERING INFORMATION
MODEL AMPERAGE RANGE SENSOR OUTPUT HOUSING UL CE RoHS
H221
H221SP 100, 150, 200, 250, or 300A
H321 300 to 800A n
H321SP 300, 400, 500, 600, 700, or 800A
H421 1000 to 2400A
H421SP 1000, 1200, 1400, 1600, 1800, 2000, 2200, or 2400A
ACCESSORIES
Universal Power Supply (PS Series) Universal Mounting Bracket Kit (AH06)
HQ00 01763.B 01131
4mA (Lower Limit) 20mA (Upper Limit)
100 to 300A
2
0A
2
RoHS
Compliant
4-20mA DC Split-core
2
AH06PS
1
1
1
1
n n
n n
n n
n n
n
n
n
n
n
1
Listed for use on 75°C insulated conductors.
2
Standard factory-calibration, but no longer eld adjustable Note: When ordering HxxxSP versions, specify upper current limit for factory calibration (device is not eld adjustable).
current monitoring