Veris Hx00 Datasheet

Hx00 SERIES
VERIS INDUSTRIES
Current Switches: Fixed
Split-Core & Solid-Core On/Off Status Current Switches
DESCRIPTION
Hawkeye x00 on/o current switches provide a cost-eective solution for monitoring status on unit vents, exhaust fans, recirculation pumps, and other xed loads where belt loss is not a concern.
Veris has applied new technology to the H300, H600, and H800 models to achieve impressive improvement in turn-on levels. The Hawkeye H300 and H600 now have the lowest turn-on current in the industry at a mere 150mA!
APPLICATIONS
Monitoring status of electrical loads
Monitoring direct-drive units, exhaust fans, process motors, and other xed
loads
Verifying lighting run times
current monitoring
Trip Point
0.15 A
TURN-ON!
(select
models)
TM
H300
H800
H600
US Patent No. 7,193,428
H900
FEATURES
More reliable for status than relays across auxiliary contacts
Ideal for direct-drive units, unit vents, fan coil units, exhaust fans, and other
Great for lighting status–less expensive than 277V relays
Low 0.15 A turn-on (H300 and H600)...ideal for small exhaust fans (not intended
to detect belt loss)
Removable mounting bracket provides installation exibility
Bracket on H900 can be installed in three dierent congurations...installer
convenience
Split-core H300, H600, and H900 for fast retrot installation
Mini solid-core H800 and micro split-core H300 t in tight enclosures...
saves valuable panel space
100% solid-state, no moving parts to fail
Polarity insensitive output
5-year warranty
Maximize Reliability
Minimize Installed Cost
Year
SPECIFICATIONS
Sensor Power N.O models: Induced from monitored current; H800NC: 5-30VDC, permanently connec ted Insulation Class 600VAC RMS (UL), 300VAC RMS (CE) Frequency Range 50/60 H z Temperature Range H800, H800NC, H300, H900: -15° to 60°C (5° to 140°F) H600: -15° to 40°C (5° to 104°F) (to 200A); -15° to 60°C (5° to 140°F) (to 150A) H800HV: - 40° to 50°C (-40° to 122°F) (to 200A); -40° to 75°C (-4 0° to 167°F) (to 100A, & 0.25A status output) Humidity Range 10-90% RH non-condensing O State Leakage (H800NC Only) 34μA@5VDC, 20 0μA@30VDC On State Voltage Drop (H800NC Only) 1.9VDC (max.) @0.1A Terminal Block Wire Size H600, H800, H90 0: 24-14 AWG (0.2 to 2.1 mm2); H300: 22-16 AWG (0.3 to 1.3 mm2) Terminal Block Torque H600, H800, H90 0: 3.5 to 4.4 in- lbs (0.4 to 0.5 N-m); H300: 7 in- lbs (0.8 N-m) Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
5
Warranty
Do not use the LED status indicators as evidence of applied voltage.
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01753.B 01131
800.354.8556
RoHS
Compliant
E150462
+1 503.598.4564
DIMENSIONAL DRAWINGS
H300
Removable Mounting Bracket
www.veris.com
H600
Removable Mounting Bracket
H800, H800HV, H800NC
Removable/Adjustable Mounting Bracket
0.3”
(8 mm)
6 AWG max.
Ø 0.18” (x2)
(5 mm)
1.5”
(38 mm)
1.8”
(46 mm)
1.6”
(40 mm)
0.6”
(15 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown.
APPLICATION/WIRING DIAGRAM
Unit Vent Heater Control
POWER SOURCE
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
0.6"
(16 mm)
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
BUILDING AUTOMATION
CONTROLLER
DI
DI
0.7"
(18 mm)
3.5"
(89 mm)
1.2"
(31 mm)
2.5" *
(64 mm)
1.0" *
(26 mm)
0.4” x 0.2” Slot (x2)
**3.1”
(79 mm)
Ø 0.3”
(8 mm)
 0.7" (18 mm)
Removable Mounting Bracket
1.1”
(26 mm)
1.7
(43 mm)
2.3"
(58 mm)
(21 mm)
(70 mm)
3.0”
(76 mm)
H900
0.8”
2.8”
2.5”
(64 mm)
1.0”
(25 mm)
0.9"
(23 mm)
(71 mm)
1.1" *
(27 mm)
Bracket can be mounted on three sides for added installation exibility.
Self-gripping Iris
1.4”*
(36 mm)
2.8" *
POWER SOURCE
UNIT VENT HEATER
ORDERING INFORMATION
MODEL AMPERAGE RANGE STATUS OUTPUT (max.) TRIP POINT HOUSING UL CE RoHS
H300 0.15 - 60A N.O. 1.0A@30VAC/DC 0.15A or less Split-core
H600 0.15 - 200A N.O. 1.0A@30VAC/DC 0.15A or less Split-core
H800 0.25 -200A N.O. 1.0A@30VAC/DC 0.25A or less Solid-core
H800NC 0.5 - 200A N.C. 0.1A@30VDC 0.5A or less Solid-core
H800HV 0.75 - 200A N.O. 0.5A@250VAC/DC 0.75A or less Solid- core
H900 1.5 - 200A N.O. 1.0A@30VAC/DC 1.5A or less Split-core
n
1
n
1
n
1
n
3
n
n n
n
n n
n n
ACCESSORIES
DIN Rail Clip Set (AH01 for H6xx, H8xx , H9x x; AH27 for H3xx) DIN Rail (AV01) and DIN Stop Clip (AV02)
AH27
HQ00 01753.B 01131
AH01
current monitoring
2
n
n
1
Listed for use on 75°C insulated conductors.
2
Product provides functional insulation only.
3
Listed for use on 90°C insulated conductors.