Veris Hx06 Datasheet

Hx06 SERIES
VERIS INDUSTRIES
Current Switches: Adjustable Trip Point
Detect Belt Loss, Coupling Shear, And Mechanical Failure
DESCRIPTION
Hawkeye x06 Series solid- and split-core current switches provide accurate, reliable, and maintenance-free fan and pump status indication.
APPLICATIONS
Monitoring fans, pumps, motors, and other electrical loads for proper operation
Detecting belt loss and motor failure...ideal for fan and pump status
Verifying lighting circuit loads
Monitoring critical motors (compressor, fuel, etc.)
Monitoring industrial process equipment status (OEM)
DETECTS BELT LOSS/COUPLING SHEAR!
current monitoring
DETECTS BELT LOSS/COUPLING SHEAR!
Calibrated
Trip Point
, N.C. Output
Fan/pump On
Electrical Failure
H806
H606
H706
H906
FEATURES
Adjustable trip point...4 amperage range options for versatility
Easier to install than dierential pressure switches...no tubing needed
100% solid-state, no moving parts to fail
Output status LEDs for fast setup
Adjustable mounting bracket on the solid-core housing...easy placement
Self-gripping iris on the split-core housing for easy installation
Bracket on H906 can be installed in three dierent congurations...added
exibility
5-year warranty
TM
O O
Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That’s why our sensors are the industry standard for status.
SPECIFICATIONS
Sensor Power 5-30VDC Insulation Class 600VAC RMS (UL), 300VAC RMS (CE) Frequency Range 50/60 H z Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH non-condensing Hysteresis 10% Typical O State Leakage 34μA@5VDC, 20 0µA@30VDC On State Voltage Drop 1.9VDC max@0.1A Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2) Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage
Loss of Belt/Coupling Shear
5
Warranty
Maximize Reliability
Minimize Installed Cost
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01756.B 01131
800.354.8556
E150462
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWINGS
H606 H806
Removable Mounting Bracket
0.6"
(16 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
(18 mm)
H706
Removable/Adjustable Mounting Bracket
 0.7"
(19 mm)
0.7"
3.5"
(89 mm)
1.2"
(31 mm)
2.5" *
(64 mm)
1.0" *
(26 mm)
0.9" (23 mm)
3.0" **
(75 mm)
Removable/Adjustable Mounting Bracket
 0.7" (18 mm)
0.4” x 0.2” Slot (x2)
**3.1”
(79 mm)
1.1”
(26 mm)
(43 mm)
(58 mm)
Removable Mounting Bracket
1.7
2.3"
H906
0.8”
(21 mm)
1.0”
(25 mm)
0.9"
(23 mm)
1.1" *
(27 mm)
Bracket can be mounted on three sides for added installation exibility.
Self-gripping Iris
2.8" *
(71 mm)
APPLICATION/ WIRING DIAGRAM
Monitoring Fan /Pump Motors for
Positive Proof of Flow
CONTACTOR
-
POWER SOURCE
Fan or Pump
Motor
-
5-30VDC
+
+
DDC CONTROLLER
-
DI
+
4.2"
(106 mm)
2.8"
(68 mm)
3.8"
(95 mm)
1.1" *
(27 mm)
(8 mm)
0.2” x 0.15” slot (2x)
ORDERING INFORMATION
MODEL AMPERAGE
RANGE
H606 1.25 - 50A
H706 1-135A 1.0A or less Solid-Core
H806 0.75 - 50A 0.75A or less Solid-Core
H906 2.5-135A 2.5A or less Split-Core
STATUS OUTPUT
(max.)
N.C. 0.1A@30VDC
MIN. TRIP
POINT
1.25A or less Split-Core
2.8”
(70 mm)
Ø 0.3”
(76 mm)
RoHS
Compliant
3.0”
2.5”
(64 mm)
1.4”*
(36 mm)
HOUSING STATUS LED UL CE RoHS
n
n n n
n n n n
n n n
n
1
n n
1
Listed for use on 75°C insulated conductors.
current monitoring
ACCESSORIES
DIN Rail Clip Set (AH01) DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01756.B 01131
AH01
AV02
AV01
Loading...