Veris HWS Datasheet

HT/HWS SERIES
Wall Mount Humidity Transmier Thermostat Humidistat Functions
VERIS INDUSTRIES
Independent RH, Temp, and Analog Setpoint Outputs
DESCRIPTION
All HT/HWS Series institutional grade relative humidity/temperature transmitters are designed to meet the rigorous needs of pharmaceutical labs, hospitals, science labs, and other settings that call for precise environmental control. Internal jumpers control access to a feature that allows adjustment of the calibration osets. The devices can also be made tamper resistant using a jumper to disable keypad programing functions. HT/HWS models are calibrated with NIST traceable calibration equipment.
Analog Output Transmitter
Analog output models feature a keypad to make adjusting humidity and temperature setpoint values easy. They transmit the setpoint values back to a control system by means of dual outputs. A slide-switch allows easy selection of output type, either 4-20mA or 0-5V/0-10VDC signals. Dual outputs enable eortless control of both humidity and temperature in a single, compact sensor.
Setpoint Relay Transmitter
setpoint devices
The HT Series setpoint relay models also oer thermostat or humidistat functionality. Two separate relays can be congured to control heating and cooling when in thermostat mode, or humidifying and de-humidifying when in humidistat mode.
HWS models oer the same precise humidity measurement and control as the HT, but without the temperature and thermostat features.
HT
APPLICATIONS
Hospitals and operating rooms, pharmaceutical labs
Clean rooms
Environmental testing facilities, and other institutional applications
FEATURES
Independent RH and T (HT relay) or analog setpoint outputs (HT analog)
provide application exibility
LCD for local display of readings and setup values
Oset function adjusts calibration inter vals for both RH and T (HT models)
Switch-selectable 4-20mA or 0-10V/0-5VDC analog outputs
Multi-point calibration to 1% RH, traceable to NIST
Replaceable RH sensor element supports eld calibration oset...saves time
Semiconductor temperature sensor can be eld calibrated
SPECIFICATIONS
Input Power 15 to 30VDC/24VAC, 100mA max. Outputs, Analog Switch-sele ctable 4-20mA, or 0-10V/0-5VDC (switch aec ts both outputs) Outputs, Relay (Relay models only) 2 Form C (SPDT), 1A 30VDC, resistive, 30W ma x. HS Element Digitally pr oled thin-lm capacitive (32-bit mathematic s) U.S. Patent 5,844,138† Accurac y at 25°C from 10-80% RH* (Multi-point cali bration NIST traceable) ±2%, 3%, or 5% models ; ±1% at 20-50% RH on HTA models ±1% at 12-40% RH on HTR models in mA out put mode; ±1% at 30% RH on HTR models in voltage output mode Reset Rate** 24 ho urs Stability ±1% @ 20°C (68° F) annually, for two years Hysteresis RH: 1.5% (typical), Temp: 1° to 10°F in 1°F increments Linearity Included in accuracy spec. Operating Humidity Range 0-100% RH non-condensing Temperature Coecient ± 0.1%RH/°C above or below 25°C (typical) Operating Temperature Range 10° to 35°C (50° to 95°F) Temperature Accuracy ±1.0°C (±1.8°F) Scaling RH: 0-100%; Temp: 10°to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F) menu selectable Calibration Oset RH: Adjustable ±10% in 0.1% increments; Temp: Adjustable ±10° in 0.1° increments Setpoint Range RH: 10-80% in 1% increments; Temp: minimum to full scale in 1°F increments
† The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty. * Specied accuracy with 24VDC supplied power with rising humidity **Reset Rate is time required to recover to 50% RH after exposure to 90% RH for 24 hours One side of transformer secondary is connected to signal common, so an isolation transformer or dedicated power supply may be required. RTD/Thermistors in wall packages are not compensated for internal heating of product.
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001872.B 01131
800.354.8556
RH
SENSOR
TEMP
SENSOR
RH
YES
AMPVOLT
NO YES
RUN
CAL
NO
TEMP
Minus PlusEnter
+
+1 503.598.4564
www.veris.com
APPLICATION/WIRING DIAGRAMS
HT Analog Option
Temp output
RH Setpoint output
Temp Setpoint output
Thermistor/RTD
Thermistor/RTD
Temp output
Thermistor/RTD
Thermistor/RTD
Heat/Hum. Alarm output
Comm Alarm output
Cool/De-Hum. Alarm output
POWER SOURCE
15 to 30VDC or 24VAC
DIGITAL CONTROL
Temp IN
RH setpoint IN
Temp setpoint IN
Thermistor/RTD IN Thermistor/RTD IN
POWER SOURCE
15 to 30VDC or 24VAC
DIGITAL CONTROL
RH IN
Temp IN Thermistor/RTD IN Thermistor/RTD IN
Heat/Humidify Alarm
Comm alarm
Cool/De-Humidify Alarm
+
-
-
-
RH IN
HT Relay Option
+
-
-
-
RH output
GND
RH output
GND
POWER SOURCE
15 to 30VDC or 24VAC
DIGITAL CONTROL
RH IN
RH setpoint IN
POWER SOURCE
15 to 30VDC or 24VAC
DIGITAL CONTROL
RH IN
Humidify Alarm
Alarm Comm
De-Humidify Alarm
HWS Analog Option
RH output
+
GND
-
-
-
HWS Relay Option
RH output
+
GND
-
-
-
RH Setpoint output
Humidify Alarm Alarm Comm De-Humidify Alarm
CONFIGURATION
DIMENSIONAL DRAWING
4.75"
(121 mm)
Enter
-+
3.5"
(89 mm)
1.2"
(29 mm)
ORDERING INFORMATION
RH/T Combination Device
Setpoint
A = Analog R = Relay
Accuracy
NIST
HT
N = NIST
1 = 1%
(1 & 2% only)
2 = 2%
X = No
3 = 3%
(2, 3, 5% only)
5 = 5%
Exam ple:
HT 2 N R S 1 H
HT Series devices contain both humidity and temperature transmitter outputs. Optional RTDs and thermistors are available.
ACCESSORIES
Replacement humidity element (HS) Replacement cover (AA53) Replacement housing (AA55)
HQ0001872.B 01131
Temp Cal
Certificate
S
= CE
0 = None 1 = 1 point Cal Ce rt 2 = 2 point Cal Ce rt
HS AA53 AA55
Option
B = 100R Platinu m, RTD C = 1k Plati num, RTD D = 10k T2, Thermist or E = 2 .2k, Thermistor F = 3k, T hermistor G = 10k CPC Ther mistor H = 10k T3, Thermi stor J = 10k Dale, Ther mistor K = 10k with 11k shunt, Ther mistor M= 20k NTC, Th ermistor N = 1800 ohm TAC, Thermistor Q = 1uA/C, Linitemp R = 10k US, Thermis tor S = 10 k 3A 221 T = 100k , Thermistor U = 20k “D”, Thermis tor W = 10k T2 high acc uracy, Thermist or Y = 10k T3 high acc uracy, Thermist or Z = 10k E1, Thermisto r
RH Only Device
Accuracy
NIST
HWS
1 = 1% 2 = 2% 3 = 3% 5 = 5%
N = NIST
(1 & 2% only) X = No (2, 3, 5% only)
Exam ple:
HWS 2 N R S
Setpoint
A = Analog R = Relay
setpoint devices