Veris HWPROTOCOL Datasheet

HW PROTOCOL SERIES
Deluxe Wall Humidity & Temperature Sensor, Protocol Communication
Modbus and BACnet
VERIS INDUSTRIES
Protocol Communication
DESCRIPTION
HW Protocol Series Deluxe humidity transmitters provide an ideal solution for measuring relative humidity in all conditions. All devices are equipped with a thin-lm capacitive sensor that is easily replaceable in the eld. These sensors are calibrated to NIST standards, with certicates available.
The HWLP features embedded BACnet and Modbus communication protocols with humidity and temperature sensing capability. The setpoint slider and pushbutton override oer additional local control.
The wall-mounted HWLP model features a low-prole housing with an LCD display for local indication. All models come with a standard ve-year warranty.
APPLICATIONS
Oce buildings, schools, or other systems utilizing BACnet or Modbus protocol
HUMIDITY
Embedded BACnet and Modbus communication protocols...compatible with
many existing control systems
Congurable to multiple baud rates
Humidity and temperature sensors in one device at one address...provides
more information and maximizes system capacity
Pushbutton override capability from the building control system...local control
in individual rooms to maximize comfort
Innovative self-calibration algorithm...maximizes performance
Field calibratable
Thin-lm capacitive sensor element recovers from 100% saturation
Fully interchangeable element to 1% or 2% accuracy...no calibration
Calibration-free interchangeable NIST traceable HS element
HS element is microprocessor proled with on-board nonvolatile memory
Multi-point digital calibration to NIST standards
NIST certication available
Replace element in the eld...minimizes eld calibration downtime
HWLP
SPECIFICATIONS
Input Power 12 to 30VDC, 24VAC; 100mA max. Housing Material High impac t ABS plastic , UL 94 VO
Communication:
Protocol BACnet or Modbus (selectable) Connection 2-wire RS- 485 Data Rate 9600, 19200, 38400, 57600 (Modb us), bps (selectable); 9600, 19200, 3840 0, 76800 (BACnet), bps (selectable) Parity None/Odd/Even (selectable-Modbus); None (BACnet) Address Range 1-127
Humidity:
HS Element Replaceable digitally proled thin-lm c apacitive; (32-bit mathematics); U.S. Patent 5,84 4,138 † Accurac y* ±2% from 10 to 80% RH; NIST traceable multi-point calibration Reset Rate** 24 ho urs Stability ±1 @20°C (68°F) annually for two years Hysteresis 1.5% typical Operating Humidity Range 0 to 100% RH noncondensing Operating Temperature Range 10° to 35°C (50° to 95°F) Temperature Coecient ±0.1% RH/ °C above or below 25°C (typical)
Operating Environment:
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Transmitter Option:
Sensor Type Solid-state, integrated circuit Accurac y ±0.5°C (±1°F) typical Resolution 0.1°C (0.2°F) Range 10° to 35°C (50° to 95°F)
Setpoint Slider Resolution Option 1% full scale Override Button Option Remotely readable and resettable
† The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty. * Specied accuracy with 24VDC supplied power with rising humidity.
** Reset rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours. Note: RTD/Thermistors in wall packages are not compensated for internal heating of product. EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC. EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2007 specication requirements)
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001723.B 01131
800.354.8556
+1 503.598.4564
+
-
www.veris.com
DIMENSIONAL DRAWINGAPPLICATION/WIRING DIAGRAM
POWER SUPPLY
12-30VDC, 24VAC
CONTROL SYSTEM
COMMON
-
RS-485+ RS-485 ­SHIELD
GND
PWR
RS-485+
RS-485-
SHIELD
BACNET DESCRIPTIONS
Standard Object Types Suppor ted
OBJECT TYPE SUPPORTED OPTIONAL
PROPERTIES
Analog Input -- AI Description*, Reliability
Analog Value -- AV Description* Present_Value
Binary Value – BV Description* Present_Value
Device -- DEV Description*, Location APDU_Timeout, Description, Location,
* Description is the same as the O bject_Identier. Reliability is “No Se nsor ” if no sensor is installed (applies to humidity, temperature, and slider).
Device Objects Table
OBJECT
NAME
HWxPxxx
TYPE &
INSTANCE
Device
133nnn
OBJECT
PROPERTY
Object_Identier
(R/W)
Object_Name
(R/W)
APDU_Timeout Default is 3000, maximum value is 60000
Max_Master Default is 127
Description Maximum length is 64 characters
Location Maximum length is 64 characters
WRITABLE PROPERTIES
Max_Master, Object_Identier, Object_Name
DESCRIPTION
Unique value where nnn initially is MS/TP
Unique name, initially a combination of
model and serial number. Maximum length is 64 characters
4.8"
(122 mm)
3.5"
(89 mm)
1.2"
(30 mm)
Objects Table
OBJECT
NAME
TYPE &
INSTANCE
DESCRIPTION OF PRESENT_VALUE PROPERTY
Humidity AI 1 Humidity in percent
Temperature AI 2 Temperature in Fahrenheit or Celsius
Slider AI 3 Slider position in percent.
Device_
Instance
AV 1 Alternative way to change object_identier property of
device. A negative value will restore the default device instance (133nnn). Fractional values are truncated.
Temp_
Oset
AV 2 Temperature oset. Value rounded to nearest tenth of a
degree. Units are current units. Initial value is zero.
RH_Oset AV 3 Relative Humidity oset. Value rounded to the nearest tenth
of a percent. Initial value is zero.
Fahrenheit BV 1 1 if temperature in Fahrenheit, 0 if in Celsius. Initially 1
Override BV 2 1 if override button pressed. Store 0 to reset. Initially 0.
Volatile
HUMIDITY
ORDERING INFORMATION
Local Display
HW
L = LCD X = No Display
HW L P H T X 3
Protocol
= Protocol
Example:
RH Option
P
1 = RH 1% NIST 2 = RH 2% NIST H = RH 2%
ACCESSORIES
Replacement humidity element (HS) Handheld digital hygrometer/psychrometer (597C1) Replacement covers for wall uni ts (AA51, AA51B, AA52, AA52B) Replacement cloud white wall h ousing (AA55)
HQ0001723.B 01131
Temp. Option
X = No temp. T = Temp. transmitter
Temp. Cal. Cert.
X = None 1 = 1 pt. cal. cer t.* 2 = 2 pt. cal. cer t.* 3 = 3 pt. cal. cer t.*
* Only available if temperature option is selected.
HS597C1
Option
Blank = None 1 = Pushbut ton override 2 = Set point slider 3 = Pushbut ton override
+ set point s lider
AA55
Housing
Blank = Cloud white B = Black
AA51/AA51B AA52/AA52B
Loading...