Hx09 SERIES
VERIS INDUSTRIES
Current Switches:
Adjustable Trip Point,
High Voltage Output
Detect Belt Loss, Coupling
Shear, And Mechanical Failure
DESCRIPTION
Hawkeye x09 Series are high performance current switches, ideal for line voltage
loads. The devices are powered by the current being monitored.
APPLICATIONS
● Detecting belt loss, coupling shear, mechanical failure, and interlocking loads
● Verifying lighting circuit and other electrical service run times
● Monitoring status of industrial process equipment
● Monitoring status of critical motors (compressor, fuel, etc.)
current monitoring
DETECTS BELT LOSS/COUPLING SHEAR!
DETECTS BELT LOSS/COUPLING SHEAR!
Fan/pump
Calibrated
Trip Point
On
Electrical
Failure
TM
H909
H609H809
H709
FEATURES
● The H809 has a low (0.75 A) minimum setpoint...eliminates the need for
multiple wraps of the conductor through the sensor even on loads as
small as 1/5 HP
● H609 and H809 are small in size to t easily inside small starter enclosures
● Removable mounting bracket optimizes eld versatility
● Bracket on H909 can be installed in three dierent congurations...
added exibility
● Status LEDs for easy setup and local indication
● Adjustable trip point...precise current trip point setting
● Detect belt loss and mechanical failure...ideal for fan/pump status monitoring
● Easier to install than dierential pressure switches...eliminates long wiring runs
● 100% solid state...no moving parts to fail
● 5-year warranty
O O
Now you can easily detect when drive belts slip, break, or pump couplings shear.
In fact, a typical HVAC motor that loses its load has a reduction of current draw
of up to 50%. That’s why our sensors are the industry standard for status.
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Insulation Class 600VAC RMS
Frequency Range 50/60 H z
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% (typical)
Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage
Loss of Belt/Coupling Shear
Year
5
Warranty
Maximize Reliability
Minimize Installed Cost
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01755.B 01131
800.354.8556
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWINGS
H609 H809
Removable Mounting Bracket
0.6"
(16 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
(18 mm)
H709/H709H V H909/H909HV
Removable/Adjustable Mounting Bracket
0.7"
(19 mm)
0.7"
3.5"
(89 mm)
1.2"
(31 mm)
0.9"
(23 mm)
2.5" *
(64 mm)
1.0" *
(26 mm)
3.0" **
(75 mm)
Removable/Adjustable Mounting Bracket
0.7"
(18 mm)
0.4” x 0.2”
Slot (x2)
**3.1”
(79 mm)
1.1”
(26 mm)
(43 mm)
(58 mm)
Removable Mounting Bracket
1.7
2.3"
0.8”
(21 mm)
1.0”
(25 mm)
0.9"
(23 mm)
1.1" *
(27 mm)
Bracket can
be mounted
on three sides
for added
installation
exibility.
Self-gripping Iris
2.8" *
(71 mm)
APPLICATION/
WIRING DIAGRAM
CONTACTOR
9
Motor
CONTROLLER
DI
Fan or Pump
4.2"
(106 mm)
RANGE
2.8"
(68 mm)
3.8"
(95 mm)
1.1" *
(27 mm)
STATUS OUTPUT
(max.)
Ø 0.3”
(8 mm)
MIN. TRIP
POINT
3.0”
(76 mm)
RoHS
Compliant
STATUS LED HOUSING UL CE RoHS
n
n
n
n
0.2” x 0.15”
slot (2x)
ORDERING INFORMATION
MODEL AMPERAGE
H609 1.25 - 50A N.O. 0.2A@120VAC/DC 1.25A or less
H709 1 - 135A N.O. 0.2A@120VAC/DC 1.0A or less
H709HV 1 - 135A N .O. 1.0A@250VAC 1.0A or less Solid-core
H809 0.75 - 50A N.O. 0.2A@120VAC/DC 0.75A or less
H909 2.5 - 135A N.O. 0.2A@120VAC/DC 2.5A or less
H909HV 2.5 - 135A N .O. 1.0A@250VAC 2.5A or less Split-core
2.8”
(70 mm)
2.5”
(64 mm)
Split-core
Solid-core
Solid-core
Split-core
1.4”*
(36 mm)
n
n
n
n
current monitoring
1
1
n
n
n
1
Listed for use on 75°C insulated conductors.
n
ACCESSORIES
DIN Rail Clip Set (AH01)
DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01755.B 01131
AH01
AV02
AV01