![](/html/c4/c4a8/c4a85daab5693ebfd59a9b90c7b0cc5e7c01804d7fc0aa1d6d8be2d0dc83b45c/bg1.png)
HW PROTOCOL SERIES
Deluxe Wall Humidity &
Temperature Sensor,
Protocol Communication
Modbus and BACnet
VERIS INDUSTRIES
Protocol Communication
DESCRIPTION
HW Protocol Series Deluxe humidity transmitters provide an ideal solution for
measuring relative humidity in all conditions. All devices are equipped with a
thin-lm capacitive sensor that is easily replaceable in the eld. These sensors are
calibrated to NIST standards, with certicates available.
The HWLP features embedded BACnet and Modbus communication protocols with
humidity and temperature sensing capability. The setpoint slider and pushbutton
override oer additional local control.
The wall-mounted HWLP model features a low-prole housing with an LCD display
for local indication. All models come with a standard ve-year warranty.
APPLICATIONS
● Oce buildings, schools, or other systems utilizing BACnet or Modbus protocol
HUMIDITY
FEATURES
● Embedded BACnet and Modbus communication protocols...compatible with
many existing control systems
● Congurable to multiple baud rates
● Humidity and temperature sensors in one device at one address...provides
more information and maximizes system capacity
● Pushbutton override capability from the building control system...local control
in individual rooms to maximize comfort
● Innovative self-calibration algorithm...maximizes performance
†
● Field calibratable
● Thin-lm capacitive sensor element recovers from 100% saturation
● Fully interchangeable element to 1% or 2% accuracy...no calibration
● Calibration-free interchangeable NIST traceable HS element
● HS element is microprocessor proled with on-board nonvolatile memory
● Multi-point digital calibration to NIST standards
● NIST certication available
● Replace element in the eld...minimizes eld calibration downtime
HWLP
SPECIFICATIONS
Input Power 12 to 30VDC, 24VAC; 100mA max.
Housing Material High impac t ABS plastic , UL 94 VO
Communication:
Protocol BACnet or Modbus (selectable)
Connection 2-wire RS- 485
Data Rate 9600, 19200, 38400, 57600 (Modb us), bps (selectable); 9600, 19200, 3840 0, 76800 (BACnet), bps (selectable)
Parity None/Odd/Even (selectable-Modbus); None (BACnet)
Address Range 1-127
Humidity:
HS Element Replaceable digitally proled thin-lm c apacitive; (32-bit mathematics); U.S. Patent 5,84 4,138 †
Accurac y* ±2% from 10 to 80% RH; NIST traceable multi-point calibration
Reset Rate** 24 ho urs
Stability ±1 @20°C (68°F) annually for two years
Hysteresis 1.5% typical
Operating Humidity Range 0 to 100% RH noncondensing
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Coecient ±0.1% RH/ °C above or below 25°C (typical)
Operating Environment:
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Transmitter Option:
Sensor Type Solid-state, integrated circuit
Accurac y ±0.5°C (±1°F) typical
Resolution 0.1°C (0.2°F)
Range 10° to 35°C (50° to 95°F)
Setpoint Slider Resolution Option 1% full scale
Override Button Option Remotely readable and resettable
† The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.
* Specied accuracy with 24VDC supplied power with rising humidity.
** Reset rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
Note: RTD/Thermistors in wall packages are not compensated for internal heating of product.
EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2007 specication requirements)
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001723.B 01131
![](/html/c4/c4a8/c4a85daab5693ebfd59a9b90c7b0cc5e7c01804d7fc0aa1d6d8be2d0dc83b45c/bg2.png)
800.354.8556
+1 503.598.4564
+
-
www.veris.com
DIMENSIONAL DRAWINGAPPLICATION/WIRING DIAGRAM
POWER SUPPLY
12-30VDC, 24VAC
CONTROL SYSTEM
COMMON
-
RS-485+
RS-485 SHIELD
GND
PWR
RS-485+
RS-485-
SHIELD
BACNET DESCRIPTIONS
Standard Object Types Suppor ted
OBJECT TYPE SUPPORTED OPTIONAL
PROPERTIES
Analog Input -- AI Description*, Reliability
Analog Value -- AV Description* Present_Value
Binary Value – BV Description* Present_Value
Device -- DEV Description*, Location APDU_Timeout, Description, Location,
* Description is the same as the O bject_Identier. Reliability is “No Se nsor ” if no sensor is
installed (applies to humidity, temperature, and slider).
Device Objects Table
OBJECT
NAME
HWxPxxx
TYPE &
INSTANCE
Device
133nnn
OBJECT
PROPERTY
Object_Identier
(R/W)
Object_Name
(R/W)
APDU_Timeout Default is 3000, maximum value is 60000
Max_Master Default is 127
Description Maximum length is 64 characters
Location Maximum length is 64 characters
WRITABLE PROPERTIES
Max_Master, Object_Identier,
Object_Name
DESCRIPTION
Unique value where nnn initially is MS/TP
Unique name, initially a combination of
model and serial number. Maximum
length is 64 characters
4.8"
(122 mm)
3.5"
(89 mm)
1.2"
(30 mm)
Objects Table
OBJECT
NAME
TYPE &
INSTANCE
DESCRIPTION OF PRESENT_VALUE PROPERTY
Humidity AI 1 Humidity in percent
Temperature AI 2 Temperature in Fahrenheit or Celsius
Slider AI 3 Slider position in percent.
Device_
Instance
AV 1 Alternative way to change object_identier property of
device. A negative value will restore the default device
instance (133nnn). Fractional values are truncated.
Temp_
Oset
AV 2 Temperature oset. Value rounded to nearest tenth of a
degree. Units are current units. Initial value is zero.
RH_Oset AV 3 Relative Humidity oset. Value rounded to the nearest tenth
of a percent. Initial value is zero.
Fahrenheit BV 1 1 if temperature in Fahrenheit, 0 if in Celsius. Initially 1
Override BV 2 1 if override button pressed. Store 0 to reset. Initially 0.
Volatile
HUMIDITY
ORDERING INFORMATION
Local Display
HW
L = LCD
X = No Display
HW L P H T X 3
Protocol
= Protocol
Example:
RH Option
P
1 = RH 1% NIST
2 = RH 2% NIST
H = RH 2%
ACCESSORIES
Replacement humidity element (HS)
Handheld digital hygrometer/psychrometer (597C1)
Replacement covers for wall uni ts (AA51, AA51B, AA52, AA52B)
Replacement cloud white wall h ousing (AA55)
HQ0001723.B 01131
Temp. Option
X = No temp.
T = Temp. transmitter
Temp. Cal. Cert.
X = None
1 = 1 pt. cal. cer t.*
2 = 2 pt. cal. cer t.*
3 = 3 pt. cal. cer t.*
* Only available if temperature
option is selected.
HS597C1
Option
Blank = None
1 = Pushbut ton override
2 = Set point slider
3 = Pushbut ton override
+ set point s lider
AA55
Housing
Blank = Cloud white
B = Black
AA51/AA51B AA52/AA52B