Hx06 SERIES
VERIS INDUSTRIES
Current Switches: Adjustable
Trip Point
Detect Belt Loss, Coupling
Shear, And Mechanical Failure
DESCRIPTION
Hawkeye x06 Series solid- and split-core current switches provide accurate, reliable,
and maintenance-free fan and pump status indication.
APPLICATIONS
● Monitoring fans, pumps, motors, and other electrical loads for proper operation
● Detecting belt loss and motor failure...ideal for fan and pump status
● Verifying lighting circuit loads
● Monitoring critical motors (compressor, fuel, etc.)
● Monitoring industrial process equipment status (OEM)
DETECTS BELT LOSS/COUPLING SHEAR!
current monitoring
DETECTS BELT LOSS/COUPLING SHEAR!
Calibrated
Trip Point
, N.C. Output
Fan/pump
On
Electrical
Failure
H806
H606
H706
H906
FEATURES
● Adjustable trip point...4 amperage range options for versatility
● Easier to install than dierential pressure switches...no tubing needed
● 100% solid-state, no moving parts to fail
● Output status LEDs for fast setup
● Adjustable mounting bracket on the solid-core housing...easy placement
● Self-gripping iris on the split-core housing for easy installation
● Bracket on H906 can be installed in three dierent congurations...added
exibility
● 5-year warranty
TM
O O
Now you can easily detect when drive belts slip, break, or pump couplings shear.
In fact, a typical HVAC motor that loses its load has a reduction of current draw
of up to 50%. That’s why our sensors are the industry standard for status.
SPECIFICATIONS
Sensor Power 5-30VDC
Insulation Class 600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range 50/60 H z
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% Typical
O State Leakage 34μA@5VDC, 20 0µA@30VDC
On State Voltage Drop 1.9VDC max@0.1A
Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage
Loss of Belt/Coupling Shear
Year
5
Warranty
Maximize Reliability
Minimize Installed Cost
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01756.B 01131
800.354.8556
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWINGS
H606 H806
Removable Mounting Bracket
0.6"
(16 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
(18 mm)
H706
Removable/Adjustable Mounting Bracket
0.7"
(19 mm)
0.7"
3.5"
(89 mm)
1.2"
(31 mm)
2.5" *
(64 mm)
1.0" *
(26 mm)
0.9"
(23 mm)
3.0" **
(75 mm)
Removable/Adjustable Mounting Bracket
0.7"
(18 mm)
0.4” x 0.2”
Slot (x2)
**3.1”
(79 mm)
1.1”
(26 mm)
(43 mm)
(58 mm)
Removable Mounting Bracket
1.7
2.3"
H906
0.8”
(21 mm)
1.0”
(25 mm)
0.9"
(23 mm)
1.1" *
(27 mm)
Bracket can
be mounted
on three sides
for added
installation
exibility.
Self-gripping Iris
2.8" *
(71 mm)
APPLICATION/
WIRING DIAGRAM
Monitoring Fan /Pump Motors for
Positive Proof of Flow
CONTACTOR
-
POWER SOURCE
Fan or Pump
Motor
-
5-30VDC
+
+
DDC CONTROLLER
-
DI
+
4.2"
(106 mm)
2.8"
(68 mm)
3.8"
(95 mm)
1.1" *
(27 mm)
(8 mm)
0.2” x 0.15”
slot (2x)
ORDERING INFORMATION
MODEL AMPERAGE
RANGE
H606 1.25 - 50A
H706 1-135A 1.0A or less Solid-Core
H806 0.75 - 50A 0.75A or less Solid-Core
H906 2.5-135A 2.5A or less Split-Core
STATUS OUTPUT
(max.)
N.C. 0.1A@30VDC
MIN. TRIP
POINT
1.25A or less Split-Core
2.8”
(70 mm)
Ø 0.3”
(76 mm)
RoHS
Compliant
3.0”
2.5”
(64 mm)
1.4”*
(36 mm)
HOUSING STATUS LED UL CE RoHS
n
n n n
n n n n
n n n
n
1
n n
1
Listed for use on 75°C insulated conductors.
current monitoring
ACCESSORIES
DIN Rail Clip Set (AH01)
DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01756.B 01131
AH01
AV02
AV01