HWS SerieS HWS SerieS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
1.2"
(29 mm)
3.5"
(89 mm)
4.75"
(121 mm)
-+
Enter
ProDuct iDentification
environmental SenSorS
Wall Mount with Analog Setpoints, LCD Display,
1% NIST, 2% NIST, 2%, 3%, or 5%
Installer’s Specifications
Power Supply* 15 to 24VDC/24VAC, 100mA max.
Outputs, Analog Switch Selectable 4-20mA or 0-10V/0-5VDC (switch affec ts both outputs)
RH Sensor Digitally pr ofiled thin-film capacitive (32-bit mathematic s)
U.S. Patent 5,844,138
Accuracy at 2 5°C from 10-80% RH** ±2%, 3%, or 5% models
±1% at 20-50% RH (Multi-p oint calibration NIST traceable)
Reset Rate** * 24 hours
Stability ±1% @ 20°C (68°F) annually, for two years
Linearit y Included in Accuracy spec.
Operating Humidity Range 0-100% RH
Temperature Coeffic ient ±0.1%RH/°C above or below 25°C (typical)
Operating Temperature Range 10° to 35°C (50° to 95°F)
Scaling 0-100% RH
Calibration Offset Adjustable ±9.9% in 0.1% increments
Setpoint Range 10-80% RH in 1% increments
*One side of transformer seconda ry is connected to signal common, so an isolation transformer o r
dedicated power supply may be req uired.
**Specified accuracy with 24VDC supplied power with rising hum idity.
***Reset Rate is time required to recover to 50% RH after e xposure to 90% RH for 24 hours.
To maintain CE compliance the connected power sup ply must have a CE mark supporting LV + CE
directives.
inStallation GUiDe
RH Only Device
HWS
1 = 1%
N = NIST (1 & 2% only)
2 = 2%
X = No (2, 3, 5% only)
3 = 3%
5 = 5%
Dimensions
SetpointAccuracy NIST
= Analog
quick install
SA
Select a mounting location away from ventilation sources. The sensor should be 1.
mounted on a vertical wall, about 4 ½ feet above the floor.
Affix the backplate to the wall.2.
Wire the device. Refer to wiring diagram.3.
Install Cover. 4.
Z204453- 0D PAGE 1 ©2010 Veris Industries USA 800.354.8556 or 1.503.598.4564 / support@veris.com 06101
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
HWS SerieS
RH
YES
AMP VOLT
NO
RUN
CAL
–
Minus PlusEnter
+
POWER SUPPLY
24 VAC/DC
CONTROL SYSTEM
COMMON
RH INPUT
RH SETPOINT
PWR
COMMON
RH OUT
RH SETPOINT
RH
SENSOR
TEMP
SENSOR
RH
YES
AMPVOLT
NO
RUN
CAL
–
Minus PlusEnter
+
installation
1. Remove the cover by pressing the tab at the top of the sensor while pulling
outward from the top of the cover.
2. Remove the backplate by unfastening the sensor from the bottom of the backplate
and pivoting the sensor outward.
inStallation GUiDe
6. Wire the backplate.
Output (3-Wire, 0-10V, 4-20mA)
7. Install and configure the sensor.
3. Punch out openings in the backplate.
4. Position the sensor vertically on the wall, 4 ½ feet above the floor.
correct
incorrect
5. Mount the backplate onto the wall using the screws provided.
Five screwholes available; use a minimum of two for secure mounti ng.
WARNING: Output select must be
correct before applying p ower.
RH YES/NO JUMPER:
YES - allows user to change setpoint
(in humidistat mode)
NO - user can NOT change setpoint
(in humidistat mode)
RUN/CAL JUMPER:
CAL Mode - allows full access to all
features.
RUN Mode - allows access to
setpoint ONLY.
8. Install the cover and snap into place.